ABB CM-PVS.31P three-phase monitoring relay for 160–300 V AC line-to-line supplies. Features adjustable overvoltage and undervoltage thresholds, phase failure detection, selectable phase sequence monitoring, true RMS measurement, adjustable tripping delay from 0 or 0.1–30 seconds, two changeover contacts rated at 250 V / 4 A and Easy Connect push-in terminals.
£158.67
The ABB CM-PVS.31P (1SVR740794R1300) is an industrial three-phase monitoring relay designed to supervise the quality and availability of three-phase AC power supplies. Part of ABB's CM-PVS measuring and monitoring relay range, it combines phase failure detection, selectable phase sequence monitoring, adjustable overvoltage monitoring and adjustable undervoltage monitoring in one compact device.
Designed for a 160–300 V AC line-to-line measuring and supply range, the CM-PVS.31P is powered directly from the monitored three-phase circuit, eliminating the need for a separate auxiliary power supply. Its independently adjustable upper and lower voltage thresholds provide greater flexibility than fixed-threshold monitoring relays, allowing the device to be configured for the voltage limits required by the installation.
The relay uses a true RMS (TRMS) measuring principle and provides an adjustable 0 s or 0.1–30 s tripping delay, with selectable ON-delayed or OFF-delayed operation. With two changeover (SPDT) contacts rated at 250 V / 4 A, three LED status indicators, ABB Easy Connect push-in terminals and a compact 22.5 mm DIN rail housing, the CM-PVS.31P is well suited to industrial motor control, machinery and electrical distribution applications.
The ABB CM-PVS.31P continuously supervises the electrical conditions of a compatible three-phase AC supply. By monitoring the voltages between L1, L2 and L3, it helps identify abnormal conditions that may affect connected machinery and industrial equipment.
Phase failure monitoring detects the loss of a supply phase. This is particularly important for three-phase motors, where a missing phase can result in reduced torque, abnormal current distribution, increased heating and possible equipment damage.
Phase sequence monitoring helps detect incorrect phase rotation. Incorrect phase rotation may cause motors to operate in the wrong direction, which can be problematic for pumps, fans, conveyors, compressors and other direction-sensitive machinery.
The phase sequence function can be disabled where phase rotation monitoring is not required, providing additional flexibility during commissioning.
In addition to phase-related faults, the CM-PVS.31P supervises overvoltage and undervoltage, helping detect supply conditions outside the configured acceptable operating range.
One of the main advantages of the CM-PVS.31P is its ability to monitor voltage using adjustable upper and lower thresholds.
Unlike fixed-threshold three-phase monitoring relays, the CM-PVS.31P allows the overvoltage and undervoltage limits to be set as absolute voltage values within the device's specified range.
The relay is designed for 160–300 V AC line-to-line systems. The selected thresholds should reflect the acceptable operating voltage limits of the connected equipment and the requirements of the complete electrical installation.
When the monitored voltage rises above the upper threshold or falls below the lower threshold, the relay provides a switching response according to the selected tripping delay and operating configuration.
This adjustable-threshold design is particularly useful where equipment requires tighter voltage supervision or where a fixed ±10% tolerance would not be suitable.
The CM-PVS.31P uses a true RMS measuring principle to evaluate the monitored AC voltages.
True RMS measurement considers the effective value of the AC voltage waveform rather than relying solely on its peak value. This provides a suitable basis for voltage supervision in industrial electrical systems.
The measuring and control supply are derived from the same three-phase circuit, so the relay does not require a separate auxiliary power connection.
The CM-PVS.31P is intended for three-phase AC systems with line-to-line voltages within 160–300 V. It should not be used directly on higher-voltage networks outside its rated measuring and supply range.
The ABB CM-PVS.31P features an adjustable tripping delay that can be switched off for 0 s operation or set between 0.1 and 30 s.
This allows the relay's response to be tailored to the installation. Where rapid fault signalling is required, an instantaneous setting can be selected. Where brief voltage disturbances are expected, an appropriate delay may help prevent unnecessary switching.
The device also supports selectable ON-delayed or OFF-delayed tripping, allowing the switching behaviour to be configured for the monitoring application.
A 200 ms start-up delay is included in the relay's operating characteristics.
These timing functions help the CM-PVS.31P integrate with industrial control circuits, but the delay setting must be selected carefully where the monitored equipment is sensitive to voltage or phase faults.
The CM-PVS.31P provides two changeover (SPDT) output contacts rated at 250 V / 4 A.
These contacts can be used to provide switching signals to compatible motor control circuits, PLC inputs, industrial alarms and other electrical monitoring equipment.
The availability of two changeover contacts allows the monitored supply condition to be integrated into more than one suitable control or signalling circuit, subject to the applicable electrical ratings.
