Carlo Gavazzi CPTDINAV51HV3AX DIN rail energy transducer for three-phase electrical monitoring, with 230 to 347 V L-N, 400 to 600 V L-L, 5(6) A CT input and 3 x 0-10 V DC analogue outputs.
The Carlo Gavazzi CPTDINAV51HV3AX is a compact and advanced DIN rail energy transducer designed for accurate monitoring of three-phase electrical systems. As part of the Carlo Gavazzi CPTDIN Advanced range, it measures key electrical parameters and provides 3 analogue 0–10 V DC outputs for connection to PLCs, controllers and monitoring systems.
This transducer is ideal for industrial control panels, distribution boards and energy management applications where reliable electrical measurement is required without a local display. It supports standard 5 A current transformer inputs and is suitable for low voltage installations requiring continuous measurement of power, energy and operating conditions.
With voltage measurement ranges from 230 to 347 V L-N and 400 to 600 V L-L, support for 50/60 Hz operation and a wide 90 to 260 V AC/DC auxiliary supply, the CPTDINAV51HV3AX provides a practical multi-output analogue solution for industrial power monitoring applications.
Energy transducers such as the Carlo Gavazzi CPTDINAV51HV3AX convert measured electrical parameters into standard analogue signals that can be used by automation and energy monitoring systems. This allows engineers to monitor load, demand, energy usage and operating conditions through PLCs, controllers or data acquisition equipment.
The CPTDINAV51HV3AX is designed for DIN rail installation and can be integrated into low voltage electrical panels for machine monitoring, distribution board measurement and energy management. Its CT-based current input and 3 x 0–10 V DC analogue outputs make it suitable for industrial systems requiring multiple simultaneous output signals.
Tick the specs you need, then view products that match.
| Measurement Connection Type | CT connection | |
|---|---|---|
| MID Approval | No | |
| Device Type | Power transducer | |
| Current Input Rating (A) | 5 A (CT) | |
| Manufacturer | Carlo Gavazzi | |
| Series | CPTDIN Advanced | |
| Model | CPTDINAV51HV3AX | |
| Product type | Energy transducer / power transducer | |
| Mounting type | DIN rail mounting | |
| Rated voltage range | 230 to 347 V L-N / 400 to 600 V L-L | |
| Voltage inputs | Three-phase network configurations | |
| Current input | 5(6) A via current transformers | |
| Frequency | 50 / 60 Hz | |
| Analogue outputs | 3 x 0–10 V DC | |
| Energy metering | Consumption and generation | |
| Measured variables | V, A, Hz, W, VA, var, PF, kWh, kvarh and operating hours | |
| Auxiliary supply | 90 to 260 V AC/DC | |
| Display | None | |
| Protection rating | IP20 | |
| Approvals | CE / cURus / CSA |
The CPTDINAV51HV3AX is used to measure electrical variables in three-phase systems and provide 3 x 0–10 V DC analogue outputs for remote monitoring and control.
The transducer provides 3 analogue outputs rated at 0–10 V DC for connection to compatible PLCs, controllers and monitoring equipment.
It is designed for use with standard 5(6) A current transformers.
No. This model is supplied without a local display and is intended for remote monitoring through its analogue outputs.
Yes. The CPTDINAV51HV3AX supports energy metering for both consumption and generation.
Carlo Gavazzi energy transducers are widely used by automation engineers, panel builders and energy management specialists for reliable electrical monitoring, compact DIN rail installation and dependable analogue signal output.