Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 6K.13.9.024.4324 is a supplied Series 6K.13 three-pole industrial contactor reference indicating a 24 V DC coil configuration and the 4324 contact arrangement rated at 24 A AC-3 and 11 kW at 400 V AC, with exact DC-coil variant confirmation required before installation.
£73.65
The Finder 6K.13.9.024.4324 is a three-pole industrial contactor reference associated with the Finder Series 6K.13 range of electromagnetic switching devices. The 4324 contactor configuration provides three normally open main power contacts (3 NO), a 24 A AC-3 operational current rating at 400 V AC and an 11 kW three-phase motor power rating, making this contactor class suitable for industrial motor control, machinery automation and electrical power switching.
The supplied part number specifies a 24 V DC coil configuration through its 9.024 designation. Finder's published Series 6K technical documentation confirms the 24 A performance characteristics of the 6K.13.4324 contactor family, although the exact 6K.13.9.024.4324 DC-coil variant is not independently confirmed in the available manufacturer ordering information. The coil supply should therefore be checked against the product marking before installation, particularly because the corresponding 6K.13.8.024.4324 version uses a 24 V AC coil.
The Finder 6K.13 contactor design incorporates silver tin oxide (AgSnO₂) contacts, robust box-clamp screw terminals, 35 mm DIN rail mounting and IP20 protection. With provision for compatible auxiliary contact modules and thermal overload protection equipment, the Series 6K.13 range offers a practical solution for electrical panel builders, industrial maintenance engineers and OEM machinery manufacturers.
The Finder 6K.13.4324 contactor design uses an electromagnetic operating mechanism to control three normally open main power contacts. When the correctly rated coil is energised, the contacts close and supply the connected electrical load. Removing the control voltage allows the contactor to return to its de-energised state, opening the main contacts. For the supplied 6K.13.9.024.4324 reference, the indicated 24 V DC coil must be confirmed against the actual device before energisation.
The 24 A AC-3 operational current rating at 400 V AC and corresponding 11 kW motor power rating make the 4324 contactor configuration suitable for specified squirrel-cage motor starting and stopping duties. The AC-3 utilisation category accounts for the electrical stresses associated with motor switching, but the actual contactor selection must also consider motor full-load current, starting conditions, operating frequency and environmental factors.
Finder's AgSnO₂ contact material, box-clamp terminal arrangement and DIN rail construction support reliable integration into industrial control assemblies. The 6K.13 family can also be used with suitable auxiliary contact modules and 6K.T1 thermal overload relays to create more complete motor control arrangements. Short-circuit protection, overload protection and conductor sizing must be selected for the complete installation, and the stated conditional short-circuit rating applies only with the manufacturer's specified protective coordination.
Tick the specs you need, then view products that match.
| Terminal Type | Screw | |
|---|---|---|
| Device Type | Contactor | |
| Coil Type | DC | |
| Coil Voltage Range | 24 V | |
| Manufacturer | Finder | |
| Supplied Part Number | 6K.13.9.024.4324 | |
| Product Series | Finder Series 6K | |
| Contactor Type | 6K.13 | |
| Product Type | Industrial electromagnetic contactor | |
| Contact Configuration | 3 NO | |
| Contact Arrangement | 3PST-NO | |
| Number of Main Contacts | 3 normally open | |
| Number of Main Poles | 3 | |
| Integrated Auxiliary Contacts | None in the standard 6K.13.4324 main contact arrangement | |
| Coil Voltage Indicated by Part Number | 24 V DC | |
| Coil Supply Type Indicated by Part Number | Direct current (DC) | |
| Exact DC-Coil Variant Status | Requires confirmation against Finder ordering information or product marking | |
| Rated Operational Current, AC-3 | 24 A at 400 V AC | |
| Rated Motor Power, AC-3 | 11 kW at 400 V AC | |
| Contact Material | Silver tin oxide (AgSnO₂) | |
| Mounting Method | DIN rail | |
| Compatible DIN Rail | 35 mm, EN 60715 | |
