Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 50.16.9.048.5420 is a Series 50 six-pole PCB-mounted safety relay featuring a 48 V DC coil, four normally open and two normally closed 8 A forcibly guided contacts, gold-plated silver tin oxide contact material and EN 61810-3 Type A construction for industrial safety-related switching and monitoring applications.
£24.91
The Finder 50.16.9.048.5420 is a six-pole, PCB-mounted electromechanical safety relay with forcibly guided contacts from the Finder Series 50 range. Designed for safety-related industrial control and monitoring applications, it combines a 48 V DC operating coil, six 8 A contacts and a mechanically linked contact arrangement that supports reliable switching and fault monitoring.
Featuring four normally open (4 NO) and two normally closed (2 NC) contacts, this relay provides multiple switching and feedback paths within a single compact component. Its Type A forcibly guided contact construction, in accordance with EN 61810-3 (formerly EN 50205), makes it particularly suitable for safety-related control circuits requiring monitoring of contact states and detection of certain contact faults.
The Finder 50.16.9.048.5420 incorporates silver tin oxide contacts with gold plating (AgSnO₂ + Au), a 0.8 W DC coil and RT III wash-tight environmental protection. Its through-hole PCB mounting design, high insulation between adjacent contacts and reinforced coil-to-contact separation make it a practical choice for machinery safety equipment, industrial automation and OEM electronic control assemblies.
The Finder 50.16.9.048.5420 operates through a 48 V DC electromagnetic coil controlling six mechanically linked contacts. When the coil is energised, the four normally open contacts close while the two normally closed contacts open. When the coil is de-energised, the contacts return to their normal positions.
The relay's EN 61810-3 Type A forcibly guided construction ensures that the normally open and normally closed contacts maintain a defined mechanical relationship. Under specified fault conditions, such as a welded contact, the contact guidance prevents an opposing contact from returning to an inconsistent closed position. This behaviour enables an appropriately designed safety controller to detect certain contact faults through feedback monitoring.
The 4 NO + 2 NC arrangement is particularly useful in systems requiring multiple switched outputs and independent feedback connections. The normally open contacts can be incorporated into controlled switching paths, while the normally closed contacts can be used within monitoring circuits to verify relay state, subject to the complete safety system design.
The relay also provides 6 kV impulse insulation between the coil and contacts, a wash-tight RT III housing and gold-plated silver tin oxide contacts. These characteristics support integration into industrial PCB assemblies exposed to demanding operating conditions.
Safety design consideration: The Finder 50.16.9.048.5420 is a forcibly guided relay component, not a complete safety controller. Achieving a specified Performance Level (PL) under EN ISO 13849-1 or Safety Integrity Level (SIL) under IEC 62061 requires appropriate circuit architecture, diagnostics, component assessment and validation of the complete safety-related control system.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Timing Function | None (instantaneous) | |
| Mounting Type | PCB | |
| Terminal Type | PCB / pins | |
| Switching Current (A) | 8 A | |
| Manufacturer | Finder | |
| Series | Finder Series 50 | |
| Product family | Finder 50.16 | |
| Manufacturer part number | 50.16.9.048.5420 | |
| Product type | Forcibly guided electromechanical safety relay | |
| Relay technology | Electromechanical | |
| Number of contacts | 6 | |
| Contact arrangement | 4 NO + 2 NC | |
| Normally open contacts | 4 | |
| Normally closed contacts | 2 | |
| Contact guidance | Forcibly guided / mechanically linked | |
| Contact guidance classification | EN 61810-3 Type A | |
| Rated contact current | 8 A | |
| Maximum peak contact current | 15 A | |
| Rated contact voltage | 250 V AC | |
| Maximum AC switching voltage | 400 V AC | |
| Maximum DC switching voltage | 220 V DC | |
| Rated resistive switching capacity (AC1) | 2,000 VA | |
| Rated AC15 switching capacity at 230 V AC | 1,100 VA | |
| Single-phase motor rating at 230 V AC | 0.37 kW | |
| DC1 breaking capacity at 24 V DC | 8 A | |
| DC1 breaking capacity at 110 V DC | 0.6 A | |
| DC1 breaking capacity at 220 V DC | 0.2 A | |
| Minimum switching load | 50 mW (5 V / 10 mA) | |
| Contact material | Silver tin oxide with gold plating (AgSnO₂ + Au) | |
| Nominal coil voltage | 48 V DC | |
| Coil type | DC electromagnetic coil | |
| Minimum coil operating voltage | 36 V DC | |
| Maximum coil operating voltage | 57.6 V DC | |
| Nominal coil resistance | 2,880 Ω | |
| Nominal coil current | 16.6 mA | |
| Nominal coil power consumption | 0.8 W | |
| Holding voltage | 0.4 × nominal coil voltage | |
| Must drop-out voltage | 0.1 × nominal coil voltage | |
| Coil-to-contact separation | 8 mm | |
| Coil-to-contact impulse withstand voltage | 6 kV (1.2/50 µs) | |
| Dielectric strength between open contacts | 1,500 V AC | |
| Typical operate time | 10 ms | |
| Typical release time | 4 ms | |
| Mechanical endurance | 10 million cycles | |
| Electrical endurance at rated AC1 load | 100,000 cycles | |
| Operating temperature | -40 °C to +70 °C | |
| Environmental protection | RT III, wash-tight | |
| Mounting type | Through-hole PCB mounting | |
| Terminal type | PCB solder pins | |
| Housing dimensions | 55 × 16.5 × 16.5 mm | |
| Relay operation | Monostable / non-latching | |
| Contact material composition | Cadmium-free |
The Finder 50.16.9.048.5420 is a six-pole forcibly guided safety relay used in industrial safety-related switching and monitoring circuits. Typical applications include machinery safety controllers, emergency-stop monitoring, safety interlocks, lift controls and industrial automation equipment.
The relay uses a 48 V DC nominal operating coil with a specified operating range of 36–57.6 V DC. Its nominal coil resistance is 2.88 kΩ, nominal coil current is approximately 16.6 mA and coil consumption is 0.8 W.
The relay has six forcibly guided contacts, comprising four normally open (4 NO) and two normally closed (2 NC) contacts. Each contact is rated at 8 A, subject to the applicable load and switching conditions.
EN 61810-3 Type A identifies a relay construction in which all normally open and normally closed contacts are forcibly guided. This mechanically linked arrangement prevents opposing contacts from being closed simultaneously under defined fault conditions, supporting fault detection and feedback monitoring in properly designed safety-related circuits.
The main difference is the contact configuration. The 50.16.9.048.5420 provides 4 NO + 2 NC contacts, while the 50.16.9.048.5510 provides 5 NO + 1 NC contacts. Both are Finder Series 50.16 six-pole forcibly guided relays with 48 V DC coils, but the contact arrangement must be selected to match the safety circuit design.
Finder Series 50 forcibly guided relays provide dependable switching and contact-monitoring components for industrial safety systems. The 50.16.9.048.5420 combines a 48 V DC coil, six 8 A mechanically linked contacts, gold-plated silver tin oxide contact construction and EN 61810-3 Type A guidance to support appropriately engineered safety-related control applications.
We use cookies