Lovato DMK70R1 three-phase True RMS digital voltmeter with phase-to-neutral and phase-to-phase voltage monitoring, minimum and maximum value storage, DIN rail mounting and a programmable relay output.
£152.68
The Lovato DMK70R1 is a compact three-phase digital voltmeter designed for continuous voltage monitoring, alarm signalling and protection in industrial switchboards, distribution boards and machinery control systems. It displays the voltage measured across each phase and between phases, providing operators with a clear overview of the condition of a three-phase electrical supply.
The instrument uses True RMS measurement to provide accurate and stable readings, including where voltage waveforms contain harmonics or distortion. It measures phase-to-phase voltages from 15 to 660 V AC and phase-to-neutral voltages from 10 to 382 V AC, making it suitable for a broad range of low-voltage installations.
The DMK70R1 stores minimum and maximum values for all monitored voltages and includes a programmable relay output with control and protection functions. Its compact three-module format allows straightforward installation on a standard DIN rail, making it ideal for new panel builds, system upgrades and electrical monitoring applications where panel space is limited.
Three-phase voltage monitoring helps engineers identify overvoltage, undervoltage, supply imbalance and phase-related faults before they cause damage or production downtime. By displaying both phase-to-neutral and phase-to-phase values, the Lovato DMK70R1 provides a detailed view of the electrical supply from one compact instrument.
The programmable relay output allows the meter to activate an alarm, switch a contactor or interface with an external control system when a configured voltage condition occurs. This makes the DMK70R1 suitable for automatic voltage supervision, supply protection and preventative maintenance applications.
Tick the specs you need, then view products that match.
| MID Approval | No | |
|---|---|---|
| Device Type | Energy meter | |
| Voltage | 240 V | |
| Manufacturer | Lovato Electric | |
| Series | DMK | |
| Model | DMK70R1 | |
| Product type | Three-phase digital voltmeter | |
| Measured parameters | Phase-to-neutral and phase-to-phase AC voltage | |
| Phase voltage values | 3 | |
| Phase-to-phase voltage values | 3 | |
| Stored values | Minimum and maximum voltage for each measurement | |
| Measurement method | True RMS | |
| Rated phase-to-phase voltage | 600 V AC | |
| Rated phase-to-neutral voltage | 347 V AC | |
| Phase-to-phase operating range | 15 to 660 V AC | |
| Phase-to-neutral operating range | 10 to 382 V AC | |
| Voltage input frequency | 45 to 66 Hz | |
| Phase-to-neutral voltage accuracy | ±0.25% full scale ±1 digit | |
| Phase-to-phase voltage accuracy | ±0.25% full scale ±1 digit | |
| Auxiliary supply voltage | 220 to 240 V AC | |
| Auxiliary supply frequency | 50 / 60 Hz | |
| Maximum power consumption | 3.6 VA | |
| Maximum power dissipation | 1.8 W | |
| Relay output | 1 programmable output | |
| Relay function | Control, alarm and protection | |
| Installation type | DIN rail mounting | |
| DIN rail module width | 3 modules | |
| Housing material | Polyamide | |
| Terminal type | Fixed | |
| Conductor cross-section | 0.2 to 4 mm² | |
| Maximum terminal tightening torque | 0.5 N·m | |
| Rated insulation voltage | 600 V | |
| Protection rating | IP40 | |
| Operating temperature | -20 to +60 °C | |
| Storage temperature | -30 to +80 °C | |
| Weight | approximately 268 g | |
| Package dimensions | 95 × 55 × 75 mm | |
| EAN | 8013975152225 | |
| Certification | EAC | |
| Conformity | IEC/EN 61010-1, IEC/EN 61000-6-2 and IEC/EN 61000-6-3 | |
| HS Code | 90303100 |
The DMK70R1 measures and displays three phase-to-neutral voltages and three phase-to-phase voltages in a three-phase AC system.
The meter operates from approximately 15 to 660 V AC phase-to-phase and 10 to 382 V AC phase-to-neutral.
Yes. It stores minimum and maximum values for each of the three phase-to-neutral and three phase-to-phase voltage measurements.
The relay can activate an external alarm, contactor or control circuit when a measured voltage reaches a programmed control or protection threshold.
Yes. It uses True RMS measurement to provide reliable readings, including where the monitored voltage waveform contains distortion.
The DMK70R1 is designed for mounting on a standard DIN rail and occupies three DIN modules.
Lovato Electric digital metering instruments are used by panel builders, automation engineers and maintenance professionals to provide dependable three-phase voltage monitoring, alarm signalling and electrical system protection.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.