Finder 7E.86.8.400.0112 is a MID Class B three-phase bi-directional energy meter featuring 1 A reference and 6 A maximum CT inputs, programmable 1 A or 5 A transformer secondary settings, dual-tariff measurement, infrared communication, two programmable S0 pulse outputs and a backlit LCD display for industrial and commercial energy monitoring.
£193.55
The Finder 7E.86.8.400.0112 is a professional three-phase, multifunction, bi-directional energy meter designed for accurate electricity consumption monitoring in industrial, commercial and building automation installations. Part of the Finder 7E Series, this MID-certified digital electricity meter combines current transformer-operated measurement, dual-tariff energy recording, an integrated infrared communication interface and two programmable S0 pulse outputs in a compact DIN rail-mounted housing.
Designed for three-phase three-wire and four-wire electrical systems, the Finder 7E.86.8.400.0112 operates with a nominal voltage of 3 × 230/400 V AC at 50/60 Hz. Its current measurement system has a 1 A reference current and 6 A maximum input, with a programmable current transformer secondary setting of 1 A or 5 A. This allows the meter to monitor high-current installations through correctly selected external current transformers rather than carrying the main load current directly through the meter.
The meter supports bi-directional active and reactive energy measurement, enabling users to monitor both imported and exported electrical energy. Its dual-tariff functionality provides separate energy registers for two tariff periods, while the backlit LCD display offers local access to consumption totals and important electrical parameters. With MID Class B active energy accuracy, two programmable S0 outputs and an infrared communication interface for compatible external modules, the Finder 7E.86.8.400.0112 is a versatile solution for electrical engineers, energy managers and industrial control panel builders.
The Finder 7E.86.8.400.0112 provides detailed electricity consumption information for three-phase electrical systems. Unlike a basic kilowatt-hour meter, this multifunction device offers a wider range of electrical measurements, helping engineers, facilities managers and energy specialists understand how electrical power is being consumed and distributed.
The meter's bi-directional measurement capability is particularly useful in installations where electrical energy can flow in both directions. It records imported and exported energy separately, making it suitable for monitoring facilities with on-site generation, including correctly configured photovoltaic installations.
Its external current transformer arrangement is designed for industrial and commercial installations where the primary electrical current may be significantly higher than the meter's own current input rating. The meter accepts a reference current of 1 A, with a maximum measuring input of 6 A, and can be configured for CT secondary currents of 1 A or 5 A.
By using an appropriately rated current transformer, the Finder 7E.86.8.400.0112 can monitor high-current circuits without requiring the main electrical load current to pass directly through the meter. Finder specifies current transformer ratios from 1:1 to 10,000:1, with suitable CT configurations supporting primary current measurement up to 50,000 A.
Correct CT selection and configuration are essential. The selected CT ratio, secondary current, polarity and phase association must match the installation. Incorrect CT settings or reversed current transformer connections can result in inaccurate readings or incorrect import and export indications. CT secondary circuits must also be handled using appropriate safety procedures, including avoiding an open-circuit secondary while the primary conductor is energised.
The dual-tariff functionality allows electricity consumption to be recorded separately across two tariff periods. This is particularly useful where electricity charges differ according to the time of day, operating schedule or supply agreement. The tariff switching arrangement must be configured and connected according to the manufacturer's instructions.
The meter provides readings for active energy, reactive energy and apparent energy, together with total and partial energy counters. Partial counters can be reset, allowing consumption to be monitored across selected operating periods, production runs or maintenance intervals without affecting the main energy measurement registers.
Its backlit LCD display offers local access to instantaneous electrical measurements, including voltage, current, active power, reactive power, apparent power, frequency and power factor. These readings can support load analysis, commissioning checks and investigations into electrical consumption.
The meter also indicates phase failure and incorrect phase sequence. These functions can assist with identifying wiring problems or abnormal electrical conditions during commissioning and maintenance. They should be used as diagnostic information rather than as substitutes for dedicated electrical protection equipment.
A distinguishing feature of the Finder 7E.86.8.400.0112 is its integrated infrared communication interface. This interface enables the transfer of metering information using compatible external communication modules, providing a flexible route towards remote energy monitoring and data collection.
The meter itself is an infrared communication version. It does not have the same integrated communication interface as the Modbus RS485 or M-Bus variants in the Finder 7E.86 range. Where a particular communication protocol is required, the selected meter and any external module must be checked for compatibility with the intended energy management system.
In addition to infrared communication, the meter includes two programmable S0 pulse outputs compliant with EN 62053-31. These can be connected to compatible pulse counting devices, monitoring controllers or data acquisition equipment to support energy consumption tracking.
The pulse outputs can be configured for supported energy quantities, including kWh, kvarh and kVAh. The correct pulse constant and output configuration should be selected to match the receiving equipment and the current transformer ratio.
The Finder 7E.86.8.400.0112 is MID certified and provides Class B active energy accuracy according to EN 50470-3. Its reactive energy measurement is specified as Class 2 according to EN 62053-23. These characteristics make it suitable for professional energy measurement applications where dependable metering performance is required.
For electricity billing, tenant sub-metering or other legally controlled applications, the relevant national regulations and installation requirements must be checked. MID certification is an important product characteristic, but the suitability of a complete metering arrangement also depends on the selected current transformers, wiring configuration, commissioning and applicable legal requirements.
The meter is designed for installation on a standard 35 mm DIN rail according to EN 60715. This makes it suitable for integration into industrial electrical cabinets, distribution boards and commercial building energy monitoring panels.
A sealable terminal cover accessory is available to help protect the electrical connections against unauthorised access. The installation should provide appropriate electrical protection, isolation, conductor sizing and enclosure protection according to the manufacturer's documentation and applicable wiring regulations.