| Terminal Type | Box-clamp screw terminals | |
| Minimum Conductor Cross-Section | 1.5 mm² | |
| Maximum Conductor Cross-Section | 25 mm² | |
| Terminal Tightening Torque | 2.5 Nm | |
| Wire Stripping Length | 13 mm | |
| Protection Rating | IP20 | |
| Rated Conditional Short-Circuit Current | 10 kA with specified protective arrangements | |
| Back-Up Fuse | 100 A gG/gL type for the manufacturer's specified coordination arrangement | |
| Operating Temperature Range | −40 to +70 °C for the published 6K.13 contactor range | |
| Shock Resistance, Normally Open Contacts | 8 g | |
| Power Loss per Pole, AC-3 at 400 V AC | 1.3 W | |
| Product Width | 45 mm | |
| Product Height | 83.5 mm | |
| Product Depth | 74 mm | |
| Compatible Auxiliary Contact Modules | Finder 06K.11 and 06K.12, subject to installation compatibility | |
| Compatible Thermal Overload Relay Series | Finder 6K.T1 | |
| Applicable Contactor Standard | IEC/EN 60947-4-1 | |
| Product Category | Industrial motor control and electromagnetic power switching |
The Finder 6K.13.9.024.4324 is a supplied reference associated with the Finder Series 6K.13 industrial contactor range. The 4324 configuration is designed for three-phase motor control and electrical power switching, with three normally open main contacts and a 24 A AC-3 rating at 400 V AC.
The 9.024 designation indicates a 24 V DC coil configuration. However, the exact 6K.13.9.024.4324 variant has not been independently confirmed in the available Finder ordering information, so the coil voltage must be checked against the product marking before installation.
The Finder 6K.13.4324 configuration has three normally open main power contacts (3 NO). These contacts close when the contactor is energised and open when the coil is de-energised.
The Finder 6K.13.4324 contactor configuration has a 24 A AC-3 operational current rating at 400 V AC. This rating applies to specified squirrel-cage motor switching duties.
The 4324 configuration has an 11 kW AC-3 motor power rating at 400 V AC. Actual suitability must also be checked against the motor's rated current, starting characteristics and protection requirements.
The supplied 6K.13.9.024.4324 reference indicates a 24 V DC coil, whereas the documented 6K.13.8.024.4324 uses a 24 V AC coil. The exact DC variant requires manufacturer confirmation. AC and DC coils must not be assumed interchangeable.
Within the Finder Series 6K.13 range, the 4324 configuration is rated at 24 A AC-3 and 11 kW, while the 4332 configuration is rated at 32 A AC-3 and 15 kW, both at 400 V AC. The correct version depends on the motor's electrical requirements.
Yes. The Finder Series 6K.13 supports compatible auxiliary contact modules, including Finder 06K.11 normally open and 06K.12 normally closed contact accessories. These can provide additional signalling and control functions when fitted according to the manufacturer's instructions.
The Finder Series 6K.13 supports suitable Finder 6K.T1 thermal overload protection relays. The correct relay adjustment range must be selected according to the motor's rated current and the installation's protection requirements.
The Finder 6K.13 contactor is designed for 35 mm DIN rail mounting in accordance with EN 60715. Its compact construction supports installation inside industrial electrical cabinets and machinery control panels.
The published Finder 6K.13.4324 terminal specifications support suitable conductors from 1.5 to 25 mm², with a 2.5 Nm tightening torque and a 13 mm wire stripping length.
The Finder 6K.13.4324 contactor family has a 10 kA conditional short-circuit current rating with the manufacturer's specified protective arrangements. The technical documentation identifies a 100 A gG/gL back-up fuse for the applicable coordination arrangement; the complete installation must follow the manufacturer's protection requirements.
Finder Series 6K industrial contactors offer compact electromagnetic switching solutions for industrial motors, machinery and electrical control systems. Their defined AC-3 motor ratings, AgSnO₂ contact construction, robust box-clamp terminals and compatibility with auxiliary contacts and thermal overload relays make them a practical choice for engineers, panel builders and OEM manufacturers developing dependable industrial motor control installations.