Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato DMK10R1 three-phase True RMS digital voltmeter with phase-to-neutral and phase-to-phase voltage monitoring, minimum and maximum value memory and a programmable relay output.
£152.68
The Lovato DMK10R1 is a compact and accurate three-phase digital voltmeter designed for continuous voltage monitoring, control and protection in industrial switchboards, machinery panels and electrical distribution systems. It displays individual phase-to-neutral and phase-to-phase voltage values, allowing engineers to assess the condition of a three-phase supply from a single panel-mounted instrument.
The meter uses True RMS measurement to provide reliable readings, including where electrical waveforms are affected by variable speed drives, switched-mode power supplies or other non-linear loads. It measures phase-to-phase voltages from 15 to 660 V AC and phase-to-neutral voltages from 10 to 382 V AC, making it suitable for a broad range of low-voltage installations.
The DMK10R1 also records the minimum and maximum voltage measured on each phase and between phases. An integrated programmable relay output can operate an external alarm, contactor or control circuit when configured voltage conditions occur. Its compact 96 × 48 mm flush-mounted format makes it ideal for professional panel-building and system-monitoring applications.
Three-phase voltage monitoring helps engineers identify supply imbalance, phase loss, overvoltage and undervoltage conditions before they cause equipment failure or production disruption. By displaying both phase-to-neutral and phase-to-phase measurements, the Lovato DMK10R1 provides a detailed overview of the electrical supply from one compact instrument.
The programmable relay output extends the meter beyond basic indication. It can activate an external warning device, switch a contactor or interface with a control system when measured voltage reaches configured limits, making the DMK10R1 suitable for automated voltage supervision and protective control applications.
Tick the specs you need, then view products that match.
| Measurement Functions | Voltage | |
|---|---|---|
| Phase | Three Phase | |
| Signal / Input Range | Frequency | |
| Coil / Supply Voltage | 220–240 V AC | |
| Device Type | Ammeter / voltmeter | |
| Manufacturer | Lovato Electric | |
| Series | DMK | |
| Model | DMK10R1 | |
| Product type | Three-phase digital voltmeter | |
| Measurement | AC phase and phase-to-phase voltage | |
| Displayed phase voltages | 3 | |
| Displayed phase-to-phase voltages | 3 | |
| Stored values | Minimum and maximum phase and phase-to-phase voltages | |
| Measurement method | True RMS | |
| Rated phase-to-phase voltage | 600 V AC | |
| Rated phase-to-neutral voltage | 347 V AC | |
| Phase-to-phase operating range | 15 to 660 V AC | |
| Phase-to-neutral operating range | 10 to 382 V AC | |
| Voltage accuracy | ±0.25% full scale ±1 digit | |
| Voltage input frequency | 45 to 66 Hz | |
| Auxiliary supply voltage | 220 to 240 V AC | |
| Auxiliary supply frequency | 50 / 60 Hz | |
| Maximum power consumption | 3.6 VA | |
| Maximum power dissipation | 1.8 W | |
| Relay output | 1 programmable relay | |
| Relay function | Control, alarm and protection | |
| Installation type | Flush mounting | |
| Front dimensions | 96 × 48 mm | |
| Housing material | Thermoplastic | |
| Terminal type | Removable | |
| Conductor cross-section | 0.2 to 2.5 mm² | |
| Maximum terminal tightening torque | 0.8 N·m | |
| Rated insulation voltage | 600 V | |
| Weight | approximately 328 g | |
| Package dimensions | 123 × 58 × 98 mm | |
| EAN | 8013975154762 | |
| Conformity | IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL508 and CSA C22.2 No. 14 | |
| HS Code | 90303100 |
The DMK10R1 measures and displays three phase-to-neutral voltages and three phase-to-phase voltages in a three-phase AC system.
The meter measures phase-to-phase voltages from approximately 15 to 660 V AC and phase-to-neutral voltages from 10 to 382 V AC.
Yes. It records minimum and maximum values for all three phase-to-neutral and all three phase-to-phase voltage measurements.
The relay can operate an external alarm, contactor or control circuit when the measured voltage reaches programmed control or protection thresholds.
Yes. It uses True RMS measurement to provide reliable voltage readings, including where the monitored waveform is distorted.
The DMK10R1 is designed for flush mounting in an electrical panel and has a compact 96 × 48 mm front format.
Lovato Electric digital metering instruments are used by panel builders, automation engineers and maintenance teams to provide dependable three-phase voltage monitoring, alarm signalling and electrical system protection.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.