Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato BFK2600A46060 three-pole power factor correction contactor with limiting resistors, a 460 V AC 60 Hz coil and a 20 kVAr IEC operational power rating at 400 V for capacitor bank switching.
£88.35
The Lovato BFK2600A46060 is a dedicated three-pole power factor correction contactor designed for reliable capacitor bank switching in industrial reactive power compensation systems. Part of the Lovato BFK26 series, it is purpose-built for AC-6b capacitor switching duties and incorporates limiting resistors to help control the high inrush currents generated when capacitor stages are energised.
This contactor features a 460 V AC coil designed for 60 Hz operation and three normally open main contacts. Its dedicated capacitor-switching construction makes it suitable for automatic power factor correction equipment, reactive power compensation panels and industrial electrical distribution systems.
With a maximum IEC operational power of 20 kvar at 400 V, together with ratings of 11 kvar at 230 V, 22 kvar at 440–480 V and 25 kvar at 690 V, the BFK2600A46060 provides a versatile solution for medium-sized capacitor switching stages in professional power factor correction installations.
Power factor correction contactors are designed specifically to switch capacitor stages used to compensate for reactive power in electrical installations. Capacitors can produce substantial transient inrush currents when energised, so the Lovato BFK2600A46060 incorporates limiting resistors to help control these current peaks during switching.
The BFK2600A46060 combines dedicated capacitor-switching performance with a 20 kvar rating at 400 V and a 460 V AC 60 Hz control coil, making it suitable for compatible automatic power factor correction panels where reliable and repetitive capacitor bank operation is required.
Tick the specs you need, then view products that match.
| Coil Voltage Range | 460–500 V | |
|---|---|---|
| Device Type | Capacitor Switching Contactor | |
| Poles | 3-pole | |
| Coil / Supply Voltage | 460 V AC | |
| Auxiliary Contacts | None | |
| Coil Type | AC | |
| Current AC-1 | 45 A | |
| HS Code | 85365080 | |
| Manufacturer | Lovato Electric | |
| Series | BFK26 | |
| Model | BFK2600A46060 | |
| Product type | Power factor correction contactor | |
| Application | Capacitor bank switching | |
| Number of poles | 3 | |
| Main contact configuration | 3 NO | |
| Coil type | AC coil 60 Hz | |
| Rated coil voltage | 460 V AC | |
| IEC operational power at 230 V | 11 kvar | |
| IEC operational power at 400 V | 20 kvar | |
| IEC operational power at 440–480 V | 22 kvar | |
| IEC operational power at 690 V | 25 kvar | |
| Conventional free-air thermal current Ith at ≤40 °C | 45 A | |
| Rated insulation voltage Ui | 690 V | |
| Rated impulse withstand voltage Uimp | 6 kV | |
| Short-time allowable current | 210 A for 10 s | |
| Making capacity | 260 A RMS | |
| Protection fuse | 40 A gG | |
| Operational frequency | 25–400 Hz | |
| Power terminal protection | IP20 when properly wired | |
| Mounting type | Screw fixing / 35 mm DIN rail | |
| Operating position | Vertical plane, ±30° allowable | |
| Mechanical life | 20,000,000 cycles | |
| Electrical life | 1,600,000 cycles | |
| Operating temperature | −50 to +70 °C | |
| Maximum altitude | 3000 m | |
| Pollution degree | 3 | |
| Dimensions (W × H × D) | approx. 45 × 126 × 123 mm | |
| Weight | approx. 474 g |
The Lovato BFK2600A46060 is designed for switching capacitor banks in automatic power factor correction and reactive power compensation systems.
The BFK2600A46060 has a maximum IEC operational power rating of 20 kVAr at 400 V.
The contactor uses a 460 V AC coil designed for 60 Hz operation.
Yes. The BFK2600A46060 incorporates limiting resistors to help control the high inrush currents generated when capacitor stages are energised.
No. The BFK2600A46060 has no built-in auxiliary contacts.
Lovato BFK contactors are purpose-designed for capacitor switching, combining dedicated power factor correction ratings with limiting resistors and robust industrial electrical characteristics for reliable reactive power compensation systems.
We use cookies