Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CM-PSS.41P (1SVR740784R3300) three-phase monitoring relay for nominal 400 V AC systems, with 360–440 V AC line-to-line measuring range, fixed ±10% overvoltage and undervoltage thresholds, phase failure detection, selectable phase sequence monitoring, adjustable 0 or 0.1–30 second tripping delay, two changeover contacts rated at 250 V / 4 A and Easy Connect push-in terminals.
£126.56
The ABB CM-PSS.41P (1SVR740784R3300) is a compact industrial three-phase monitoring relay designed to supervise the electrical condition of nominal 400 V AC three-phase power supplies. Part of ABB's CM-PSS measuring and monitoring relay family, it combines phase failure detection, selectable phase sequence monitoring, overvoltage monitoring and undervoltage monitoring in one DIN rail-mounted device.
Designed for a 3 × 400 V AC nominal supply, the CM-PSS.41P monitors line-to-line voltages within a specified 360–440 V AC measuring range. Its fixed overvoltage and undervoltage response thresholds are based on ±10% of the nominal voltage, making it a practical solution for installations requiring straightforward supervision of acceptable three-phase supply conditions without independently adjustable voltage thresholds.
The relay provides two changeover (SPDT) output contacts rated at 250 V / 4 A, an adjustable 0 s or 0.1–30 s tripping delay, and selectable ON-delayed or OFF-delayed tripping. ABB's Easy Connect push-in terminals, compact 22.5 mm housing width and self-powered three-phase supply arrangement make the CM-PSS.41P suitable for motor control panels, OEM machinery and industrial electrical distribution systems.
The ABB CM-PSS.41P supervises key electrical parameters of a nominal 400 V AC three-phase supply, providing switching signals when monitored conditions move outside the relay's defined operating limits.
Phase failure detection helps identify the loss of one of the three supply phases. Phase loss can cause abnormal operation in three-phase motors, including reduced torque, excessive current in the remaining phases and overheating.
Phase sequence monitoring detects incorrect phase rotation when the function is enabled. This is useful for equipment where the direction of motor rotation is important, including pumps, compressors, fans and conveyors.
The relay also monitors overvoltage and undervoltage. These functions help identify supply conditions that may affect connected motors, contactors, power supplies and other industrial equipment.
The CM-PSS.41P provides monitoring and control signals rather than direct power-circuit protection. Suitable circuit breakers, overload protection and other protective devices remain necessary where required by the installation.
The CM-PSS.41P is designed for a nominal 400 V AC line-to-line supply and uses fixed voltage monitoring thresholds corresponding to ±10% of nominal voltage.
The nominal response levels are:
This fixed-threshold arrangement reduces the number of settings required during commissioning and is suitable where the specified voltage limits align with the equipment's operating requirements.
The thresholds are not independently adjustable. Applications requiring user-adjustable upper and lower voltage limits should be evaluated using a suitable ABB CM-PVS monitoring relay instead.
Because the response levels are based on the nominal 400 V AC rating, the CM-PSS.41P should not be treated as a universal three-phase monitoring relay for arbitrary nominal voltages.
The ABB CM-PSS.41P includes selectable phase sequence monitoring to help detect incorrect phase rotation in the three-phase supply.
Incorrect phase rotation can cause connected motors to turn in the opposite direction from that intended. Depending on the machinery, this may lead to reduced performance, incorrect process operation or mechanical damage.
When phase sequence monitoring is enabled, the relay can signal an incorrect phase rotation condition through its output contacts.
The function can also be disabled where phase sequence monitoring is not required by the application.
This flexibility allows the CM-PSS.41P to be used in a broad range of three-phase monitoring arrangements while retaining phase failure and voltage supervision.
The CM-PSS.41P provides an adjustable tripping delay with settings of 0 s or 0.1–30 s.
The delay can help accommodate short-duration supply disturbances that do not require an immediate control response, while the instantaneous setting supports applications where rapid signalling is preferred.
ON-delayed and OFF-delayed tripping are selectable, allowing the output response to be configured for the control arrangement.
The relay also has a specified 200 ms start-up delay.
Tripping delay settings should be selected according to the operating characteristics of the connected equipment. Excessive delay may be unsuitable where rapid disconnection is needed to prevent damage or hazardous operation.
The ABB CM-PSS.41P provides two changeover (SPDT) contacts rated at 250 V / 4 A.
These contacts can be incorporated into suitable motor control circuits, PLC inputs, alarm systems and electrical interlocking arrangements.
The two changeover outputs allow the monitoring relay to provide switching signals for more than one compatible control function, subject to the applicable contact ratings and wiring arrangement.
