1SVR730794R1300 ABB CM-PVS.31S Three-Phase Monitoring Relay 160–300 V AC

1SVR730794R1300 ABB CM-PVS.31S Three-Phase Monitoring Relay 160–300 V AC

ABB CM-PVS.31S 1SVR730794R1300 is a 3 × 160–300 V AC three-phase monitoring relay with phase failure, selectable phase sequence, adjustable overvoltage and undervoltage monitoring, adjustable tripping delay and two changeover contacts.

SKU: 1SVR730794R1300Alt SKU: CM-PVS.31SMPN: 1SVR730794R1300
Price
List Price £237.23 ex VAT
Your Price (ex VAT) Save 35%
£154.20 35% OFF
You save £83.03 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £154.20
Trade pricing is personalised to your account

Manufacturer Lead Time

£154.20

Why Choose the ABB CM-PVS.31S Three-Phase Monitoring Relay?

The ABB CM-PVS.31S 1SVR730794R1300 is a compact three-phase monitoring relay designed to supervise critical parameters in three-phase AC supplies. It monitors phase failure, phase sequence, overvoltage and undervoltage, helping industrial control systems detect abnormal mains conditions before they affect connected machinery or processes.

The CM-PVS.31S is powered directly by the measuring circuit and is designed for 3 × 160–300 V AC line-to-line systems. Adjustable absolute overvoltage and undervoltage thresholds allow the monitoring limits to be matched to the installation, while phase-sequence monitoring can be enabled or disabled according to application requirements.

The relay provides two changeover (SPDT) output contacts rated at 250 V / 4 A. A fixed 200 ms start-up delay and selectable instantaneous or 0.1–30 s tripping delay help accommodate transient conditions, while selectable ON- or OFF-delay operation, three status LEDs and screw terminals provide flexible integration into industrial control panels.

Key Advantages

  • Combines phase failure, phase sequence, overvoltage and undervoltage monitoring in one relay.
  • Designed for three-phase systems from 160–300 V AC line-to-line.
  • TRMS measuring principle provides dependable voltage evaluation.
  • Adjustable absolute overvoltage and undervoltage thresholds.
  • Phase-sequence monitoring can be switched off when not required.
  • Powered directly from the monitored three-phase circuit.
  • 2 c/o (SPDT) output contacts provide flexible signalling and control.
  • Selectable instantaneous or 0.1–30 s tripping delay.
  • Selectable ON- or OFF-delayed tripping response.
  • Compact 22.5 mm width conserves DIN-rail space.

Key Features

  • ABB CM-PVS.31S three-phase monitoring relay.
  • 3 × 160–300 V AC rated control supply and measuring voltage.
  • 50/60 Hz supply frequency.
  • Phase failure detection.
  • Selectable phase-sequence monitoring.
  • Adjustable overvoltage monitoring.
  • Adjustable undervoltage monitoring.
  • TRMS measuring principle.
  • 200 ms start-up delay.
  • Tripping delay selectable between 0 s and 0.1–30 s.
  • Selectable ON- or OFF-delay tripping function.
  • 2 changeover (SPDT) contacts.
  • Output contacts rated at 250 V / 4 A.
  • 3 LEDs for operating-state indication.
  • Screw terminals with double-chamber cage connection technology.

Comprehensive Three-Phase Supply Monitoring

The ABB CM-PVS.31S continuously evaluates a 160–300 V AC three-phase supply for voltage and phase conditions. Adjustable overvoltage and undervoltage thresholds allow acceptable operating limits to be defined for the installation, while phase-failure detection and selectable phase-sequence supervision help identify supply faults that could disrupt or damage three-phase equipment.

The TRMS measuring principle supports reliable voltage evaluation, while the adjustable tripping delay allows short-duration disturbances to be tolerated when appropriate. With the option of ON- or OFF-delayed operation and two changeover contacts, the CM-PVS.31S can be integrated into alarm circuits, contactor control, machine interlocking and other protective control functions.

Typical Applications

  • Three-phase mains voltage supervision.
  • Phase failure detection.
  • Phase-sequence monitoring.
  • Overvoltage and undervoltage supervision.
  • Three-phase motor and pump control systems.
  • Compressors, fans and material handling machinery.
  • Industrial automation and process equipment.
  • Electrical control and distribution panels.

Technical Specifications

Tick the specs you need, then view products that match.

Time Delay Adjustable
Monitoring Function Three-phase supply
Monitored Supply Three-phase
Signal / Input Range 3 × 160–300 V AC
Series CM-PVS
ABB order code 1SVR730794R1300
Product type Three-phase monitoring relay
Monitoring functions Phase failure, phase sequence, overvoltage and undervoltage
Rated control supply voltage 3 × 160–300 V AC, line-to-line
Measuring range 3 × 160–300 V AC, line-to-line
Rated frequency 50/60 Hz
Measuring principle TRMS
Voltage thresholds Adjustable as absolute values
Phase-sequence monitoring Selectable
Start-up delay 200 ms
Tripping delay 0 s or 0.1–30 s, adjustable
Tripping function ON-delay or OFF-delay, selectable
Output 2 c/o (SPDT) contacts
Contact rating 250 V / 4 A
Status indication 3 LEDs
Terminal type Screw terminals
Operating temperature -25 to +60 °C
Storage temperature -40 to +85 °C
Maximum output circuit operating voltage UL/CSA 300 V AC
UL/CSA contact rating B300
Product width 22.5 mm
Product height 85.6 mm
Product depth 103.7 mm
Product net weight 0.141 kg
EAN 4016779851831

Frequently Asked Questions

What is the ABB CM-PVS.31S 1SVR730794R1300 used for?

It is a three-phase monitoring relay used to detect phase failure, incorrect phase sequence, overvoltage and undervoltage conditions in three-phase AC systems.

What voltage range does the CM-PVS.31S monitor?

The CM-PVS.31S is designed for a line-to-line three-phase measuring and supply voltage of 3 × 160–300 V AC.

Does the CM-PVS.31S require a separate control supply?

No. The CM-PVS.31S is powered directly by the measuring circuit, with its rated control supply voltage corresponding to the monitored 3 × 160–300 V AC three-phase supply.

Can phase-sequence monitoring be disabled on the CM-PVS.31S?

Yes. Phase-sequence monitoring is selectable and can be switched off when the application does not require phase-rotation supervision.

Does the CM-PVS.31S have an adjustable tripping delay?

Yes. The relay provides a 200 ms start-up delay and a tripping delay selectable between instantaneous operation and 0.1–30 s, with ON- or OFF-delayed operation selectable.

Trusted ABB Three-Phase Monitoring Technology

ABB CM-PVS three-phase monitoring relays provide dependable supervision of phase and voltage conditions in industrial electrical systems, helping machine builders, panel builders and operators integrate effective supply monitoring, alarm and protective control functions.