ABB CM-MPN.72S 1SVR750489R8300 is a multifunctional three-phase monitoring relay for 530–820 V AC systems with TRMS measurement, phase failure, phase sequence, overvoltage, undervoltage and phase unbalance monitoring, configurable dual changeover outputs and screw terminals.
£213.04
The ABB CM-MPN.72S, order code 1SVR750489R8300, is a multifunctional three-phase monitoring relay designed for supervision of high-voltage three-phase electrical systems. It monitors phase failure, phase sequence, overvoltage, undervoltage and phase unbalance, helping protect motors, machinery and industrial automation equipment against abnormal supply conditions.
The CM-MPN.72S operates directly from the monitored circuit with a 3 × 530–820 V AC line-to-line rated control supply and measuring voltage at 50/60 Hz. Adjustable threshold values enable the monitoring response to be matched to the installation, while selectable phase sequence monitoring and automatic phase sequence correction provide additional flexibility for three-phase applications.
With two configurable changeover (SPDT) output contacts rated at 250 V / 4 A, a 200 ms start-up delay and selectable instantaneous or 0.1–30 s tripping delay, the CM-MPN.72S provides flexible signalling and control. Screw terminals with double-chamber cage connections and a compact 45 mm DIN-rail housing support secure installation in industrial control panels.
Three-phase monitoring relays continuously supervise the incoming electrical supply and provide a switching response when monitored parameters move outside configured limits. The ABB CM-MPN.72S monitors phase presence, phase sequence, voltage levels and phase balance, helping protect industrial equipment from potentially damaging three-phase supply faults.
Its 530–820 V AC line-to-line range makes the CM-MPN.72S particularly suitable for higher-voltage industrial three-phase networks. Configurable output operation allows the contacts to provide either a common signal or separate overvoltage and undervoltage signals, while adjustable thresholds and timing functions allow the monitoring response to be matched to the application.
Tick the specs you need, then view products that match.
| Time Delay | Adjustable | |
|---|---|---|
| Monitoring Function | Three-phase supply | |
| Monitored Supply | Three-phase | |
| Signal / Input Range | 3 × 530–820 V AC | |
| Series | CM-MPN | |
| ABB order code | 1SVR750489R8300 | |
| Product group | 310921 – Measuring & Monitoring Relays | |
| Product type | Multifunctional three-phase monitoring relay | |
| Rated control supply voltage | 3 × 530–820 V AC line-to-line | |
| Measuring range | 3 × 530–820 V AC line-to-line | |
| Rated frequency | 50/60 Hz | |
| Supply source | Powered from measuring circuit | |
| Measuring principle | TRMS | |
| Phase failure monitoring | Yes | |
| Phase sequence monitoring | Yes, selectable | |
| Automatic phase sequence correction | Yes | |
| Overvoltage monitoring | Yes | |
| Undervoltage monitoring | Yes | |
| Phase unbalance monitoring | Yes | |
| Start-up delay | 200 ms | |
| Tripping delay | 0 s or adjustable 0.1–30 s | |
| Tripping function | ON- or OFF-delay, selectable | |
| Output | 2 × 1 c/o or 1 × 2 c/o (SPDT) contacts, configurable | |
| Contact rating | 250 V / 4 A | |
| Connection technology | Screw terminals with double-chamber cage connections | |
| Housing protection | IP50 | |
| Terminal protection | IP20 | |
| Operating temperature | -25 to +60 °C | |
| Storage temperature | -40 to +85 °C | |
| Mounting type | DIN rail | |
| Width | 45 mm | |
| Height | 85.6 mm | |
| Depth | 104.8 mm | |
| Net weight | 0.224 kg |
The CM-MPN.72S is used to monitor three-phase electrical supplies for phase failure, phase sequence, overvoltage, undervoltage and phase unbalance conditions.
The CM-MPN.72S has a line-to-line rated control supply and measuring range of 3 × 530–820 V AC at 50/60 Hz.
Yes. The relay provides selectable phase sequence monitoring and supports automatic phase sequence correction.
The relay has a 200 ms start-up delay and selectable ON- or OFF-delay operation with an instantaneous 0 s setting or an adjustable 0.1–30 s tripping delay.
The CM-MPN.72S uses screw terminals with double-chamber cage connections and provides two configurable changeover contacts that can operate as 2 × 1 c/o or 1 × 2 c/o outputs.
ABB CM three-phase monitoring relays provide dependable supervision of voltage and phase conditions in industrial electrical systems, helping protect motors, machinery and automation equipment against abnormal three-phase supply conditions.