Finder 7E.85.8.400.0312 is a MID Class C multifunction three-phase bi-directional energy meter featuring 1 A reference and 6 A maximum CT inputs, programmable current transformer ratios up to 10000 A, dual-tariff measurement, M-Bus communication, two S0 pulse outputs and a backlit LCD display for industrial and commercial energy monitoring.
£196.77
The Finder 7E.85.8.400.0312 is an advanced three-phase multifunction, bi-directional energy meter designed for accurate electricity monitoring, industrial energy management and building automation. Part of the Finder 7E Series, this MID-certified digital electricity meter combines high-precision energy measurement, dual-tariff recording, an integrated M-Bus communication interface and two S0 pulse outputs in a compact DIN rail-mounted enclosure.
Designed for use with external current transformers (CTs), the Finder 7E.85.8.400.0312 supports a 1 A reference current and 6 A maximum measuring input, allowing the monitoring of substantially higher installation currents through appropriately selected and configured CTs. Its programmable transformer ratio supports installations with primary currents up to 10,000 A, making it suitable for industrial distribution boards, commercial electrical installations and energy-intensive manufacturing facilities.
The meter supports three-phase three-wire and three-phase four-wire electrical systems, with a nominal supply of 3 × 230/400 V AC. Its illuminated LCD display provides access to active and reactive energy, voltage, current, power, power factor, frequency and harmonic distortion information. With accuracy class 0.5S / MID Class C, import and export energy recording, M-Bus remote communication and two-tariff operation, this Finder energy meter offers a comprehensive solution for professional electricity monitoring and consumption analysis.
The Finder 7E.85.8.400.0312 is designed to provide detailed electrical consumption information in industrial and commercial installations. Unlike a basic kilowatt-hour counter, this multifunction energy meter measures a broad range of electrical parameters, allowing engineers and energy managers to understand how electricity is being consumed, distributed and returned to the supply network.
Its bi-directional measurement capability allows the meter to record both imported and exported electrical energy. This is especially valuable in installations incorporating on-site electricity generation, such as photovoltaic systems, where electrical energy may flow in either direction. Separate import and export measurements support more detailed energy analysis and reporting.
The meter operates with external current transformers, rather than carrying the main installation current directly through its measuring terminals. With a 1 A reference current and 6 A maximum current input, the device can monitor high-current installations when used with correctly selected and configured CTs. The programmable transformer ratio supports primary currents up to 10,000 A.
The dual-tariff function enables energy consumption to be recorded across two tariff periods. This is useful for installations where electricity is charged at different rates according to operating schedules, time periods or energy supply arrangements. The tariff configuration should be matched to the actual metering and control requirements of the installation.
A key feature of the 7E.85.8.400.0312 variant is its integrated M-Bus communication interface. M-Bus is widely used for remote meter reading in commercial buildings, industrial facilities and energy management systems. The interface supports the EN 13757-3 protocol, allowing compatible systems to collect electrical measurement data without relying solely on manual display readings.
The meter also includes two S0 pulse outputs. These provide additional integration options for external pulse counters, building management systems and monitoring equipment. One output is programmable, offering flexibility when configuring the energy monitoring system.
Its backlit LCD display provides local access to key electrical measurements. The available information includes phase and line voltages, phase currents, active power, reactive power, apparent power, power factor and frequency. Energy totals can be used to analyse electrical consumption over time, while the additional measurement functions support investigation of electrical load conditions.
The Finder 7E.85 also provides total harmonic distortion measurements for current and voltage. These measurements can help identify waveform distortion associated with non-linear loads such as variable speed drives, electronic power supplies and industrial power conversion equipment. Maximum demand monitoring provides further information for assessing electrical load peaks.
With MID Class C certification and Class 0.5S active energy accuracy, the meter is designed for applications requiring dependable electrical energy measurement. The relevant national regulations, installation conditions and certification requirements must be checked before using the meter for billing or other legally controlled metering applications.
The four-module DIN rail housing allows the meter to be installed within electrical distribution boards and industrial control panels. Its compact dimensions, sealable terminal covers and IP51 protection rating make it suitable for properly designed indoor electrical installations. The specified operating temperature range of −40 to +70 °C supports use in demanding environments.
For correct operation, the installer must configure the appropriate three-phase wiring system, current transformer ratio, tariff settings and M-Bus communication parameters. CT polarity, phase sequence and voltage connections are particularly important for accurate import and export measurement. Installation and commissioning should be carried out by a suitably qualified electrical professional in accordance with Finder's instructions and applicable electrical regulations.
