Finder 06K.06 is a four-contact auxiliary module featuring 2 normally open and 2 normally closed mechanically linked contacts rated at 2 A, 400 V AC-15, for compatible Finder Series 6K Type 6K.04 industrial contactors.
£12.42
The Finder 06K.06 is a four-contact auxiliary contact module designed for use with Finder Series 6K Type 6K.04 industrial contactors. Featuring 2 normally open (NO) and 2 normally closed (NC) contacts, this accessory expands the control and signalling capabilities of compatible contactors in industrial automation and electrical control applications.
With a contact rating of 2 A at 400 V AC-15, the Finder 06K.06 is suitable for auxiliary control circuits, contactor status indication, electrical interlocking and automation signalling. Its mechanically linked contacts are designed in accordance with EN 60947-5-1, supporting coordinated auxiliary contact operation in appropriately designed control systems.
The module incorporates silver-nickel (AgNi) contacts and screw terminals for electrical connections. Designed specifically for the Finder 6K.04 contactor family, it provides a practical solution for expanding auxiliary contact availability without introducing a separate control relay.
The Finder 06K.06 expands the available control contacts of a compatible Finder 6K.04 industrial contactor. When the associated contactor operates, the auxiliary contacts change state, allowing external control circuits to monitor contactor operation or perform additional switching functions. The two normally open contacts close when actuated, while the two normally closed contacts open.
The 2 NO + 2 NC arrangement allows several control functions to be implemented using a single accessory. Typical examples include auxiliary feedback to a programmable logic controller, status indication lamps, electrical interlocking arrangements and control circuit permissives. The mechanically linked contact design supports applications requiring coordinated contact states, subject to the complete control system design.
The module is intended for auxiliary circuits rather than direct switching of the contactor's main power load. Its 2 A at 400 V AC-15 operational rating must be considered separately from the main contactor's power switching capability. Installation and wiring should follow Finder's Series 6K technical documentation.
Tick the specs you need, then view products that match.
| Terminal Type | Screw | |
|---|---|---|
| Device Type | Accessory | |
| Manufacturer | Finder | |
| Product series | Series 6K | |
| Model | 06K.06 | |
| Manufacturer part number | 06K.06 | |
| Product type | Auxiliary Contact Module | |
| Category | Contactor Accessories | |
| Compatible contactor | Finder Type 6K.04 | |
| Auxiliary contact configuration | 2 NO + 2 NC | |
| Total number of contacts | 4 | |
| Rated operational current (AC-15) | 2 A at 400 V AC | |
| Conventional thermal current | 10 A | |
| Rated contact voltage | 400 V AC for the specified AC-15 operational rating | |
| Contact material | Silver-nickel (AgNi) | |
| Contact arrangement | Mechanically linked | |
| Applicable contact standard | EN 60947-5-1 | |
| Terminal type | Screw terminals | |
| Conductor stripping length | 8 mm | |
| Maximum conductor cross-section | 2.5 mm² | |
| Minimum conductor cross-section | 0.5 mm² | |
| Control coil | Not incorporated; operated by the associated contactor | |
| Typical application | Industrial contactor auxiliary control and signalling |
The Finder 06K.06 is an auxiliary contact module designed to provide additional normally open and normally closed contacts for compatible Finder Type 6K.04 industrial contactors.
The module contains four auxiliary contacts, consisting of 2 normally open (NO) and 2 normally closed (NC) contacts.
The Finder 06K.06 is specifically designed for Finder Series 6K Type 6K.04 industrial contactors. Compatibility with other contactor types should not be assumed.
The auxiliary contacts are rated at 2 A at 400 V AC-15. The module also has a 10 A conventional thermal current rating, which is not equivalent to its AC-15 switching rating.
2 NO + 2 NC means the module contains two normally open contacts and two normally closed contacts. These change state when the associated contactor operates, providing additional control and signalling functions.
Yes. Finder specifies mechanically linked auxiliary contacts for the 06K.06 module in accordance with EN 60947-5-1.
The module uses screw terminals for auxiliary circuit wiring, with a specified conductor stripping length of 8 mm.
Yes. Its auxiliary contacts can provide contactor status signals to suitable PLC inputs, provided the control circuit voltage, current and input requirements are compatible with the module's ratings.
The Finder 06K.03 provides 1 NO + 1 NC auxiliary contact, while the Finder 06K.06 provides 2 NO + 2 NC contacts. Both are designed for compatible Finder Type 6K.04 contactors.
No. The 06K.06 is a mechanically operated auxiliary contact module and does not incorporate a separate control coil. Its contacts operate through the associated Finder contactor.
Finder Series 6K industrial contactors and auxiliary modules are designed for dependable switching and control applications. The Finder 06K.06 provides four mechanically linked auxiliary contacts, a 2 A AC-15 operational rating and dedicated compatibility with Finder 6K.04 contactors, making it a practical accessory for control panel builders, automation engineers and industrial maintenance professionals.