Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato BFK1210A04860 three-pole power factor correction contactor with limiting resistors, a 48 V AC 60 Hz control coil and a maximum IEC AC-6b operational power rating of 12.5 kvar at 400 V for capacitor switching applications.
£61.45
The Lovato BFK1210A04860 is a three-pole power factor correction contactor designed specifically for switching capacitor banks in industrial and commercial power factor correction systems. Part of the Lovato BFK12 contactor series, it incorporates limiting resistors to control the high inrush currents associated with capacitor switching.
The BFK1210A04860 provides a maximum IEC AC-6b operational power rating of 12.5 kvar at 400 V, with additional ratings of 7 kvar at 230 V, 14 kvar at 440–480 V and 16 kvar at 690 V. Its three normally open main poles provide reliable switching of three-phase capacitor stages in automatic power factor correction equipment.
Featuring a 48 V AC 60 Hz control coil, a rated insulation voltage of 690 V and an IEC conventional free-air thermal current of 28 A, the BFK1210A04860 provides a purpose-built solution for capacitor switching. Screw terminals and support for 35 mm DIN rail or screw mounting simplify integration into power factor correction panels.
Power factor correction contactors are specifically engineered for switching capacitor banks, where energisation can produce substantially higher transient currents than conventional loads. The Lovato BFK1210A04860 incorporates limiting resistors to manage these capacitor switching conditions and provide reliable operation in automatic power factor correction equipment.
With an AC-6b rating of 12.5 kvar at 400 V, the BFK1210A04860 is suited to individual capacitor stages in low-voltage PFC banks. Its three-pole configuration, 48 V AC 60 Hz control coil and flexible mounting options make it straightforward to integrate into new or existing power factor correction panels.
Tick the specs you need, then view products that match.
| Coil Voltage Range | 42–48 V | |
|---|---|---|
| Device Type | Capacitor Switching Contactor | |
| Poles | 3-pole | |
| Coil Type | AC | |
| Current AC-1 | 28 A | |
| HS Code | 85365080 | |
| Manufacturer | Lovato Electric | |
| Series | BFK12 | |
| Model | BFK1210A04860 | |
| Product type | Power factor correction contactor | |
| Number of poles | 3 | |
| Main contact configuration | 3NO | |
| Control circuit | AC | |
| Rated control voltage | 48 V AC | |
| Control frequency | 60 Hz | |
| Rated insulation voltage Ui | 690 V | |
| Rated impulse withstand voltage Uimp | 6 kV | |
| Operational frequency | 25–400 Hz | |
| IEC conventional free-air thermal current Ith | 28 A | |
| AC-6b operational power at 230 V | 7 kvar | |
| AC-6b operational power at 400 V | 12.5 kvar | |
| AC-6b operational power at 440–480 V | 14 kvar | |
| AC-6b operational power at 690 V | 16 kvar | |
| Short-time allowable current for 10 s | 150 A | |
| Recommended gG protection fuse | 25 A | |
| Making capacity | 120 A RMS | |
| Breaking capacity at 440 V | 96 A | |
| Breaking capacity at 500 V | 96 A | |
| Breaking capacity at 690 V | 94 A | |
| Resistance per pole | 2.5 mΩ | |
| Power dissipation per pole at Ith | 2 W | |
| Main terminal tightening torque | 1.5–1.8 Nm | |
| Coil terminal tightening torque | 0.8–1 Nm | |
| Maximum number of simultaneously connectable wires | 2 | |
| Main circuit connection | Screw connection | |
| Mounting type | Screw / 35 mm DIN rail | |
| Operating temperature | -50 to +70 °C | |
| Storage temperature | -60 to +80 °C | |
| Maximum altitude | 3000 m | |
| Pollution degree | 3 | |
| Mechanical life | 20,000,000 cycles | |
| Weight | 416 g |
The BFK1210A04860 is designed for switching capacitors in power factor correction systems and includes limiting resistors for capacitor switching applications.
The contactor has a maximum IEC AC-6b operational power rating of 12.5 kvar at 400 V.
The BFK1210A04860 has a 48 V AC control coil rated for 60 Hz operation.
Yes. The BFK1210A04860 incorporates limiting resistors specifically for capacitor switching in power factor correction applications.
The contactor supports screw fixing or mounting on a 35 mm DIN rail for integration into power factor correction panels and electrical control cabinets.
Lovato BFK contactors are designed specifically for capacitor switching in power factor correction systems, combining dedicated inrush-current limiting technology with robust industrial electrical ratings for dependable PFC panel operation.
We use cookies