Tick the specs you need, then view products that match.
| Mounting Type | DIN rail | |
|---|---|---|
| Monitoring Function | Three-phase supply | |
| Monitored Supply | Three-phase | |
| Manufacturer | Finder | |
| Series | 7E Series | |
| Model | 7E.86.8.400.0112 | |
| Product type | Multifunction three-phase energy meter | |
| Meter construction | Electronic, current transformer-operated | |
| Measurement direction | Bi-directional, import and export | |
| Number of phases | Three-phase | |
| Supported wiring systems | Three-phase three-wire and three-phase four-wire | |
| Supported CT wiring arrangements | Three-phase four-wire with three CTs; three-phase three-wire with two or three CTs, as specified in the manufacturer's wiring diagrams | |
| Nominal voltage | 3 × 230/400 V AC | |
| Rated frequency | 50/60 Hz | |
| Reference current | 1 A | |
| Maximum measuring current | 6 A | |
| Current measurement method | External current transformers | |
| Programmable CT secondary current | 1 A or 5 A | |
| Minimum current transformer ratio | 1:1 | |
| Maximum current transformer ratio | 10,000:1 | |
| Maximum measurable primary current | Dependent on CT selection and ratio configuration; Finder specifies applications up to 50,000 A using suitable CTs | |
| Active energy accuracy | Class B according to EN 50470-3 | |
| Reactive energy accuracy | Class 2 according to EN 62053-23 | |
| MID certification | Yes | |
| Tariff functionality | Two tariffs | |
| Energy measurement | Active, reactive and apparent energy | |
| Energy flow measurement | Imported and exported energy | |
| Energy registers | Total and partial counters | |
| Partial counter reset | Supported | |
| Communication interface | Infrared communication port | |
| External communication modules | Compatible modules may be used for remote data transmission | |
| Pulse outputs | 2 × S0 | |
| Pulse output configuration | Programmable | |
| Pulse output standard | EN 62053-31 | |
| Display type | Backlit LCD | |
| Display resolution | Eight-digit energy display | |
| Instantaneous measurements | Voltage, current, active power, reactive power, apparent power, frequency and power factor | |
| Additional indications | Energy flow direction, phase failure and phase sequence error | |
| Electrical protection class | Class II | |
| Mounting type | DIN rail | |
| DIN rail standard | EN 60715, 35 mm | |
| Terminal security | Sealable terminal cover accessory | |
| Installation | Electrical distribution board or appropriately rated control enclosure |
The Finder 7E.86.8.400.0112 is a multifunction three-phase energy meter used for monitoring electricity consumption, imported and exported energy, power and other electrical parameters in industrial and commercial installations. It includes dual-tariff measurement, infrared communication and two programmable S0 pulse outputs.
Yes. The Finder 7E.86.8.400.0112 is MID certified and provides Class B active energy accuracy according to EN 50470-3. Suitability for legally controlled metering depends on the applicable regulations and installation requirements.
Yes. The meter is designed for external current transformer operation. It has a 1 A reference current and 6 A maximum measuring input, with a programmable CT secondary current setting of 1 A or 5 A.
The meter has a 6 A maximum current input and supports programmable current transformer ratios up to 10,000:1. Finder specifies applications up to 50,000 A using suitable current transformers and the correct ratio configuration.
The Finder 7E.86.8.400.0112 has an integrated infrared communication interface. Compatible external communication modules can be used to transfer meter data to suitable monitoring and data acquisition systems.
No. The 7E.86.8.400.0112 is the infrared communication version. For applications requiring an integrated Modbus RS485 interface, the Finder 7E.86.8.400.0212 variant should be considered.
Yes. The meter supports bi-directional energy measurement, allowing imported and exported energy to be recorded separately. This makes it suitable for monitoring appropriately configured electrical installations with on-site generation, including photovoltaic systems.
Yes. The Finder 7E.86.8.400.0112 is a dual-tariff energy meter, allowing energy consumption to be recorded separately across two tariff periods using the appropriate tariff switching arrangement.
The meter provides two programmable S0 pulse outputs compliant with EN 62053-31. These can be used with compatible pulse counters, data acquisition equipment and energy monitoring systems.
The meter measures active, reactive and apparent energy, together with instantaneous voltage, current, active power, reactive power, apparent power, frequency and power factor. It also indicates energy flow direction, phase failure and incorrect phase sequence.
Yes. The meter supports three-phase three-wire and three-phase four-wire electrical systems. It can be configured for the supported current transformer arrangements shown in the manufacturer's installation diagrams.
Both models provide three-phase current transformer-operated energy measurement, dual-tariff recording and MID certification. The main difference is communication: the 7E.86.8.400.0112 uses an infrared interface with two S0 outputs, while the 7E.86.8.400.0212 has integrated Modbus RS485 communication.
Both models provide dual-tariff, bi-directional three-phase energy measurement using external current transformers. The key difference is communication: the 7E.86.8.400.0112 uses an infrared interface, while the 7E.86.8.400.0312 uses an integrated M-Bus interface.
The meter is designed for 35 mm DIN rail mounting according to EN 60715. It should be installed inside an appropriately rated electrical distribution board or control enclosure by a suitably qualified electrical professional.
Finder 7E Series energy meters provide dependable electricity measurement solutions for industrial facilities, commercial buildings and electrical distribution systems. With MID Class B certification, current transformer operation, bi-directional measurement, dual-tariff recording, an integrated infrared communication interface, two programmable S0 pulse outputs and DIN rail mounting, the Finder 7E.86.8.400.0112 offers a practical solution for electrical engineers, energy managers, facilities professionals and industrial control panel manufacturers.
We use cookies