Tick the specs you need, then view products that match.
| Mounting Type | DIN rail | |
|---|---|---|
| Monitored Supply | Three-phase | |
| Monitoring Function | Three-phase supply | |
| Manufacturer | Finder | |
| Series | 7E Series | |
| Model | 7E.85.8.400.0312 | |
| Product type | Multifunction three-phase energy meter | |
| Meter type | Electronic, current transformer-operated | |
| Measurement direction | Bi-directional, import and export | |
| Number of phases | Three-phase | |
| Supported electrical systems | Three-phase three-wire and three-phase four-wire | |
| Nominal voltage | 3 × 230/400 V AC | |
| Line-to-neutral operating voltage | 100–277 V AC | |
| Line-to-line operating voltage | 100–480 V AC | |
| Rated frequency | 50/60 Hz | |
| Reference current | 1 A | |
| Maximum measuring current | 6 A | |
| Minimum measured current | 0.05 A | |
| Starting current | 0.005 A | |
| Measuring current range | 0.05–6 A | |
| Maximum short-duration peak current | 120 A for 500 ms | |
| Current transformer compatibility | External CT connection | |
| CT ratio configuration | Programmable | |
| Maximum supported CT primary current | 10,000 A | |
| Active energy accuracy | Class 0.5S according to IEC 62053-22 | |
| MID accuracy classification | Class C | |
| Reactive energy accuracy | Class 2 according to IEC 62053-23 | |
| MID certification | Yes | |
| MID operating temperature certification | Up to +70 °C | |
| Tariff functionality | Dual tariff | |
| Communication interface | M-Bus | |
| Communication protocol | EN 13757-3 | |
| M-Bus baud rates | 600, 1200, 2400, 4800 and 9600 baud | |
| M-Bus primary address range | 001–250 | |
| M-Bus secondary addressing | Supported | |
| Pulse outputs | 2 × S0 | |
| Programmable pulse output | Yes | |
| Display type | Backlit LCD | |
| Energy counter display | Eight digits | |
| Maximum displayed energy count | 999,999.99 kWh | |
| Minimum energy display increment | 0.01 kWh | |
| Measured energy | Imported, exported and total active energy; imported, exported and total reactive energy | |
| Measured electrical parameters | Voltage, current, active power, reactive power, apparent power, power factor and frequency | |
| Additional measurements | Current and voltage total harmonic distortion, maximum demand | |
| Front-panel controls | Four buttons | |
| Mounting type | DIN rail | |
| DIN rail standard | EN 60715, 35 mm | |
| Housing width | 71.9 mm | |
| Housing height | 99.4 mm | |
| Housing depth | Approximately 59.6 mm, excluding installation-dependent clearances | |
| DIN module width | 4 modules | |
| Protection rating | IP51 | |
| Operating ambient temperature | −40 to +70 °C | |
| Terminal protection | Sealable terminal covers | |
| EAN | 8012823461403 |
The Finder 7E.85.8.400.0312 is a multifunction three-phase energy meter used for monitoring electricity consumption, imported and exported energy, electrical power and other parameters in industrial and commercial installations. It includes dual-tariff measurement, M-Bus communication and two S0 pulse outputs.
Yes. The Finder 7E.85.8.400.0312 is MID certified in accuracy Class C, with certification covering operation up to +70 °C. Suitability for legally controlled metering depends on the applicable regulations and installation requirements.
Yes. The meter is designed for external current transformer operation, with a 1 A reference current and 6 A maximum measuring input. Suitable CTs must be selected and their ratio correctly configured in the meter.
The meter has a 6 A maximum current input and supports external current transformers with programmable primary current values up to 10,000 A. The actual installation current must be measured through appropriately rated CTs rather than connected directly to the meter's current inputs.
The Finder 7E.85.8.400.0312 has an integrated M-Bus interface compliant with EN 13757-3. It supports remote meter reading and integration with compatible energy management and building automation systems.
No. The 7E.85.8.400.0312 uses M-Bus communication. For applications requiring Modbus RS485, the corresponding Finder 7E.85.8.400.0212 variant should be considered.
Yes. The meter supports bi-directional energy measurement, allowing imported and exported active energy to be recorded separately. This makes it suitable for monitoring electrical installations with on-site generation, including appropriately configured photovoltaic systems.
Yes. The 7E.85.8.400.0312 is a dual-tariff energy meter, allowing energy consumption to be recorded across two tariff periods according to the configured tariff control arrangement.
The meter provides two S0 pulse outputs, including a programmable output. These can be used with compatible pulse counters, data acquisition equipment and building energy management systems.
The meter measures active and reactive energy, voltage, current, active power, reactive power, apparent power, power factor, frequency, maximum demand and total harmonic distortion. It also provides separate imported and exported energy readings.
Yes. The meter supports three-phase three-wire and three-phase four-wire electrical systems. The appropriate supply configuration must be selected during commissioning and wired according to the manufacturer's installation instructions.
Both models provide M-Bus communication, current transformer operation and multifunction three-phase energy measurement. The main difference is tariff functionality: the 7E.85.8.400.0312 supports two tariffs, while the 7E.85.8.400.0310 is a single-tariff version.
Both models provide dual-tariff, bi-directional three-phase energy measurement with two S0 pulse outputs. The key difference is communication: the 7E.85.8.400.0312 uses M-Bus, while the 7E.85.8.400.0212 uses Modbus RS485.
The meter is designed for 35 mm DIN rail mounting according to EN 60715. Its housing is approximately 71.9 mm wide, occupying four standard DIN modules.
Finder 7E Series energy meters provide advanced electricity measurement and monitoring solutions for industrial facilities, commercial buildings and electrical distribution systems. With MID Class C certification, current transformer operation, bi-directional measurement, dual-tariff recording, integrated M-Bus communication, two S0 pulse outputs and a compact DIN rail design, the Finder 7E.85.8.400.0312 is a versatile choice for electrical engineers, energy managers, building automation specialists and industrial control panel manufacturers.