ABB CM-PVS.31S 1SVR730794R1300 is a 3 × 160–300 V AC three-phase monitoring relay with phase failure, selectable phase sequence, adjustable overvoltage and undervoltage monitoring, adjustable tripping delay and two changeover contacts.
£154.20
The ABB CM-PVS.31S 1SVR730794R1300 is a compact three-phase monitoring relay designed to supervise critical parameters in three-phase AC supplies. It monitors phase failure, phase sequence, overvoltage and undervoltage, helping industrial control systems detect abnormal mains conditions before they affect connected machinery or processes.
The CM-PVS.31S is powered directly by the measuring circuit and is designed for 3 × 160–300 V AC line-to-line systems. Adjustable absolute overvoltage and undervoltage thresholds allow the monitoring limits to be matched to the installation, while phase-sequence monitoring can be enabled or disabled according to application requirements.
The relay provides two changeover (SPDT) output contacts rated at 250 V / 4 A. A fixed 200 ms start-up delay and selectable instantaneous or 0.1–30 s tripping delay help accommodate transient conditions, while selectable ON- or OFF-delay operation, three status LEDs and screw terminals provide flexible integration into industrial control panels.
The ABB CM-PVS.31S continuously evaluates a 160–300 V AC three-phase supply for voltage and phase conditions. Adjustable overvoltage and undervoltage thresholds allow acceptable operating limits to be defined for the installation, while phase-failure detection and selectable phase-sequence supervision help identify supply faults that could disrupt or damage three-phase equipment.
The TRMS measuring principle supports reliable voltage evaluation, while the adjustable tripping delay allows short-duration disturbances to be tolerated when appropriate. With the option of ON- or OFF-delayed operation and two changeover contacts, the CM-PVS.31S can be integrated into alarm circuits, contactor control, machine interlocking and other protective control functions.
Tick the specs you need, then view products that match.
| Time Delay | Adjustable | |
|---|---|---|
| Monitoring Function | Three-phase supply | |
| Monitored Supply | Three-phase | |
| Signal / Input Range | 3 × 160–300 V AC | |
| Series | CM-PVS | |
| ABB order code | 1SVR730794R1300 | |
| Product type | Three-phase monitoring relay | |
| Monitoring functions | Phase failure, phase sequence, overvoltage and undervoltage | |
| Rated control supply voltage | 3 × 160–300 V AC, line-to-line | |
| Measuring range | 3 × 160–300 V AC, line-to-line | |
| Rated frequency | 50/60 Hz | |
| Measuring principle | TRMS | |
| Voltage thresholds | Adjustable as absolute values | |
| Phase-sequence monitoring | Selectable | |
| Start-up delay | 200 ms | |
| Tripping delay | 0 s or 0.1–30 s, adjustable | |
| Tripping function | ON-delay or OFF-delay, selectable | |
| Output | 2 c/o (SPDT) contacts | |
| Contact rating | 250 V / 4 A | |
| Status indication | 3 LEDs | |
| Terminal type | Screw terminals | |
| Operating temperature | -25 to +60 °C | |
| Storage temperature | -40 to +85 °C | |
| Maximum output circuit operating voltage UL/CSA | 300 V AC | |
| UL/CSA contact rating | B300 | |
| Product width | 22.5 mm | |
| Product height | 85.6 mm | |
| Product depth | 103.7 mm | |
| Product net weight | 0.141 kg | |
| EAN | 4016779851831 |
It is a three-phase monitoring relay used to detect phase failure, incorrect phase sequence, overvoltage and undervoltage conditions in three-phase AC systems.
The CM-PVS.31S is designed for a line-to-line three-phase measuring and supply voltage of 3 × 160–300 V AC.
No. The CM-PVS.31S is powered directly by the measuring circuit, with its rated control supply voltage corresponding to the monitored 3 × 160–300 V AC three-phase supply.
Yes. Phase-sequence monitoring is selectable and can be switched off when the application does not require phase-rotation supervision.
Yes. The relay provides a 200 ms start-up delay and a tripping delay selectable between instantaneous operation and 0.1–30 s, with ON- or OFF-delayed operation selectable.
ABB CM-PVS three-phase monitoring relays provide dependable supervision of phase and voltage conditions in industrial electrical systems, helping machine builders, panel builders and operators integrate effective supply monitoring, alarm and protective control functions.