For example, the relay may be used to signal an abnormal three-phase supply condition to a PLC while also participating in a suitably designed motor contactor control circuit.
The output contacts are intended for control and signalling duties within their rated limits and should not be used to switch a motor's main power conductors directly unless the complete application and ratings specifically permit it.
The CM-PSS.41P features ABB's Easy Connect Technology, using screwless push-in terminals to simplify installation in industrial electrical panels.
The spring-clamp connection system supports efficient wiring and maintenance-free terminal connections when installed with compatible conductors in accordance with ABB's instructions.
The relay measures 85.6 × 22.5 × 103.7 mm, occupying only 22.5 mm of DIN rail width.
Its compact housing is particularly useful in motor control centres, machinery cabinets and electrical distribution enclosures where panel space is limited.
The operating ambient temperature range is −25 to +60 °C, and the device has an IP50 housing protection rating.
An optional sealable transparent cover is available to help prevent unauthorised changes to the configuration controls.
Tick the specs you need, then view products that match.
| Monitoring Function | Three-phase supply | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Signal / Input Range | 360–440 V AC | |
| Time Delay | Adjustable |
The ABB CM-PSS.41P is a three-phase monitoring relay used to detect phase failure, incorrect phase sequence, overvoltage and undervoltage in nominal 400 V AC three-phase electrical systems.
The CM-PSS.41P, ABB order code 1SVR740784R3300, is designed for a nominal 3 × 400 V AC three-phase supply at 50/60 Hz. It is powered directly by the monitored circuit.
The specified measuring range is 360–440 V AC line-to-line, corresponding to ±10% of the nominal 400 V AC supply.
No. The relay monitors the three-phase supply through the L1, L2 and L3 connections. A neutral connection is not required for its standard monitoring arrangement.
Yes. The CM-PSS.41P provides phase failure detection, helping identify loss of a supply phase so the connected control system can respond.
Yes. The relay includes selectable phase sequence monitoring. When enabled, it detects incorrect phase rotation in the monitored three-phase supply.
No. The CM-PSS.41P uses fixed overvoltage and undervoltage thresholds of approximately ±10% of its nominal 400 V AC rating. The nominal response levels are 360 V AC and 440 V AC.
The CM-PSS.41P is specified for phase failure, phase sequence, overvoltage and undervoltage monitoring. It is not specified as an adjustable phase unbalance monitoring relay. Applications requiring dedicated phase unbalance monitoring should be evaluated using a suitable ABB CM-PAS or CM-MPS model.
The relay supports 0 s operation or an adjustable tripping delay from 0.1–30 s. ON-delayed and OFF-delayed tripping modes are selectable.
The CM-PSS.41P provides two changeover (SPDT) output contacts rated at 250 V / 4 A for compatible industrial control and signalling circuits.
Both models monitor nominal 400 V AC three-phase supplies and provide the same principal monitoring functions and two changeover contacts. The CM-PSS.41P uses push-in terminals, while the CM-PSS.41S uses screw terminals.
The CM-PSS.31P is designed for nominal 380 V AC three-phase supplies, while the CM-PSS.41P is designed for nominal 400 V AC supplies. Both use fixed ±10% voltage thresholds, selectable phase sequence monitoring and push-in terminals.
The CM-PSS.41P has fixed ±10% voltage thresholds based on a nominal 400 V AC supply. The CM-PVS.41P provides adjustable overvoltage and undervoltage thresholds for applications requiring configurable voltage limits.
The CM-PSS.41P is specifically designed for a nominal 400 V AC supply. Although 380 V AC is within its specified measuring range, its fixed response thresholds are based on 400 V AC. For a nominal 380 V AC installation, the CM-PSS.31P is the corresponding model to evaluate.
The relay uses ABB Easy Connect push-in terminals, providing screwless spring-clamp connections for efficient electrical installation.
The CM-PSS.41P is designed for DIN rail mounting inside industrial motor control panels, machinery cabinets and electrical distribution enclosures. Its housing is only 22.5 mm wide.
ABB CM-PSS three-phase monitoring relays provide dependable supply supervision for industrial machinery and electrical control systems. The CM-PSS.41P combines phase failure detection, selectable phase sequence monitoring, fixed overvoltage and undervoltage thresholds, adjustable tripping delays and two changeover contacts in a compact DIN rail device. Its nominal 400 V AC rating and Easy Connect push-in terminals make it a practical choice for industrial control panels requiring straightforward three-phase voltage monitoring.
Manufacturer references: ABB Official Product Catalogue – 1SVR740784R3300 and ABB CM-PSS.41P Product Information. Verify the latest ABB technical documentation, wiring instructions, voltage limits and contact ratings before commissioning.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.