Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato BF4000A23060 BF40 three-pole power contactor with a 40 A AC-3 rating, 18.5 kW motor rating at 400 V AC and 230 V AC 60 Hz control coil for industrial motor-control applications.
£96.06
The Lovato BF4000A23060 is a robust three-pole power contactor designed for reliable switching of three-phase motors and industrial electrical loads. Part of the Lovato BF40 series, it provides an IEC AC-3 operational current rating of 40 A at up to 440 V and combines compact installation with high electrical and mechanical endurance.
For motor-control applications, the BF4000A23060 is rated for 18.5 kW at 400 V AC, 22 kW at 415–440 V AC and up to 30 kW at 690 V AC. It also provides a conventional free-air thermal current of 70 A at up to 40 °C, making it suitable for both motor switching and general-purpose AC-1 loads.
This specific BF4000A23060 version features a 230 V AC, 60 Hz control coil. With a rated insulation voltage of 1000 V, an 8 kV impulse withstand rating, IP20 front terminal protection and screw or 35 mm DIN rail mounting, it is well suited to industrial machinery, motor-control panels and automation systems.
The Lovato BF4000A23060 provides electromagnetic switching between industrial control circuitry and higher-power three-phase motor loads. Energising the 230 V AC coil closes the contactor's three main poles, allowing PLCs, control relays, motor starters and automated machinery to start and stop motors without routing the full motor current through the control device.
Its 40 A AC-3 rating, high switching endurance and 18.5 kW motor capacity at 400 V AC make the BF40 suitable for frequent industrial motor-control duties. The combination of DIN rail or screw mounting, IP20 front protection and a broad range of compatible Lovato accessories also supports straightforward integration into new and existing control-panel designs.
Tick the specs you need, then view products that match.
| Terminal Type | Screw | |
|---|---|---|
| Coil Voltage Range | 200–250 V | |
| Power | 18.5 kW | |
| Current | 40 A | |
| Poles | 3-pole | |
| Coil / Supply Voltage | 230 V AC | |
| Device Type | Contactor | |
| Coil Type | AC | |
| Current AC-1 | 70 A | |
| HS Code | 85365080 | |
| Manufacturer | Lovato Electric | |
| Series | BF40 | |
| Product designation | Power contactor | |
| Model / order code | BF4000A23060 | |
| Product type | Three-pole power contactor | |
| Number of poles | 3 | |
| Rated operational current AC-3 at ≤440 V | 40 A | |
| Rated operational current AC-4 at 400 V | 24 A | |
| Conventional free-air thermal current Ith at ≤40 °C | 70 A | |
| AC-1 operational current at ≤40 °C | 70 A | |
| AC-1 operational current at ≤55 °C | 60 A | |
| AC-1 operational current at ≤70 °C | 50 A | |
| AC-3 motor power at 230 V | 11 kW | |
| AC-3 motor power at 400 V | 18.5 kW | |
| AC-3 motor power at 415 V | 22 kW | |
| AC-3 motor power at 440 V | 22 kW | |
| AC-3 motor power at 500 V | 22 kW | |
| AC-3 motor power at 690 V | 30 kW | |
| Rated coil voltage | 230 V AC | |
| Coil frequency | 60 Hz | |
| Rated insulation voltage Ui | 1000 V | |
| Rated impulse withstand voltage Uimp | 8 kV | |
| Operational frequency | 25–400 Hz | |
| Short-time allowable current for 10 s | 400 A | |
| Making capacity | 400 A RMS | |
| Breaking capacity at 440 V | 320 A | |
| Recommended gG protection fuse | 100 A | |
| Recommended aM protection fuse | 50 A | |
| Main terminal conductor capacity | 1.5–35 mm² flexible | |
| Main terminal tightening torque | 4–5 Nm | |
| Power terminal protection | IP20 front | |
| Mechanical life | 15,000,000 cycles | |
| Electrical life | 1,500,000 cycles | |
| Maximum mechanical operating frequency | 3600 cycles/h | |
| Coil consumption at 60 Hz | 210 VA inrush / 15 VA holding | |
| Operating temperature | -50 to +70 °C | |
| Storage temperature | -60 to +80 °C | |
| Maximum installation altitude | 3000 m | |
| Normal operating position | Vertical plane | |
| Permitted mounting inclination | ±30° | |
| Mounting | Screw or 35 mm DIN rail | |
| Weight | 1020 g | |
| UL/CSA motor rating at 480 V | 30 HP |
The Lovato BF4000A23060 is a three-pole power contactor designed for switching three-phase motors and other industrial electrical loads in machinery, motor starters and automation systems.
The BF4000A23060 has an AC-3 operational current rating of 40 A at up to 440 V and an AC-1 operational current rating of 70 A at up to 40 °C.
The contactor is rated for three-phase motors up to 18.5 kW at 400 V AC, 22 kW at 415–440 V AC and 30 kW at 690 V AC.
This specific BF40 contactor uses a 230 V AC control coil designed for 60 Hz operation.
The BF4000A23060 can be installed using screw mounting or a 35 mm DIN rail, providing flexible installation in industrial control panels and motor-control assemblies.
Lovato BF series power contactors are designed for dependable industrial motor and load switching, combining high electrical endurance, robust construction and flexible panel mounting for machinery, automation and motor-control applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.