Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 6K.T0.0.000.2704 is a Class 10A thermal overload relay with an adjustable 2.7–4 A current setting, 690 V maximum rated operational voltage, one normally open and one normally closed auxiliary contact and direct-mounting compatibility with Finder 6K.04 mini contactors for electric motor overload protection.
£39.13
The Finder 6K.T0.0.000.2704 is an adjustable thermal overload relay designed to protect electric motors against sustained overload conditions. Part of the Finder 6K industrial contactor and motor protection range, this device is specifically designed for direct attachment to compatible Finder 6K.04 mini contactors, providing a compact and practical motor starter protection solution.
With an adjustable current setting of 2.7–4 A, the Finder 6K.T0.0.000.2704 allows the thermal overload protection threshold to be matched to the rated current of a connected motor. Its Class 10A thermal tripping characteristic provides a defined response to overload conditions, helping reduce the risk of excessive motor heating and associated equipment damage.
The relay features one normally open (1 NO) and one normally closed (1 NC) auxiliary contact for overload signalling and control circuit integration. Additional features include a 690 V maximum rated operational voltage, IP20 protection rating, integrated stop button, automatic reset capability and screw-type main circuit connections.
The Finder 6K.T0.0.000.2704 is designed to help protect electric motors from excessive heating caused by prolonged overload current. Thermal overload relays respond to sustained overcurrent conditions according to a defined time-current characteristic, enabling the motor control system to disconnect the motor before excessive thermal stress occurs.
The adjustable 2.7–4 A current range allows the relay to be set according to the connected motor's nameplate current and the manufacturer's selection instructions. This flexibility makes it suitable for appropriately rated small motor applications where accurate overload setting is important.
The Class 10A tripping characteristic defines the relay's overload response under specified test conditions. It is commonly associated with motor starter applications where a relatively fast thermal response is required. The actual trip time depends on the degree of overload and the applicable operating conditions.
The relay's normally closed auxiliary contact can be incorporated into the contactor control circuit so that an overload trip interrupts the contactor coil supply. The normally open auxiliary contact can provide an overload indication to a signalling device or monitoring system.
Designed for direct mounting onto Finder 6K.04 mini contactors, the relay supports compact motor starter assemblies with fewer separate components. Its automatic reset capability must only be used where the electrical control system prevents hazardous unexpected restarting.
Important: A thermal overload relay does not replace short-circuit protection. Suitable fuses or circuit breakers must be provided in accordance with the electrical installation and motor starter coordination requirements.
Tick the specs you need, then view products that match.
| Device Type | Contactor | |
|---|---|---|
| Coil Type | AC, AC/DC, DC | |
| Manufacturer | Finder | |
| Series | 6K | |
| Product type | Thermal overload relay | |
| Manufacturer part number | 6K.T0.0.000.2704 | |
| Alternative manufacturer code | 6KT000002704 | |
| Compatible contactor series | Finder 6K.04 | |
| Adjustable current range | 2.7–4 A | |
| Minimum current setting | 2.7 A | |
| Maximum current setting | 4 A | |
| Maximum rated operational voltage (Ue) | 690 V | |
| Thermal trip class | Class 10A | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Auxiliary contact configuration | 1 NO + 1 NC | |
| Auxiliary contact material | Silver-nickel (AgNi) | |
| Mounting method | Direct attachment to compatible contactor | |
| Main circuit connection | Screw terminals | |
| Stop button | Yes | |
| Automatic reset capability | Yes | |
| Remote electrical reset input | No | |
| Push-button reset function | No | |
| Protection rating | IP20 | |
| Operating principle | Thermal overload detection | |
| EAN / GTIN-13 | 8012823456683 |
The Finder 6K.T0.0.000.2704 is a thermal overload relay designed to protect appropriately rated electric motors against sustained overload conditions when used with compatible Finder 6K.04 mini contactors.
The relay has an adjustable current setting of 2.7–4 A, allowing its thermal overload protection threshold to be matched to the connected motor's rated current.
The Finder 6K.T0.0.000.2704 is designed for direct attachment to Finder 6K.04 mini contactors. Compatibility with other contactor sizes should be checked separately.
Class 10A identifies the thermal overload relay's tripping characteristic under defined test conditions. It is intended for compatible motor starting and overload protection applications.
Yes. The relay includes one normally open and one normally closed auxiliary contact for overload indication, signalling and integration into motor control circuits.
Yes. The Finder 6K.T0.0.000.2704 supports automatic reset. This capability should only be used where unexpected motor restarting cannot create a hazard.
No. The relay provides thermal overload protection and must be used with appropriately selected short-circuit protective devices, such as fuses or circuit breakers.
The Finder 6K.T0.0.000.2704 has a maximum rated operational voltage of 690 V, subject to the specified installation and operating conditions.
The Finder 6K.T0.0.000.2704 provides adjustable thermal overload protection for compatible Finder 6K.04 motor starter assemblies. With its 2.7–4 A current setting, Class 10A tripping characteristic, integrated auxiliary contacts and direct-mounting design, it offers a practical motor protection solution for electrical engineers, industrial panel builders, automation specialists and maintenance professionals.