Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CM-PVS.81P (1SVR740794R2300) three-phase monitoring relay for 200–400 V AC line-to-line supplies. Features adjustable overvoltage and undervoltage thresholds, phase failure detection, selectable phase sequence monitoring, true RMS measurement, adjustable 0 or 0.1–30 second tripping delay, two changeover contacts rated at 250 V / 4 A and Easy Connect push-in terminals.
£158.67
The ABB CM-PVS.81P (1SVR740794R2300) is a versatile industrial three-phase monitoring relay designed to supervise the voltage and phase conditions of three-phase AC power supplies. Part of ABB's CM-PVS measuring and monitoring relay range, it combines phase failure detection, selectable phase sequence monitoring, adjustable overvoltage monitoring and adjustable undervoltage monitoring in one compact device.
Operating across a 200–400 V AC line-to-line measuring and supply range, the CM-PVS.81P is powered directly by the monitored three-phase circuit. Its independently adjustable upper and lower voltage thresholds allow the relay to be configured for the acceptable voltage limits of connected machinery and industrial equipment. The true RMS (TRMS) measuring principle provides effective AC voltage evaluation.
The CM-PVS.81P features two changeover (SPDT) output contacts rated at 250 V / 4 A, a selectable instantaneous or 0.1–30 s tripping delay, and ON-delayed or OFF-delayed operation. With ABB Easy Connect push-in terminals, three LED status indicators and a compact 22.5 mm DIN rail housing, it is well suited to industrial motor control, electrical distribution, machinery automation and supply fault signalling.
The ABB CM-PVS.81P continuously supervises a compatible three-phase AC supply by measuring the voltages between L1, L2 and L3.
Phase failure monitoring helps detect the loss of a supply phase. This is important in industrial motor installations, where phase loss can result in abnormal current distribution, reduced torque, overheating and possible equipment damage.
Phase sequence monitoring helps identify incorrect phase rotation. Reversed phase rotation can cause three-phase motors to turn in the wrong direction, potentially affecting pumps, fans, conveyors, compressors and other direction-sensitive equipment.
The phase sequence monitoring function can be disabled where phase rotation supervision is not required.
In addition to phase-related faults, the CM-PVS.81P provides overvoltage and undervoltage monitoring to detect conditions outside the configured acceptable voltage range.
These monitoring functions make the CM-PVS.81P suitable for industrial applications requiring more comprehensive three-phase supervision than a basic phase failure relay.
The CM-PVS.81P features independently adjustable upper and lower voltage thresholds, allowing the acceptable operating voltage range to be configured for the installation.
Unlike three-phase monitoring relays with fixed percentage-based thresholds, the CM-PVS.81P allows the overvoltage and undervoltage response levels to be set as absolute voltage values.
The relay operates across a 200–400 V AC line-to-line measuring range. The configured thresholds must be selected within the device's permitted adjustment limits and should reflect the operating requirements of the connected equipment.
When the measured voltage exceeds the configured upper threshold or falls below the lower threshold, the relay changes its output state according to the selected timing and operating configuration.
This adjustable-threshold design is useful where equipment requires application-specific voltage limits rather than a fixed tolerance around a nominal supply voltage.
The ABB CM-PVS.81P uses a true RMS (TRMS) measuring principle to evaluate the monitored AC voltage.
True RMS measurement considers the effective value of the voltage waveform, providing a suitable basis for monitoring AC electrical supplies.
The relay is powered directly by the monitored three-phase circuit, meaning the measuring voltage also serves as the control supply.
This arrangement simplifies wiring because a separate auxiliary supply connection is not required.
The CM-PVS.81P is designed for three-phase AC installations with line-to-line voltages within its specified 200–400 V AC range. It should not be connected directly to a supply exceeding its rated operating limits.
The CM-PVS.81P provides a selectable instantaneous tripping setting of 0 s or an adjustable delay from 0.1–30 s.
This flexibility allows the relay to be configured for different monitoring requirements. An instantaneous setting supports rapid fault signalling, while a suitable delay can help prevent unnecessary switching caused by brief supply disturbances.
The device also supports selectable ON-delayed or OFF-delayed tripping, providing additional control over the output response.
A specified 200 ms start-up delay is included in the relay's operating characteristics.
The selected tripping delay should reflect the requirements of the connected equipment. Where rapid fault detection is essential, an unnecessarily long delay may be unsuitable.
The ABB CM-PVS.81P provides two changeover (SPDT) output contacts, each suitable for switching within the device's specified ratings.
The output contact rating is 250 V / 4 A, allowing the relay to be integrated into compatible industrial control and signalling circuits.
Typical applications include signalling abnormal supply conditions to PLC inputs, activating industrial alarm circuits and participating in suitably designed motor contactor control arrangements.
