Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 6M.TA.9.024.1200 is a 50 A single-phase AC/DC power analyser with True RMS measurement, voltage monitoring up to 800 V AC or 1000 V DC, 0.5% full-scale accuracy, bidirectional energy measurement and Modbus RS485 RTU communication for industrial energy monitoring applications.
£79.59
The Finder 6M.TA.9.024.1200 is a compact single-phase AC/DC power analyser designed for accurate electrical measurement, energy monitoring and industrial automation applications. Part of the Finder 6M Series, this multifunctional monitoring device combines current sensing, voltage measurement, power analysis and energy monitoring in one unit.
Featuring True RMS (TRMS) AC measurement and DC measurement capability, the Finder 6M.TA.9.024.1200 supports nominal currents up to 50 A, with voltage measurement capabilities extending to 800 V AC and 1,000 V DC. Its integrated current sensing arrangement eliminates the need for a separate external current transformer in suitable installations, simplifying wiring and reducing the space required for monitoring equipment.
An integrated Modbus RS485 RTU communication interface allows measurement data to be accessed by compatible PLCs, energy management systems and supervisory monitoring software. With 0.5% full-scale accuracy, bidirectional active energy measurement and a DIN rail mounting adaptor included, this power analyser provides a practical solution for monitoring electrical consumption, power quality and energy flow in commercial and industrial installations.
The Finder 6M.TA.9.024.1200 is designed to provide detailed information about electrical performance in single-phase AC and DC installations. Its integrated sensing system measures current flowing through the monitored conductor, while dedicated voltage connections allow the device to calculate electrical power and energy parameters.
For AC circuits, True RMS measurement provides meaningful readings even when current waveforms are distorted by electronic loads. The analyser measures RMS voltage and current, active power, apparent power, reactive power, frequency, power factor, peak values and current total harmonic distortion. These measurements can help engineers assess equipment operation, identify abnormal electrical conditions and monitor energy consumption.
The analyser also supports bidirectional active energy measurement, making it useful for applications where electrical energy can flow in either direction, including photovoltaic installations, battery energy systems and compatible power conversion equipment. The direction and interpretation of measured energy depend on the installation wiring and system configuration.
Through its Modbus RS485 RTU interface, the device can transmit measurement values to compatible industrial controllers, SCADA systems and energy monitoring software. It can also be integrated into Ethernet-based systems through a suitable Modbus RTU-to-TCP/IP gateway, such as the Finder 6M.BU.0.024.2200.
| Manufacturer | Finder |
|---|---|
| Series | 6M Series Power Analysers |
| Model | 6M.TA.9.024.1200 |
| Product type | Single-phase AC/DC power analyser |
| Measurement system | Single-phase AC and DC |
| AC measurement method | True RMS (TRMS) |
| Nominal AC current | 50 A |
| Nominal DC current | 50 A |
| Minimum measured current | 0.5 A |
| Maximum measurable peak current | 90 A |
| AC voltage measurement range | 90–800 V AC |
| DC voltage measurement range | 90–1,000 V DC |
| Current accuracy | 0.5% of full scale |
| Voltage accuracy | 0.5% of full scale |
| Measurement frequency | DC or 1–400 Hz AC |
| Voltage measurement | RMS and peak values |
| Current measurement | RMS and peak values |
| Active power measurement | kW |
| Apparent power measurement | kVA |
| Reactive power measurement | kvar |
| Power factor measurement | PF and cosφ |
| Frequency measurement | Hz |
| Harmonic distortion measurement | Current THD |
| Energy measurement | Bidirectional active energy in kWh |
| Communication interface | Modbus RS485 RTU |
| RS485 communication speed | 1,200–115,200 bit/s |
| Default Modbus address | 1 |
| Default serial communication speed | 9,600 bit/s |
| Default serial data format | 8 data bits, no parity, 1 stop bit |
| Register representation options | MSW first, LSW first or hundredths |
| Nominal supply voltage | 24 V DC |
| Supply voltage range | 9–30 V DC |
| Power supply type | External DC supply |
| Operating temperature range | −15 to +65 °C |
| Protection rating | IP20 |
| Mounting type | 35 mm DIN rail using supplied adaptor |
| Electrical connections | Screw terminals |
| Current sensing arrangement | Integrated single-conductor pass-through sensor |
| Applicable safety standard | EN 61010-1 |
| EAN | 8012823445717 |
The Finder 6M.TA.9.024.1200 is a single-phase AC/DC power analyser used to measure electrical current, voltage, power, energy consumption and related electrical parameters in industrial automation, energy management and electrical distribution applications.
Yes. The analyser supports True RMS AC measurement and DC electrical measurement. It is suitable for compatible single-phase AC installations and DC electrical circuits within its specified measurement ranges.
The analyser has a 50 A nominal current measurement rating for both AC and DC applications, a minimum measured current of 0.5 A and a specified maximum measurable peak current of 90 A.
The Finder 6M.TA.9.024.1200 supports voltage measurement from 90–800 V AC and 90–1,000 V DC. The instrument must be installed according to its specified electrical and safety requirements.
The analyser provides 0.5% full-scale accuracy for current and voltage measurement. This specification refers to measurement accuracy relative to the instrument's full-scale range.
Yes. The analyser includes an integrated Modbus RS485 RTU interface with configurable communication speeds from 1,200 to 115,200 bit/s, allowing compatible monitoring systems and industrial controllers to access measurement data.
The analyser requires an external DC power supply with a nominal voltage of 24 V DC and a specified operating range of 9–30 V DC.
Yes. The Finder 6M.TA.9.024.1200 supports bidirectional active energy measurement in kWh, making it suitable for monitoring energy import and export in appropriately configured electrical installations.
The analyser measures RMS voltage, RMS current, active power, apparent power, reactive power, power factor, frequency, current total harmonic distortion, peak voltage, peak current, cosine phi and bidirectional active energy.
The Finder 6M.TA.9.024.1200 incorporates a single-conductor pass-through current sensor, so a separate external current transformer is not required for suitable installations within the device's measurement range.
Yes. The analyser supports 35 mm DIN rail mounting using the adaptor supplied with the device, allowing integration into electrical distribution boards and industrial control cabinets.
Yes. Its Modbus RS485 RTU interface can be connected to an Ethernet-based Modbus TCP/IP monitoring system through a compatible communication gateway, such as the Finder 6M.BU.0.024.2200.
The Finder 6M.TA.9.024.1200 combines AC/DC current sensing, power analysis, bidirectional energy measurement and Modbus communication in a compact single-phase monitoring device. Its integrated sensing arrangement, 0.5% full-scale accuracy and DIN rail installation capability make it a practical solution for electrical engineers, system integrators, energy management specialists and industrial automation professionals.
We use cookies