Lovato DMED110T1 single-phase multi-measurement energy meter with direct connection up to 40 A, LCD display, programmable pulse output and compact 1-module DIN rail housing.
£75.90
The Lovato DMED110T1 is a compact single-phase digital energy meter designed for direct measurement of electrical energy and key circuit values in residential, commercial and light industrial installations. With a maximum direct current rating of 40 A, it can monitor suitable loads without requiring an external current transformer.
Unlike basic energy counters, the DMED110T1 provides multi-measurement functionality, allowing users to view imported active energy, imported reactive energy and essential electrical parameters through its clear LCD display. Its compact 1-module DIN rail enclosure occupies only 18 mm of panel width, making it ideal for distribution boards and control panels where installation space is limited.
The meter operates from a 220–240 V AC single-phase supply and includes a programmable static pulse output for integration with remote counters, data concentrators and energy-management systems. Class 1 active energy accuracy and Class 2 reactive energy accuracy provide dependable monitoring for cost analysis, load assessment and electrical efficiency projects.
The Lovato DMED110T1 monitors voltage and current directly within a single-phase electrical circuit and calculates the associated energy consumption. It records both imported active energy and imported reactive energy, giving users greater insight into circuit performance than a basic kilowatt-hour counter.
Its programmable pulse output allows measured consumption to be transmitted to a compatible data concentrator, remote counter or building-management system. This makes the DMED110T1 suitable for local sub-metering, energy-efficiency analysis, equipment monitoring and centralised consumption reporting.
Tick the specs you need, then view products that match.
| MID Approval | No | |
|---|---|---|
| Device Type | Energy meter | |
| Current Input Rating (A) | 40 A | |
| Current | 40 A | |
| Phase | Single Phase | |
| Manufacturer | Lovato Electric | |
| Series | DME | |
| Model | DMED110T1 | |
| Product type | Single-phase digital energy meter | |
| Metering type | Direct connection | |
| Measured energy | Imported active and imported reactive energy | |
| Rated voltage | 220–240 V AC phase-to-neutral | |
| Operating voltage range | 184–264 V AC | |
| Operating frequency | 50/60 Hz | |
| Maximum current | 40 A | |
| Reference current | 5 A | |
| Minimum current | 0.25 A | |
| Transition current | 0.5 A | |
| Starting current | 20 mA | |
| Active energy accuracy | Class 1 according to IEC/EN 62053-21 | |
| Reactive energy accuracy | Class 2 according to IEC/EN 62053-23 | |
| LED pulse rate | 1000 pulses/kWh | |
| LED pulse duration | 30 ms | |
| Static pulse output | Programmable, 1, 10, 100 or 1000 pulses/kWh | |
| Static output pulse duration | 100 ms | |
| Static output supply | 10–30 V DC external | |
| Static output maximum current | 50 mA | |
| Rated insulation voltage | 250 V | |
| Impulse withstand voltage | 6 kV | |
| Power consumption | Maximum 7 VA | |
| Power dissipation | Maximum 0.45 W | |
| Conductor capacity | 1.5–10 mm² | |
| Terminal tightening torque | Maximum 1.5 N·m | |
| Mounting | 35 mm DIN rail | |
| Housing width | 1 DIN rail module, approximately 18 mm | |
| Dimensions (H × W × D) | Approximately 90 × 18 × 58 mm | |
| Operating temperature | -25°C to +55°C | |
| Storage temperature | -25°C to +70°C | |
| Weight | Approximately 90 g | |
| EAN | 8013975182130 | |
| Certifications | cULus, EAC and RCM | |
| Conformity | IEC/EN 61010-1, EN 50470-1, UL 61010-1 and CSA 22.2 No. 61010-1 | |
| HS Code | 90283011 |
The Lovato DMED110T1 measures imported active and reactive electrical energy in single-phase circuits and provides local multi-measurement information through its LCD display.
The meter supports a direct electrical connection with a maximum current rating of 40 A.
No. It is a direct-connected meter, so an external current transformer is not required when the measured circuit remains within its 40 A maximum rating.
The DMED110T1 measures imported active energy and imported reactive energy, alongside useful electrical circuit values.
Yes. It includes one programmable static output that can be configured for 1, 10, 100 or 1000 pulses per kWh.
Lovato Electric energy meters are widely used by panel builders, electrical contractors and energy managers for dependable multi-measurement monitoring, straightforward installation and efficient electrical consumption analysis.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.