Finder 6K.T0.0.000.0811 is a Class 10A thermal motor overload relay with an adjustable 8–11 A current setting range, one normally open and one normally closed auxiliary contact, and direct-mount compatibility with Finder 6K.04 mini contactors.
£44.49
The Finder 6K.T0.0.000.0811 is an adjustable 8–11 A thermal overload relay designed to protect electrical motors against sustained overload conditions when used with compatible Finder Series 6K.04 mini contactors. Part of the Finder Series 6K motor control range, this protection device helps reduce the risk of motor overheating caused by excessive operating current.
Featuring a Class 10A thermal tripping characteristic, the Finder 6K.T0.0.000.0811 provides overload protection for appropriately rated industrial motors. Its adjustable current setting allows the protection threshold to be matched to the connected motor's rated current within the specified 8–11 A range.
The relay incorporates one normally open and one normally closed auxiliary contact for overload signalling and contactor control. With direct mounting compatibility for Finder 6K.04 contactors, a maximum rated operational voltage of 690 V and IP20 protection, it is suitable for integration into appropriately designed industrial motor starter assemblies.
The Finder 6K.T0.0.000.0811 provides thermal overload protection for motors controlled through compatible Finder 6K.04 mini contactors. Its adjustable 8–11 A current range enables the protection setting to be matched to the motor's rated operating current, helping reduce the risk of damage caused by prolonged overload conditions.
When the overload relay trips, its auxiliary contacts change state. The normally closed auxiliary contact can be connected into the contactor control circuit to interrupt the coil supply, while the normally open auxiliary contact can provide an overload indication or fault signal to compatible monitoring equipment.
The relay's Class 10A tripping characteristic should be considered alongside the motor's starting time, full-load current and operating duty. Thermal overload protection does not replace short-circuit protection; suitable fuses or circuit breakers must also be included in the complete motor starter installation. Reset arrangements should be selected to prevent unintended motor restarting.
Tick the specs you need, then view products that match.
| Device Type | Contactor | |
|---|---|---|
| Coil Type | AC, AC/DC, DC | |
| Manufacturer | Finder | |
| Series | 6K | |
| Model | 6K.T0.0.000.0811 | |
| Manufacturer article number | 6KT000000811 | |
| Product type | Thermal motor overload relay | |
| Adjustable current setting range | 8–11 A | |
| Tripping class | Class 10A | |
| Maximum rated operational voltage | 690 V | |
| Compatible contactor family | Finder 6K.04 | |
| Mounting method | Direct attachment to compatible contactor | |
| Normally open auxiliary contacts | 1 NO | |
| Normally closed auxiliary contacts | 1 NC | |
| Auxiliary contact material | AgNi | |
| Main circuit connection | Screw terminals | |
| Degree of protection | IP20 | |
| Stop function | Integrated stop button | |
| Automatic reset capability | Yes | |
| EAN | 8012823456744 |
The Finder 6K.T0.0.000.0811 is a thermal overload relay used to help protect appropriately rated electrical motors against sustained overload conditions. It is designed for direct attachment to compatible Finder 6K.04 mini contactors.
The overload relay has an adjustable current setting range of 8–11 A. The setting should be selected according to the connected motor's rated current and the manufacturer's installation guidance.
The Finder 6K.T0.0.000.0811 is designed for Finder Series 6K.04 mini contactors and uses a direct-attachment mounting arrangement. Compatibility with other contactor models should not be assumed.
Class 10A identifies the thermal overload relay's tripping classification. It is used when selecting overload protection for motors with appropriate starting characteristics and operating requirements.
Yes. The relay includes one normally open (1 NO) and one normally closed (1 NC) auxiliary contact. These contacts can be used for overload indication and interruption of the associated contactor control circuit when the relay trips.
Finder Series 6K thermal overload relays provide practical motor protection solutions for machine builders, electrical panel manufacturers, maintenance engineers and industrial automation professionals. Combining an adjustable 8–11 A current range, Class 10A tripping characteristics and compatibility with Finder 6K.04 mini contactors, the Finder 6K.T0.0.000.0811 supports dependable overload protection in professionally designed industrial motor starter systems.