Lovato BFK1810A110 is a three-pole power factor correction contactor with integrated limiting resistors, a 1NO auxiliary contact, a 15 kvar rating at 400 V AC-6b and a 110 V AC 50/60 Hz coil for capacitor bank switching.
£57.30
The Lovato BFK1810A110 is a specialised three-pole power factor correction contactor designed for reliable switching of capacitor banks in industrial and commercial electrical installations. As part of the Lovato BFK18 contactor series, it is specifically designed for AC-6b capacitor switching duties and incorporates limiting resistors to control the high inrush currents associated with energising capacitors.
The BFK1810A110 provides a maximum IEC operational power rating of 15 kvar at 400 V and features a 110 V AC 50/60 Hz coil. It also incorporates a 1NO auxiliary contact, providing an additional normally open contact for signalling, interlocking or control functions within power factor correction equipment.
With a conventional free-air thermal current of 32 A, rated insulation voltage of 690 V and rated impulse withstand voltage of 6 kV, the BFK1810A110 is engineered for dependable capacitor switching. Screw fixing or 35 mm DIN rail mounting enables straightforward integration into automatic power factor correction panels and electrical control cabinets.
Power factor correction contactors such as the Lovato BFK1810A110 are specifically engineered for switching capacitor banks. Capacitors can produce substantial transient inrush currents when energised, so the BFK design incorporates limiting resistors that reduce these current peaks and help minimise electrical stress during switching.
The BFK1810A110 provides 15 kvar at 400 V AC-6b and combines dedicated capacitor switching characteristics with a 110 V AC 50/60 Hz coil. Its three-pole design, built-in auxiliary contact and panel-friendly mounting options make it suitable for automatic power factor correction equipment in industrial and commercial installations.
Tick the specs you need, then view products that match.
| Coil Voltage Range | 100–130 V | |
|---|---|---|
| Device Type | Capacitor Switching Contactor | |
| Poles | 3-pole | |
| Coil / Supply Voltage | 110 V AC | |
| Auxiliary Contacts | 1NO | |
| Coil Type | AC | |
| Current AC-1 | 32 A | |
| HS Code | 85365080 | |
| Manufacturer | Lovato Electric | |
| Series | BFK18 | |
| Model | BFK1810A110 | |
| Product type | Contactor for power factor correction with AC control circuit | |
| Number of poles | 3 | |
| Built-in auxiliary contacts | 1NO | |
| Coil type | AC coil 50/60 Hz | |
| Rated coil voltage | 110 V AC | |
| Rated operational power AC-6b at 230 V | 9 kvar | |
| Rated operational power AC-6b at 400 V | 15 kvar | |
| Rated operational power AC-6b at 440–480 V | 17 kvar | |
| Rated operational power AC-6b at 690 V | 20 kvar | |
| IEC conventional free-air thermal current Ith (≤40°C) | 32 A | |
| Rated insulation voltage Ui | 690 V | |
| Rated impulse withstand voltage Uimp | 6 kV | |
| Operational frequency | 25–400 Hz | |
| Short-time allowable current for 10 s | 200 A | |
| Recommended gG protection fuse | 40 A | |
| Making capacity | 180 A RMS | |
| Breaking capacity at 440 V | 144 A | |
| Breaking capacity at 500 V | 120 A | |
| Breaking capacity at 690 V | 94 A | |
| Resistance per pole | 2.5 mΩ | |
| Power dissipation per pole at Ith | 2.6 W | |
| Main terminal tightening torque | 1.5–1.8 Nm | |
| Power terminal protection | IP20 when correctly wired | |
| Auxiliary contact thermal current | 10 A | |
| Auxiliary contact designation | A600 - P600 | |
| Mechanical life | 20,000,000 cycles | |
| Electrical life | 400,000 cycles | |
| Coil inrush consumption at 50 Hz | 75 VA | |
| Coil holding consumption at 50 Hz | 9 VA | |
| Coil inrush consumption at 60 Hz | 70 VA | |
| Coil holding consumption at 60 Hz | 6.5 VA | |
| Maximum mechanical operating frequency | 3600 cycles/h | |
| Operating temperature | -50 to +70°C | |
| Storage temperature | -60 to +80°C | |
| Maximum altitude | 3000 m | |
| Pollution degree | 3 | |
| Mounting type | Screw / DIN rail 35 mm | |
| Weight | 418 g | |
| EAN | 8013975163276 |
The BFK1810A110 is a three-pole contactor designed specifically for switching capacitor banks in automatic power factor correction and reactive power compensation systems.
The BFK1810A110 has an IEC AC-6b rated operational power of 15 kvar at 400 V.
The BFK1810A110 uses a 110 V AC 50/60 Hz coil for operation from compatible AC control circuits.
Yes. The BFK1810A110 incorporates limiting resistors designed to reduce the high inrush current produced when capacitor stages are energised.
Yes. The BFK1810A110 includes a built-in 1NO auxiliary contact for use in signalling, interlocking and control circuits.
Lovato Electric BFK contactors are purpose-designed for capacitor switching in power factor correction systems, combining integrated inrush-current limiting resistors with dependable electrical performance for industrial and commercial installations.