2CMA241685R1000 ABB D11 15-M 40 Single-Phase 40 A M-Bus Energy Meter

2CMA241685R1000 ABB D11 15-M 40 Single-Phase 40 A M-Bus Energy Meter

ABB D11 15-M 40 is a compact single-phase direct-connected 40 A DIN rail energy meter with active and reactive import/export measurement and integrated M-Bus communication for remote energy monitoring.

SKU: 2CMA241685R1000Alt SKU: D11 15-M 40MPN: 2CMA241685R1000
Price
List Price £110.34 ex VAT
Your Price (ex VAT) Save 25%
£82.76 25% OFF
You save £27.59 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £82.76
Trade pricing is personalised to your account

Manufacturer Lead Time

£82.76

Why Choose the ABB D11 15-M 40 M-Bus Energy Meter?

The ABB D11 15-M 40 is a compact single-phase direct-connected electricity meter designed for accurate energy monitoring in residential, commercial and light industrial electrical installations. As part of the ABB D11 15 DIN rail mounted meter range, it combines bidirectional energy measurement with integrated M-Bus communication in a space-saving one-module format.

This electronic energy meter measures active and reactive energy in both import and export directions, making it suitable for conventional consumption monitoring and installations with bidirectional energy flow. Its integrated M-Bus interface enables measurement data to be collected remotely by compatible building-management, energy-management and automatic meter-reading systems.

With direct connection for currents up to 40 A and operation on 220–240 V AC single-phase systems, the D11 15-M 40 requires no external current transformer for loads within its rated range. Its compact 1 DIN-module design allows straightforward installation in distribution boards and control panels where available rail space is limited.

Key Advantages

  • Compact single-phase direct-connected energy meter rated up to 40 A.
  • Integrated M-Bus communication for remote meter reading and energy monitoring.
  • Measures active and reactive energy in import and export directions.
  • Class 1 active-energy accuracy for dependable electricity measurement.
  • Class 2 reactive-energy accuracy for reactive consumption monitoring.
  • Direct connection eliminates the need for external current transformers within the rated current range.
  • Space-saving construction occupies only one DIN module.

Key Features

  • ABB D11 15 energy meter series.
  • Single-phase direct-connected metering.
  • 0.25–5(40) A current range.
  • 40 A maximum current.
  • 220–240 V AC operating voltage.
  • Integrated M-Bus communication interface.
  • Measurement of active and reactive energy.
  • Measures both imported and exported energy.
  • Class 1 active-energy and Class 2 reactive-energy accuracy.
  • Digital display for local meter reading.
  • Designed for standard 35 mm DIN rail mounting.
  • Compact 1 DIN-module construction.

Compact M-Bus Energy Monitoring

Direct-connected meters such as the ABB D11 15-M 40 measure electrical current without requiring external current transformers for loads within their rated range. This simplifies installation and wiring while enabling accurate monitoring of active and reactive energy in compact single-phase distribution systems.

Integrated M-Bus communication makes the D11 15-M 40 particularly suitable for networked metering installations. Energy information can be collected by compatible M-Bus masters, gateways and energy-management platforms, allowing multiple meters to form part of a centralised building or utility monitoring system.

Typical Applications

  • Single-phase residential energy monitoring.
  • Commercial building sub-metering.
  • Apartment and multi-occupancy metering systems.
  • Light industrial electrical distribution systems.
  • Electrical control panels and distribution boards.
  • Building-management and energy-management systems.
  • Bidirectional import and export energy monitoring.
  • Remote meter reading through M-Bus networks.

Technical Specifications

Tick the specs you need, then view products that match.

Measurement Connection Type CT connection
Current Input Rating (A) 40 A
Device Type Energy meter
Series D11 15
ABB order code 2CMA241685R1000
Product type Single-phase electronic energy meter
Connection type Direct connected
Number of phases 1
Current range 0.25–5(40) A
Maximum current 40 A
Operating voltage 220–240 V AC
Frequency 50 / 60 Hz
Active energy accuracy Class 1
Reactive energy accuracy Class 2
Energy measurement Active and reactive, import and export
Communication M-Bus
Display Digital
Protection rating IP20
Mounting type DIN rail
DIN rail 35 mm
Mounting width 1 DIN module
Width approx. 17.5 mm
Height approx. 92 mm
Depth approx. 65 mm
Weight approx. 0.07 kg

Frequently Asked Questions

What is the ABB D11 15-M 40 used for?

The ABB D11 15-M 40 is used for single-phase electricity monitoring, measuring active and reactive energy in both import and export directions for directly connected loads up to 40 A.

Does the ABB D11 15-M 40 require a current transformer?

No. The meter is direct connected up to 40 A, so external current transformers are not required for installations operating within its rated current range.

What communication interface does the D11 15-M 40 use?

The D11 15-M 40 includes an integrated M-Bus communication interface for connection to compatible remote meter-reading and energy-management systems.

Can the D11 15-M 40 measure imported and exported energy?

Yes. The meter supports measurement of active and reactive energy in both import and export directions, making it suitable for bidirectional energy-monitoring applications.

How much DIN rail space does the ABB D11 15-M 40 require?

The meter occupies only one DIN module, approximately 17.5 mm wide, making it particularly suitable for distribution boards where installation space is limited.

Trusted ABB Energy Metering Technology

ABB D11 15 energy meters combine compact DIN rail installation with accurate bidirectional energy measurement and flexible communications, providing an efficient solution for single-phase residential, commercial and light industrial energy-monitoring applications.