Finder 6K.T1.0.000.1827 is a Class 10A thermal motor overload relay with an adjustable 1.8–2.7 A current setting range, one normally open and one normally closed auxiliary contact, selectable manual or automatic reset and direct-mount compatibility with Finder 6K.13 and 6K.14 contactors.
£42.48
The Finder 6K.T1.0.000.1827 is an adjustable 1.8–2.7 A thermal overload relay designed to protect industrial electric motors against sustained overload conditions when used with compatible Finder Series 6K.13 and 6K.14 contactors. Part of the Finder Series 6K motor control range, this device provides thermal motor protection for appropriately designed industrial motor starter assemblies.
Featuring a Class 10A thermal tripping characteristic, the Finder 6K.T1.0.000.1827 allows the overload threshold to be adjusted within its specified 1.8–2.7 A current range. The relay incorporates one normally open and one normally closed auxiliary contact for overload signalling, control circuit interruption and fault indication.
Designed for direct attachment to compatible contactors, the relay features an adjustable connection pin spacing for use with Finder 6K.13 and 6K.14 models. Its manual or automatic reset selection, integrated stop button, IP20 protection rating and 690 V rated insulation voltage support integration into professionally designed industrial electrical control equipment.
The Finder 6K.T1.0.000.1827 provides thermal overload protection for motors operated through compatible Finder 6K.13 and 6K.14 contactors. Its adjustable 1.8–2.7 A setting enables the relay to be configured according to the motor's rated current, helping reduce the risk of damage caused by sustained overload conditions.
When an overload causes the relay to trip, the auxiliary contacts change state. The normally closed contact (95–96) can be incorporated into the contactor coil control circuit to interrupt operation, while the normally open contact (97–98) can provide an overload indication or fault signal to compatible monitoring equipment.
The relay's Class 10A tripping characteristic should be considered alongside the motor's full-load current, starting duration and operating duty. The selectable manual or automatic reset function provides flexibility for the control arrangement, although automatic restarting must be prevented where it could create a hazard. This thermal overload relay does not provide short-circuit protection, so suitable upstream fuses or circuit breakers are also required.
Tick the specs you need, then view products that match.
| Device Type | Contactor | |
|---|---|---|
| Coil Type | AC, AC/DC, DC | |
| Manufacturer | Finder | |
| Series | 6K | |
| Model | 6K.T1.0.000.1827 | |
| Manufacturer article number | 6KT100001827 | |
| Product type | Thermal motor overload relay | |
| Adjustable current setting range | 1.8–2.7 A | |
| Tripping class | Class 10A | |
| Compatible contactor families | Finder 6K.13 and 6K.14 | |
| Mounting method | Direct attachment to compatible contactor | |
| Connection pin spacing | Adjustable | |
| Normally open auxiliary contacts | 1 NO | |
| Normally closed auxiliary contacts | 1 NC | |
| Rated insulation voltage | 690 V | |
| Maximum rated operational voltage | 690 V | |
| Auxiliary contact rated current (AC-15, 24 V) | 3 A | |
| Auxiliary contact rated current (AC-15, 230 V) | 2 A | |
| Auxiliary contact rated current (AC-15, 400 V) | 1 A | |
| Auxiliary contact rated current (DC-13, 24 V) | 1 A | |
| Auxiliary contact material | AgNi | |
| Main circuit connection | Screw connection | |
| Terminal design | Box clamp | |
| Degree of protection | IP20 | |
| Ambient temperature range | −25 °C to +60 °C | |
| Reset functions | Manual push-button or automatic reset | |
| Stop function | Integrated stop button | |
| EAN | 8012823456768 |
The Finder 6K.T1.0.000.1827 is a thermal overload relay designed to help protect appropriately rated electric motors against sustained overload conditions when used with compatible Finder 6K.13 or 6K.14 contactors.
The relay has an adjustable current setting range of 1.8–2.7 A. The setting should be matched to the motor's rated current in accordance with the manufacturer's installation instructions.
The Finder 6K.T1.0.000.1827 is designed for Finder Series 6K.13 and 6K.14 industrial contactors. It features adjustable connection pin spacing to accommodate these compatible contactor types.
Yes. The relay supports manual push-button reset and automatic reset, allowing the reset arrangement to be selected for the application. Automatic reset should only be used where the control system prevents hazardous unintended restarting.
The relay includes one normally open (1 NO) and one normally closed (1 NC) auxiliary contact. These contacts can be used for overload signalling and interruption of the associated contactor control circuit when the relay trips.
Finder Series 6K thermal overload relays provide motor protection solutions for electrical panel manufacturers, machine builders, maintenance engineers and industrial automation professionals. Combining an adjustable 1.8–2.7 A current range, Class 10A thermal tripping, selectable manual or automatic reset and compatibility with Finder 6K.13 and 6K.14 contactors, the Finder 6K.T1.0.000.1827 supports dependable overload protection in professionally designed industrial motor starter systems.