The CM-PVS.31P is a monitoring relay and does not replace correctly rated motor protection circuit breakers, short-circuit protective devices or other equipment required by the installation.
The ABB CM-PVS.31P uses Easy Connect Technology, featuring screwless push-in terminals that simplify electrical panel wiring.
The spring-clamp connection system provides secure, maintenance-free electrical connections when installed using compatible conductors and ABB's recommended wiring procedures.
With dimensions of 85.6 × 22.5 × 103.7 mm, the relay occupies only 22.5 mm of DIN rail width, helping conserve space in industrial control cabinets.
Three LED indicators provide convenient information about operating and output states. Front-mounted adjustment controls allow configuration of the voltage thresholds, phase sequence monitoring and tripping delay.
An optional sealable transparent cover is available to help prevent unauthorised changes to the configured settings.
Tick the specs you need, then view products that match.
| Monitoring Function | Three-phase supply | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Signal / Input Range | 3 × 160–300 V AC | |
| Time Delay | Adjustable |
The ABB CM-PVS.31P is a three-phase monitoring relay used to detect phase failure, incorrect phase sequence, overvoltage and undervoltage in compatible three-phase AC electrical systems.
The CM-PVS.31P, ABB order code 1SVR740794R1300, operates from a 3 × 160–300 V AC three-phase supply at 50/60 Hz. It is powered directly by the monitored electrical circuit.
The relay has a specified 160–300 V AC line-to-line measuring range. Both its measuring voltage and control supply are derived from the monitored three-phase circuit.
No. The CM-PVS.31P monitors the three-phase supply through the L1, L2 and L3 terminals. A neutral connection is not required for its standard monitoring arrangement.
Yes. The relay provides phase failure monitoring, helping identify the loss of a supply phase so that the connected control system can respond.
Yes. The CM-PVS.31P includes selectable phase sequence monitoring. When enabled, it detects incorrect phase rotation in the monitored three-phase supply.
Yes. The CM-PVS.31P provides adjustable overvoltage and undervoltage thresholds. Both thresholds can be set as absolute voltage values within the device's specified measuring range.
Yes. The relay uses a true RMS (TRMS) measuring principle to evaluate the effective voltage of the monitored three-phase AC supply.
The relay supports 0 s operation or an adjustable tripping delay from 0.1–30 s. ON-delayed and OFF-delayed tripping modes are selectable.
The relay provides two changeover (SPDT) output contacts rated at 250 V / 4 A. These contacts can be used for compatible PLC inputs, alarm circuits and motor control systems.
Both models provide 160–300 V AC monitoring, adjustable overvoltage and undervoltage thresholds, phase failure detection, selectable phase sequence monitoring and two changeover contacts. The main difference is the terminal technology: the CM-PVS.31P uses push-in terminals, while the CM-PVS.31S uses screw terminals.
The CM-PVS.31P is designed for a 160–300 V AC line-to-line range, while the CM-PVS.41P is designed for a 300–500 V AC line-to-line range. Both provide adjustable voltage thresholds, phase failure detection, selectable phase sequence monitoring and push-in terminals.
The CM-PVS.31P provides adjustable overvoltage and undervoltage thresholds and operates across a 160–300 V AC line-to-line range. The CM-PSS.31P uses fixed voltage thresholds and is designed for a nominal 380 V AC three-phase supply. Both models provide phase failure and phase sequence monitoring.
No. The CM-PVS.31P is rated for 160–300 V AC line-to-line and is not suitable for direct connection to a nominal 400 V AC three-phase supply. The CM-PVS.41P, rated for 300–500 V AC, is the corresponding model to evaluate for that voltage range.
The relay uses ABB Easy Connect push-in terminals, providing screwless spring-clamp electrical connections for efficient installation and maintenance-free wiring.
The relay is designed for DIN rail mounting inside industrial motor control panels, machinery cabinets and electrical distribution enclosures. Its compact 22.5 mm housing width helps conserve installation space.
ABB CM-PVS three-phase monitoring relays provide dependable supply supervision for industrial machinery, motor control and electrical distribution applications. With phase failure detection, selectable phase sequence monitoring, adjustable overvoltage and undervoltage thresholds, true RMS measurement and configurable tripping delays, the CM-PVS.31P offers a flexible solution for monitoring 160–300 V AC three-phase systems. Its two changeover contacts, Easy Connect push-in terminals and compact DIN rail housing support efficient integration into industrial automation installations.
Technical references: ABB CM-PVS.31 / CM-PVS.41 Technical Datasheet and ABB CM-PVS.31P Product Information. Verify the current ABB installation instructions, voltage threshold settings and contact ratings before commissioning.