Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CM-PAS.31S (1SVR730774R1300) is a three-phase 160–300 V AC monitoring relay with phase failure, phase sequence and adjustable phase unbalance detection, True RMS measurement, two change-over contacts and a configurable 0 or 0.1–30 s tripping delay for industrial electrical systems.
£146.19
The ABB CM-PAS.31S (1SVR730774R1300) is a versatile three-phase monitoring relay designed to supervise phase failure, phase sequence and phase unbalance in industrial electrical systems. Part of the ABB CM-PAS monitoring relay series, it helps protect motors, machinery and electrical equipment against abnormal three-phase supply conditions.
Designed for a three-phase 160–300 V AC line-to-line measuring range, the CM-PAS.31S continuously monitors the connected electrical supply using a True RMS measuring principle. Its adjustable phase unbalance threshold and selectable tripping delay allow engineers to configure monitoring behaviour according to the requirements of the installation.
The relay features two change-over output contacts, an adjustable 0 or 0.1–30 s tripping delay and three LED status indicators. Powered directly by the monitored circuit, the ABB CM-PAS.31S requires no separate auxiliary supply. Its compact 22.5 mm DIN rail-mounted housing and screw-terminal connections make it suitable for industrial control cabinets and automated machinery.
Industrial motors and automated machinery depend on stable three-phase electrical supplies for reliable operation. Missing phases, incorrect phase sequence and excessive voltage imbalance can cause motor overheating, reduced torque, unexpected shutdowns and equipment damage. The ABB CM-PAS.31S three-phase monitoring relay helps identify these conditions and provides switching signals that can be integrated into protective control circuits.
The CM-PAS.31S monitors the connected L1, L2 and L3 supply conductors and evaluates the voltage conditions using its True RMS measuring principle. If a monitored phase is lost, the phase sequence is incorrect or the measured phase unbalance exceeds the configured threshold, the relay responds according to its monitoring logic and selected delay setting.
The adjustable phase unbalance threshold allows the monitoring sensitivity to be matched to the requirements of the installation. This is particularly useful where supply voltage imbalance must be detected before it causes prolonged stress on motors or other three-phase equipment.
The relay also provides a configurable tripping delay of 0 or 0.1–30 s. This allows the response to be set for immediate monitoring or delayed operation, depending on the application. The delay is intended to help coordinate the relay response with the characteristics of the monitored electrical system.
With two change-over output contacts, the CM-PAS.31S can interface with compatible contactor control circuits, programmable logic controllers and alarm systems. The relay is a monitoring and signalling device rather than a circuit breaker or motor overload relay. Where disconnection of a motor supply is required, its contacts should operate an appropriately rated external switching device.
Its self-powered design, compact DIN rail housing and front-mounted adjustments simplify installation and commissioning. The three LED indicators provide convenient status information, while the optional ABB COV.11 transparent cover can help prevent unintended changes to the configured settings.
Tick the specs you need, then view products that match.
| Monitoring Function | Three-phase supply | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Signal / Input Range | 160–300 V AC | |
| Time Delay | Adjustable |
The ABB CM-PAS.31S is designed to monitor phase failure, phase sequence and phase unbalance in industrial three-phase electrical supplies. It provides relay switching signals that can be used by compatible motor control, alarm and automation systems.
The ABB CM-PAS.31S, order code 1SVR730774R1300, operates with a three-phase 160–300 V AC line-to-line measuring and supply voltage at 50/60 Hz. The monitored supply also powers the relay, so a separate auxiliary supply is not required.
Yes. The CM-PAS.31S includes phase sequence monitoring alongside phase failure and phase unbalance detection. It can identify an incorrect phase rotation condition and provide an output signal to a connected control system.
Yes. The phase unbalance threshold is adjustable using the relay's front-mounted controls. The CM-PAS.31S also provides an adjustable 0.1–30 s tripping delay, with a separate zero-delay setting, allowing its response to be configured for the application.
The relay provides two change-over (SPDT) output contacts rated at 250 V AC / 4 A. These contacts can be integrated into appropriately rated contactor control circuits, alarm systems and industrial automation equipment.
ABB CM-PAS three-phase monitoring relays provide dependable supervision of industrial electrical supplies. Combining phase failure detection, phase sequence monitoring, adjustable phase unbalance detection and configurable tripping delays, the CM-PAS.31S supports reliable operation of motors, machinery and electrical control systems.