Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB A44 111-100 is a three-phase CT/VT-connected DIN-rail active energy meter with 1 A nominal and 6 A maximum measurement current, Class B accuracy, a 3 x 57.7/100–288/500 V AC system voltage range and electrical pulse output.
£223.38
The ABB A44 111-100 is a professional three-phase CT/VT-connected electricity meter designed for indirect active energy measurement in industrial, commercial and building-services installations. Part of the ABB A44 EQ meter series, this Steel-function meter combines transformer-connected measurement with electrical instrumentation, alarm functionality and a pulse output in a compact DIN-rail format.
The A44 111-100 uses 1 A or 5 A current-transformer secondary circuits, with a nominal measurement current of 1 A and maximum input current of 6 A. It supports 3-wire and 4-wire three-phase systems and operates across a broad 3 × 57.7/100–288/500 V AC system voltage range, making it suitable for a wide variety of transformer-connected distribution networks.
Active energy is measured to Class B (Class 1) accuracy, and the meter is MID verified and IEC approved. A configurable electrical pulse output allows energy information to be transferred to external monitoring equipment, while the integrated infrared port supports communication with compatible ABB serial communication adapters.
The ABB A44 111-100 is designed for electrical systems where direct connection of the primary load current to an energy meter is impractical. External current transformers reduce the primary current to a standard measurement level, allowing the A44 111-100 to monitor higher-current three-phase installations while retaining accurate Class B active energy measurement.
In addition to accumulated active energy, the A44 platform provides useful instrumentation values and alarm functionality for monitoring electrical operating conditions. The pulse output can transfer energy information to compatible external equipment, while the infrared interface allows the meter to work with suitable ABB communication adapters when additional system connectivity is required.
Tick the specs you need, then view products that match.
| Measurement Connection Type | CT connection | |
|---|---|---|
| MID Approval | Yes | |
| Device Type | Energy meter | |
| Series | A44 EQ Meters | |
| ABB order code | 2CMA170533R1000 | |
| Product type | Three-phase electricity / energy meter | |
| Functionality level | Steel | |
| Connection type | CT/VT transformer connected | |
| Number of phases | 3 | |
| Network configuration | 3-wire / 4-wire | |
| Metering configuration | 2-element / 3-element | |
| Nominal current | 1 A | |
| Maximum measurement current | 6 A | |
| CT secondary compatibility | 1 A / 5 A | |
| Phase-to-neutral rated voltage | 57.7–288 V AC | |
| Phase-to-phase rated voltage | 100–500 V AC | |
| System voltage | 3 × 57.7/100–288/500 V AC | |
| Voltage measurement range | 3 × 47–331 V AC | |
| Frequency | 50/60 Hz | |
| Measured energy | Active energy | |
| Active energy accuracy | Class B (Class 1) | |
| Tariff rating | Single tariff | |
| Output | Electrical pulse output | |
| Communication interface | Infrared port | |
| Display | Digital LCD, 7 counter positions | |
| Protection rating | IP20 | |
| Operating temperature | −40 to +70 °C | |
| Mounting type | DIN rail | |
| Module width | 7 DIN modules | |
| Dimensions (W × H × D) | 123 × 97 × 65 mm | |
| Product weight | approx. 0.35 kg | |
| Approvals | MID verified and IEC approved |
The ABB A44 111-100 is used for three-phase transformer-connected active energy measurement in commercial and industrial electrical systems where external CTs and, where applicable, VTs are used for indirect metering.
The A44 111-100 has a nominal measurement current of 1 A, a maximum measurement current of 6 A and supports installations using 1 A or 5 A current-transformer secondary circuits.
The meter provides Class B (Class 1) active energy accuracy and is designed for professional transformer-connected electricity metering.
Yes. The A44 111-100 incorporates an electrical pulse output that can provide active energy pulse information to compatible external monitoring and data-acquisition equipment.
The A44 111-100 has an infrared communication port but does not include built-in RS-485 or M-Bus serial communication. Compatible ABB communication adapters can be used with the infrared interface where additional connectivity is required.
ABB A44 energy meters provide accurate transformer-connected three-phase measurement with instrumentation, alarm and pulse-output functionality, supporting dependable energy monitoring across industrial, commercial and electrical distribution applications.