Carlo Gavazzi CPTDINAV63LR2AX advanced three-phase power transducer with two relay outputs for industrial energy monitoring and automation systems.
The Carlo Gavazzi CPTDINAV63LR2AX is a compact and advanced three-phase power transducer designed for accurate electrical measurement, monitoring and control in industrial energy management and automation systems. As part of the CPT-DIN Advanced Power Transducer series, it provides reliable measurement of electrical parameters with configurable relay outputs for integration into modern industrial installations.
This DIN-rail mounted power transducer is designed to monitor electrical variables including voltage, current, power, energy and power factor. Its programmable functions, alarm capabilities and compact enclosure make it suitable for installation in control panels, machinery and industrial monitoring systems where dependable electrical data is required.
The CPTDINAV63LR2AX features an AV6 three-phase measurement configuration, an 18–60 VAC/DC auxiliary supply and two relay outputs for alarm and control functions, providing flexible monitoring and automation integration.
The Carlo Gavazzi CPT-DIN Advanced series provides accurate monitoring of electrical parameters to support industrial energy management, machine diagnostics and automation control. The CPTDINAV63LR2AX combines measurement functionality with programmable relay outputs, allowing electrical conditions and alarms to be monitored directly within industrial systems.
Its compact DIN-rail format, configurable parameters and advanced measurement functions make it suitable for improving energy visibility, monitoring equipment performance and supporting reliable industrial automation.
Tick the specs you need, then view products that match.
| Measurement Connection Type | CT connection | |
|---|---|---|
| Coil / Supply Voltage | 18–60 V AC/DC | |
| Device Type | Power transducer | |
| Phase | Three Phase | |
| Signal / Input Range | AC V / A (TRMS), CT input (/5 A or /1 A) | |
| Manufacturer | Carlo Gavazzi | |
| Series | CPT-DIN Advanced | |
| Model | CPTDINAV63LR2AX | |
| Product type | Advanced power transducer | |
| System configuration | AV6 three-phase measurement | |
| Voltage input | 57–120 V L-N / 100–208 V L-L | |
| Current input | 1/5(6) A AC | |
| Auxiliary supply | 18–60 VAC/DC | |
| Relay outputs | 2 programmable relay outputs | |
| Energy measurement | kWh and kvarh | |
| Accuracy | ±0.5% full scale for voltage and current | |
| Energy accuracy | Class 1 kWh / Class 2 kvarh | |
| Measurement technology | TRMS | |
| Communication/configuration | Programmable via UCS software | |
| Mounting type | DIN rail mounting | |
| Dimensions | approx. 45 × 83.5 × 98.5 mm |
The CPTDINAV63LR2AX is used for measuring and monitoring electrical parameters in three-phase industrial power systems and automation applications.
The unit provides two programmable relay outputs for alarm and switching functions.
The transducer operates from an 18–60 VAC/DC auxiliary supply.
The device is designed for DIN-rail mounting inside industrial electrical panels and automation cabinets.
The transducer can measure voltage, current, active power, reactive power, apparent power, frequency, power factor and energy consumption.
Carlo Gavazzi CPT-DIN advanced power transducers are widely used by engineers and system integrators to deliver accurate electrical measurement, reliable alarm monitoring and efficient energy management in industrial automation systems.