Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CM-PVE (1SVR550871R9500) is a self-powered three-phase 320–460 V AC monitoring relay with phase failure, overvoltage and undervoltage detection, fixed monitoring thresholds and one normally open output contact, designed for industrial electrical protection and automation systems without neutral monitoring.
£54.12
The ABB CM-PVE (1SVR550871R9500) is a compact and reliable three-phase monitoring relay designed to detect phase failure, overvoltage and undervoltage in industrial AC electrical systems. As part of the ABB CM-PVE monitoring relay series, it provides dependable supply supervision for industrial motors, electrical distribution equipment and automated machinery.
This phase and voltage monitoring relay continuously supervises the connected three-phase supply, helping identify electrical conditions that could cause motor overheating, equipment malfunction or unexpected production downtime. Its fixed overvoltage and undervoltage monitoring thresholds simplify operation, while its integrated normally open relay contact enables connection to compatible motor contactors, alarm circuits and automation systems.
Designed for three-phase 320–460 V AC line-to-line supplies, the ABB CM-PVE operates directly from the monitored circuit without requiring a separate auxiliary power supply. This specific version is designed for three-phase monitoring without a neutral connection, making it suitable for three-wire industrial power systems. Its compact 22.5 mm housing width and DIN rail mounting allow convenient integration into electrical control cabinets.
Industrial motors and automated electrical systems depend on stable three-phase power supplies for reliable operation. Excessive voltage can place additional stress on motor insulation and electrical components, while insufficient voltage can reduce motor torque, increase current demand and cause unreliable machinery operation. A missing phase may also result in abnormal motor operation and overheating. The ABB CM-PVE phase and voltage monitoring relay helps identify these supply conditions before they cause prolonged equipment disruption.
The CM-PVE monitors the three-phase supply through its L1, L2 and L3 measuring connections. When the monitored supply satisfies the relay's operating conditions, its normally open output contact closes according to the closed-circuit principle. If a detectable phase failure, overvoltage or undervoltage condition occurs, the output contact opens, allowing the connected control circuit to initiate a protective response.
The relay uses fixed monitoring thresholds, making it particularly suitable for applications where straightforward installation and dependable supply supervision are priorities. Its 500 ms start-up and tripping delays provide defined response times, while the integrated LED offers a convenient indication of the relay's operating state.
Unlike the CM-PVE variant designed for neutral monitoring, ABB order code 1SVR550871R9500 is specifically intended for three-phase line-to-line monitoring without neutral supervision. It is therefore appropriate for compatible three-wire industrial supplies. It should not be selected where dedicated phase-to-neutral or single-phase monitoring is required.
The relay can be integrated into industrial motor starter circuits, electrical distribution panels and automated machinery. Its output contact is intended for compatible control and signalling circuits rather than direct interruption of a motor's main power supply. Where motor disconnection is required, the CM-PVE should operate an appropriately rated contactor or other suitable protective switching device.
Tick the specs you need, then view products that match.
| Monitoring Function | Three-phase supply | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Signal / Input Range | 320–460 V AC | |
| Time Delay | Fixed |
The ABB CM-PVE monitors industrial three-phase AC supplies for phase failure, overvoltage and undervoltage. It provides a relay switching signal that can be integrated into motor control circuits, electrical protection systems and industrial automation equipment.
This ABB CM-PVE version operates with a three-phase 320–460 V AC line-to-line supply at 50/60 Hz. The monitored supply also powers the relay, so no separate auxiliary supply is required.
No. ABB order code 1SVR550871R9500 is the three-phase version without neutral monitoring. It monitors the line-to-line voltages through L1, L2 and L3 and is suitable for compatible three-wire industrial electrical systems.
Under healthy supply conditions, the relay's normally open output contact closes. If a detectable phase failure, overvoltage or undervoltage condition occurs, the output contact opens, enabling a connected contactor or control system to respond to the fault.
The ABB CM-PVE provides one normally open (SPST-NO) output contact rated at 250 V AC / 4 A. It also incorporates a 500 ms start-up delay and a 500 ms tripping delay for defined monitoring and switching behaviour.
ABB CM-PVE monitoring relays provide dependable phase failure, overvoltage and undervoltage supervision for industrial electrical systems. Combining self-powered operation, fixed monitoring thresholds, relay output signalling and compact DIN rail installation, the CM-PVE helps protect industrial equipment and supports reliable operation of motors, machinery and electrical distribution systems.