Finder 6K.14.8.024.4718 is an 18 A industrial contactor featuring a 24 V AC coil, three normally open main contacts, one normally closed auxiliary contact, AgSnO2 contact material and DIN rail mounting for industrial motor control and electrical switching.
£31.17
The Finder 6K.14.8.024.4718 is an industrial electromagnetic contactor from the Finder Series 6K, designed for motor control, electrical load switching and machinery automation. Its part number identifies a 24 V AC coil configuration and an 18 A contactor variant, making it a suitable candidate for industrial control panels where a compatible low-voltage AC control supply is available.
The 6K.14 configuration provides a four-contact arrangement comprising three normally open main power contacts and one normally closed auxiliary contact (3 NO + 1 NC). The main contacts are intended for appropriately rated three-phase electrical loads, while the auxiliary contact provides a separate switching function for control, indication and interlocking circuits.
As part of Finder's industrial contactor family, the 6K.14.8.024.4718 offers the practical benefits of electromagnetic operation, coordinated multi-pole switching and integration into industrial electrical assemblies. Its suitability for a particular motor or load must be assessed against the manufacturer's applicable AC-3, AC-1 and auxiliary contact ratings, together with the installation's protection requirements.
The Finder 6K.14.8.024.4718 uses an electromagnetic operating mechanism controlled by its 24 V AC coil. When the correct control voltage is applied, the contactor's three normally open main contacts close to energise the connected electrical load. At the same time, the normally closed auxiliary contact opens. Removing the coil supply allows the contacts to return to their normal positions.
The 3 NO + 1 NC configuration is useful where a motor control circuit requires three main switching poles and a separate normally closed control contact. The auxiliary contact can be used for appropriately rated interlocking, signalling or monitoring arrangements. It must not be treated as an additional main power contact, and its electrical rating must be considered separately.
When selecting the contactor for a motor, engineers should verify the motor's full-load current, supply voltage, starting conditions and switching frequency against the relevant manufacturer ratings. A complete installation also requires suitable overload protection, short-circuit protection and appropriately rated conductors. For replacement work, the coil voltage and contact configuration should be matched to the original device.
Tick the specs you need, then view products that match.
| Device Type | Contactor | |
|---|---|---|
| Coil Type | AC | |
| Coil Voltage Range | 24 V | |
| Manufacturer | Finder | |
| Manufacturer Part Number | 6K.14.8.024.4718 | |
| Product Series | Finder Series 6K | |
| Contactor Type | 6K.14 | |
| Product Category | Industrial contactors | |
| Product Function | Electromagnetic power switching | |
| Nominal Coil Voltage | 24 V AC | |
| Coil Supply Type | Alternating current (AC) | |
| Contactor Current Variant | 18 A | |
| Main Contact Configuration | 3 NO | |
| Auxiliary Contact Configuration | 1 NC | |
| Combined Contact Arrangement | 3 NO + 1 NC | |
| Number of Main Power Poles | 3 | |
| Number of Auxiliary Contacts | 1 | |
| Main Contact Operating Principle | Normally open, closing upon coil energisation | |
| Auxiliary Contact Operating Principle | Normally closed, opening upon coil energisation | |
| Intended Electrical Applications | Three-phase motor control and industrial load switching | |
| Applicable Contactor Standard | IEC/EN 60947-4-1 | |
| Installation Requirements | Suitable enclosure, conductor sizing and protective coordination |
The Finder 6K.14.8.024.4718 is an industrial electromagnetic contactor intended for motor control, electrical load switching and machinery automation. Its three normally open main contacts support three-phase switching, while its normally closed auxiliary contact provides a separate control function.
The part number specifies a 24 V AC nominal operating coil. The contactor should be operated from a compatible alternating-current control supply rather than an assumed equivalent DC supply.
The Finder 6K.14.8.024.4718 has a 3 NO + 1 NC arrangement, comprising three normally open main power contacts and one normally closed auxiliary contact.
The 4718 designation identifies the 18 A contactor variant with a normally closed auxiliary contact configuration within the relevant Finder Series 6K arrangement.
Yes, the contactor is intended for appropriately rated three-phase motor switching applications. The motor's rated current, operating voltage and starting duty must be checked against the manufacturer's applicable AC-3 specifications before installation.
The normally closed auxiliary contact provides an additional switching function for suitably rated control, indication or interlocking circuits. It opens when the contactor coil is energised and closes when the contactor returns to its de-energised state.
No. The specified 24 V AC coil should not be assumed suitable for direct-current operation. A Finder contactor with a compatible DC coil should be selected where the available control supply is 24 V DC.
No. The auxiliary contact is intended for control and signalling duties within its own electrical rating. The three main power contacts must be used for appropriately rated motor switching.
A motor-control installation requires suitable short-circuit protection, motor overload protection and correctly sized conductors. The protective devices must be selected according to the motor characteristics, supply conditions and manufacturer's coordination information.
AC-1 relates to non-inductive or slightly inductive loads, while AC-3 covers specified squirrel-cage motor starting and stopping duties. These ratings are not interchangeable because motor switching produces different electrical stresses.
Yes. The Finder 6K.14.8.024.4718 can be incorporated into a suitably designed automated control panel where the control output is compatible with its 24 V AC coil and the switched load remains within the applicable ratings.
Check the exact part number, coil voltage and supply type, main and auxiliary contact arrangement, motor switching rating, mounting compatibility and terminal connections. The replacement must meet the electrical and mechanical requirements of the installation.
Finder Series 6K industrial contactors provide practical electromagnetic switching solutions for motor control, machinery and electrical automation systems. Their range of coil voltages, main contact ratings and auxiliary contact configurations helps engineers, panel builders and OEM manufacturers select contactors suited to industrial electrical control requirements.