The two changeover contacts provide flexibility where more than one compatible control or signalling function is required.
The CM-PVS.81P is a monitoring device rather than a replacement for correctly rated motor overload protection, circuit breakers or other protective equipment required by the electrical installation.
The CM-PVS.81P uses ABB's Easy Connect Technology, featuring screwless push-in terminals for efficient electrical panel wiring.
The spring-clamp terminal design supports maintenance-free electrical connections when installed with suitable conductors according to ABB's wiring instructions.
Its compact dimensions of 85.6 × 22.5 × 103.7 mm allow the relay to occupy only 22.5 mm of DIN rail width.
Three LED indicators provide information about operating and output states, while front-mounted controls allow adjustment of voltage thresholds and tripping delay settings.
The relay is designed for operation at ambient temperatures from −25 to +60 °C, with an IP50 housing and IP20 terminals.
An optional sealable transparent cover is available to help prevent unauthorised changes to the configured settings.
Tick the specs you need, then view products that match.
| Monitoring Function | Three-phase supply | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Signal / Input Range | 200–400 V AC | |
| Time Delay | Adjustable |
The ABB CM-PVS.81P is a three-phase monitoring relay used to detect phase failure, incorrect phase sequence, overvoltage and undervoltage in compatible three-phase AC electrical systems.
The CM-PVS.81P, ABB order code 1SVR740794R2300, operates from a 3 × 200–400 V AC three-phase supply at 50/60 Hz. It is powered directly by the monitored electrical circuit.
The relay has a specified 200–400 V AC line-to-line measuring range. Its measuring voltage and control supply are derived from the same three-phase circuit.
No. The CM-PVS.81P monitors the three-phase supply through the L1, L2 and L3 terminals. A neutral connection is not required for its standard monitoring arrangement.
Yes. The relay provides phase failure monitoring, helping identify the loss of a supply phase so the connected control system can respond.
Yes. The CM-PVS.81P includes selectable phase sequence monitoring. When enabled, it detects incorrect phase rotation in the monitored three-phase supply.
Yes. The CM-PVS.81P provides independently adjustable overvoltage and undervoltage thresholds. Both thresholds are set as absolute voltage values within the relay's permitted adjustment range.
Yes. The relay uses a true RMS (TRMS) measuring principle to evaluate the effective voltage of the monitored three-phase AC supply.
The relay supports 0 s operation or an adjustable tripping delay from 0.1–30 s. ON-delayed and OFF-delayed tripping modes are selectable.
The relay provides two changeover (SPDT) output contacts rated at 250 V / 4 A. These contacts can be used for compatible PLC inputs, alarms and industrial control circuits.
Both models provide 200–400 V AC monitoring, adjustable overvoltage and undervoltage thresholds, phase failure detection, selectable phase sequence monitoring and two changeover contacts. The main difference is the terminal technology: the CM-PVS.81P uses push-in terminals, while the CM-PVS.81S uses screw terminals.
The CM-PVS.81P has a 200–400 V AC line-to-line range, while the CM-PVS.31P has a 160–300 V AC line-to-line range. Both provide adjustable voltage thresholds, phase failure detection, selectable phase sequence monitoring and push-in terminals.
The CM-PVS.81P is designed for 200–400 V AC line-to-line supplies, while the CM-PVS.41P is designed for 300–500 V AC line-to-line supplies. The appropriate model should be selected according to the installation voltage and required threshold settings.
The CM-PVS.81P has an upper rated measuring and supply limit of 400 V AC line-to-line. A nominal 400 V AC installation may experience normal positive voltage variations above this limit, so the CM-PVS.41P, rated for 300–500 V AC, is generally the more appropriate model to evaluate for such installations.
The relay uses ABB Easy Connect push-in terminals, providing screwless spring-clamp electrical connections for efficient installation.
The relay is designed for DIN rail mounting inside industrial motor control panels, machinery cabinets and electrical distribution enclosures. Its compact 22.5 mm housing width helps conserve installation space.
ABB CM-PVS three-phase monitoring relays provide dependable electrical supply supervision for industrial machinery, motor control and distribution applications. With phase failure detection, selectable phase sequence monitoring, adjustable overvoltage and undervoltage thresholds, true RMS measurement and configurable tripping delays, the CM-PVS.81P offers a flexible solution for monitoring compatible 200–400 V AC three-phase systems. Its two changeover contacts, Easy Connect push-in terminals and compact DIN rail housing support efficient integration into industrial automation installations.
Technical references: ABB CM-PVS.81 Technical Datasheet (2CDC112202D0201), ABB Official Product Catalogue – 1SVR740794R2300 and ABB CM-PVS.81P Product Information. Verify the latest ABB technical documentation, permissible supply voltage, threshold settings and contact ratings before installation or commissioning.