ABB CM-PVS.41P three-phase monitoring relay 1SVR740794R3300 for 300–500 V AC systems with adjustable overvoltage and undervoltage monitoring, phase failure and selectable phase-sequence monitoring, adjustable tripping delay and two changeover outputs.
£158.67
The ABB CM-PVS.41P is a professional three-phase monitoring relay designed to supervise critical voltage and phase conditions in industrial three-phase electrical systems. Supplied under ABB order code 1SVR740794R3300, it monitors overvoltage, undervoltage, phase failure and phase sequence, helping protect motors, machinery and electrical equipment against unsuitable supply conditions.
The CM-PVS.41P operates directly from the monitored supply across a 3 × 300–500 V AC line-to-line measuring range. Its overvoltage and undervoltage threshold values are adjustable as absolute values, while phase-sequence monitoring can be switched off when it is not required. The relay uses a TRMS measuring principle for dependable voltage supervision.
A selectable ON- or OFF-delayed tripping function can operate instantaneously or with an adjustable 0.1–30 s delay. Two changeover (SPDT) output contacts rated at 250 V / 4 A, three status LEDs and maintenance-free Easy Connect push-in terminals provide straightforward integration into industrial control and protection circuits.
The ABB CM-PVS.41P continuously evaluates a three-phase supply for overvoltage, undervoltage, phase failure and phase-sequence faults. Its adjustable voltage thresholds allow the permitted operating window to be matched to the connected equipment, while the selectable phase-sequence function provides additional flexibility where rotational direction monitoring is required.
When a monitored condition moves outside the configured limits, the relay can switch its outputs immediately or after the selected 0.1–30 s delay. Selectable ON- and OFF-delay behaviour allows the response to be adapted to the application, making the CM-PVS.41P suitable for protecting motors, pumps, compressors, machinery and other equipment supplied from 300–500 V AC three-phase networks.
Tick the specs you need, then view products that match.
| Time Delay | Adjustable | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Signal / Input Range | 3 × 300–500 V AC | |
| Monitoring Function | Three-phase supply | |
| Series | CM-PVS | |
| ABB order code | 1SVR740794R3300 | |
| Product group | 310921-Measuring & Monitoring Relays | |
| Product type | Three-phase monitoring relay | |
| Monitoring functions | Overvoltage, undervoltage, phase failure and phase sequence | |
| Measuring range | 3 × 300–500 V AC line-to-line | |
| Rated control supply voltage | 3 × 300–500 V AC | |
| Supply | Powered by the measuring circuit | |
| Rated frequency | 50/60 Hz | |
| Measuring principle | TRMS | |
| Voltage thresholds | Overvoltage and undervoltage, adjustable as absolute values | |
| Phase-sequence monitoring | Selectable | |
| Start-up delay | 200 ms | |
| Tripping delay | 0 s or 0.1–30 s, adjustable | |
| Tripping-delay function | ON-delay or OFF-delay, selectable | |
| Outputs | 2 changeover (SPDT) contacts | |
| Contact rating | 250 V / 4 A | |
| Maximum output circuit operating voltage UL/CSA | 300 V AC | |
| UL/CSA contact rating | B300 | |
| Status indication | 3 LEDs | |
| Connection technology | Easy Connect push-in / screwless terminals | |
| Protection rating | Housing IP50, terminals IP20 | |
| Operating temperature | -25 to +60 °C | |
| Storage temperature | -40 to +85 °C | |
| Mounting | DIN rail | |
| Dimensions (W × H × D) | 22.5 × 85.6 × 103.7 mm | |
| Net weight | 0.131 kg | |
| EAN | 4016779852029 |
The CM-PVS.41P monitors overvoltage, undervoltage, phase failure and phase sequence in three-phase AC electrical systems.
The CM-PVS.41P is designed for a 3 × 300–500 V AC line-to-line measuring range, with the monitored voltage also powering the relay.
Yes. The CM-PVS.41P provides adjustable overvoltage and undervoltage thresholds set as absolute voltage values.
Yes. The relay supports instantaneous 0 s operation or an adjustable 0.1–30 s tripping delay, with selectable ON- or OFF-delay behaviour.
The CM-PVS.41P provides two changeover (SPDT) output contacts rated at 250 V / 4 A for connection to contactors, alarms and control circuits.
ABB CM-PVS three-phase monitoring relays provide dependable supervision of overvoltage, undervoltage, phase failure and phase sequence, combining adjustable thresholds, configurable tripping behaviour and compact DIN rail installation for industrial three-phase systems.