ABB DRAF09-13N 1SBK134137R1300 is an IP66 enclosed direct-on-line starter rated at 9 A at 400 V for three-phase motors, with a 100–250 V AC 50/60 Hz control supply and support for motors up to 4 kW at 380–400 V.
£56.15
The ABB DRAF09-13N, order code 1SBK134137R1300, is an enclosed direct-on-line (DOL) motor starter designed for switching and controlling three-phase AC motors. Combining an ABB AF contactor with a robust enclosure, the DRAF09-13N provides a practical motor-control solution for machinery, pumps, fans and other industrial equipment.
The DRAF09-13N is rated for a maximum operational current of 9 A at 400 V and supports three-phase motors rated up to 2.2 kW at 220–240 V, 4 kW at 380–400 V and 5.5 kW at 500–690 V. Its AF contactor uses electronic coil technology with a wide 100–250 V AC 50/60 Hz control voltage range.
Designed as an enclosed starter, the DRAF09-13N provides IP66 protection for demanding installation environments. A compatible ABB TF42 thermal overload relay can be selected separately to provide motor overload protection, allowing the starter to be configured to suit the connected motor's rated current.
Direct-on-line starters such as the ABB DRAF09-13N switch the full supply voltage directly to a three-phase motor when starting. This straightforward motor-control method is widely used where the electrical supply and driven equipment can accommodate the motor's direct starting current and torque.
The DRAF09-13N combines ABB AF contactor technology with a protective enclosure to simplify the implementation of an enclosed motor starter. When paired with a correctly selected TF42 thermal overload relay, it provides a compact solution for motor switching and overload protection in industrial machinery and process equipment.
Tick the specs you need, then view products that match.
| Poles | 3-pole | |
|---|---|---|
| Coil Voltage Range | 100–130 V, 200–250 V | |
| Coil / Supply Voltage | 110 V AC, 115 V AC, 120 V AC, 208 V AC, 220 V AC, 230 V AC, 240 V AC | |
| Device Type | Accessory | |
| Coil Type | AC | |
| Manufacturer | ABB | |
| Series | DRAF | |
| Model | DRAF09-13N | |
| Order code | 1SBK134137R1300 | |
| Product type | Enclosed direct-on-line motor starter | |
| Motor phases | 3-phase | |
| Maximum operational current at 400 V | 9 A | |
| Motor power at 220–240 V | 2.2 kW | |
| Motor power at 380–400 V | 4 kW | |
| Motor power at 500 V | 5.5 kW | |
| Motor power at 690 V | 5.5 kW | |
| Control voltage | 100–250 V AC, 50/60 Hz | |
| Control supply wiring | Phase / neutral | |
| Protection rating | IP66 | |
| Compatible overload relay | ABB TF42 series, ordered separately | |
| Dimensions (H × W × D) | 230 × 126.5 × 131.5 mm | |
| Weight | 0.820 kg |
The DRAF09-13N is an enclosed direct-on-line starter designed for switching and controlling three-phase AC motors in industrial equipment.
The DRAF09-13N supports motors rated up to 2.2 kW at 220–240 V, 4 kW at 380–400 V and 5.5 kW at 500–690 V.
The DRAF09-13N uses a 100–250 V AC 50/60 Hz control supply with phase-to-neutral control wiring.
The DRAF09-13N has an IP66 protection rating, providing a high level of protection against dust and water ingress.
No. A compatible ABB TF42 thermal overload relay is ordered separately and should be selected according to the rated current of the connected motor.
ABB DRAF enclosed direct-on-line starters combine proven AF contactor technology, wide-range electronic coil control and robust enclosure protection to provide dependable motor switching for industrial machinery and equipment.