Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 6K.T1.0.000.1724 is a Class 10A thermal overload relay with an adjustable 17–24 A current setting, one normally open and one normally closed auxiliary contact, manual and automatic reset functionality and direct-mounting compatibility with Finder 6K.13 and 6K.14 industrial contactors.
£57.62
The Finder 6K.T1.0.000.1724 is an adjustable thermal overload relay designed to protect industrial electric motors against sustained overload conditions. Part of the Finder 6K Series, this motor protection device is specifically designed for direct mounting to compatible Finder 6K.13 and 6K.14 industrial contactors.
Featuring an adjustable current setting range of 17–24 A and a Class 10A tripping characteristic, the Finder 6K.T1.0.000.1724 provides thermal overload protection for motors operating within the appropriate current range. The adjustable setting allows the protection threshold to be matched to the connected motor's rated current and operating requirements.
The relay incorporates one normally open and one normally closed auxiliary contact, manual and automatic reset functionality, and an integrated stop button. Its 690 V rated insulation voltage, IP20 protection rating and screw-connected cage-clamp terminals make it a practical solution for industrial motor starter assemblies and electrical control panels.
The Finder 6K.T1.0.000.1724 provides thermal overload protection by responding to sustained excessive current in a motor circuit. When an overload persists sufficiently to activate the relay's thermal tripping mechanism, its auxiliary contacts change state. When the normally closed auxiliary contact is correctly incorporated into the contactor control circuit, the trip causes the contactor to release and disconnect the motor supply.
The 17–24 A adjustment range enables the relay to be configured for the connected motor's rated current, while its Class 10A tripping characteristic supports appropriate motor starting and overload protection requirements. Manual and automatic reset options provide installation flexibility, although automatic reset must only be selected where unexpected restarting cannot create a hazard. The relay does not replace the need for suitable short-circuit protection.
Tick the specs you need, then view products that match.
| Device Type | Contactor | |
|---|---|---|
| Coil Type | AC, AC/DC, DC | |
| Manufacturer | Finder | |
| Series | 6K | |
| Model | 6K.T1.0.000.1724 | |
| Manufacturer article number | 6KT100001724 | |
| Product type | Thermal overload relay | |
| Protection function | Motor thermal overload protection | |
| Adjustable current range | 17–24 A | |
| Tripping class | Class 10A | |
| Compatible contactors | Finder 6K.13 and 6K.14 | |
| Mounting method | Direct mounting to compatible contactors | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Auxiliary contact material | AgNi (silver-nickel) | |
| Rated insulation voltage | 690 V | |
| Maximum rated operational voltage | 690 V | |
| Reset functionality | Manual and automatic | |
| Reset push-button | Yes | |
| Stop button | Yes | |
| Main circuit connection | Screw connection with cage-clamp terminals | |
| Protection rating | IP20 | |
| Applicable standard | IEC 60947-4-1 | |
| EAN / GTIN-13 | 8012823456904 | |
| Product category | Thermal Overload Relays |
The Finder 6K.T1.0.000.1724 is a thermal overload relay designed to protect industrial electric motors against sustained overload conditions. It is intended for direct mounting to compatible Finder 6K.13 and 6K.14 contactors.
The relay has an adjustable current setting range of 17–24 A, allowing its overload protection threshold to be matched to a suitable motor's rated operating current.
The Finder 6K.T1.0.000.1724 is designed for direct mounting to Finder 6K.13 and 6K.14 industrial contactors, enabling an integrated contactor and thermal overload relay assembly.
Class 10A describes the thermal overload relay's standardised tripping characteristic. It helps determine whether the relay is suitable for the motor's starting duration and operating conditions.
Yes. The relay supports manual and automatic reset. Automatic reset should only be used where the motor control system prevents hazardous unexpected restarting.
The Finder 6K.T1.0.000.1724 includes one normally open and one normally closed auxiliary contact for overload trip indication, contactor control and signalling applications.
Yes. The relay incorporates a stop button and reset push-button, providing local control and reset functionality.
The main difference is the adjustable overload current range. The 6K.T1.0.000.1724 covers 17–24 A, while the 6K.T1.0.000.1318 covers 13–18 A. Both are Class 10A thermal overload relays designed for compatible Finder 6K.13 and 6K.14 contactors.
No. The Finder 6K.T1.0.000.1724 provides thermal overload protection but does not replace a fuse or circuit breaker. Suitable short-circuit protection must be provided separately.
The Finder 6K.T1.0.000.1724 has a maximum rated operational voltage of 690 V and must be installed within its specified electrical ratings.
Finder 6K Series thermal overload relays are designed for electrical engineers, industrial automation specialists, panel builders and machinery manufacturers requiring adjustable motor overload protection, reliable trip signalling and direct integration with compatible industrial contactors.