2CMA100249R1000 ABB A44 113-100 Three-Phase CT/VT-Connected Energy Meter with M-Bus

2CMA100249R1000 ABB A44 113-100 Three-Phase CT/VT-Connected Energy Meter with M-Bus

ABB A44 113-100 is a three-phase CT/VT-connected DIN-rail active energy meter with Class B accuracy, measurement current up to 6 A, configurable transformer ratios and integrated M-Bus communication.

SKU: 2CMA100249R1000Alt SKU: A44 113-100MPN: 2CMA100249R1000
Price
List Price £443.51 ex VAT
Your Price (ex VAT) Save 25%
£332.63 25% OFF
You save £110.88 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £332.63
Trade pricing is personalised to your account

Manufacturer Lead Time

£332.63

Why Choose the ABB A44 113-100 Energy Meter?

The ABB A44 113-100 is an advanced three-phase CT/VT-connected electricity meter designed for accurate active energy measurement in industrial, commercial and building-services installations. As part of the ABB A44 energy meter series, it is intended for indirect measurement of three-phase networks where external current and, where required, voltage transformers are used.

The A44 113-100 supports both 3-wire and 4-wire three-phase systems and provides configurable transformer ratios for current and voltage. It measures active energy to Class B (Class 1) accuracy and accepts measurement current up to 6 A, making it suitable for transformer-connected metering of higher-current electrical distribution systems.

Integrated M-Bus communication enables remote meter reading and connection to compatible building and energy-management systems. The meter also provides a configurable output for active-energy pulses or alarm signalling, up to 25 configurable alarm conditions, an infrared interface and a large backlit display showing energy and key electrical instrumentation values.

Key Advantages

  • Advanced three-phase CT/VT-connected energy meter for indirect measurement.
  • Suitable for 3-wire and 4-wire three-phase networks.
  • Class B (Class 1) active energy accuracy for dependable energy monitoring.
  • Measurement current up to 6 A for transformer-connected applications.
  • Wide 3 × 57.7/100–288/500 V AC measurement voltage range.
  • Integrated M-Bus communication for remote meter reading and energy-management integration.
  • Configurable transformer ratios support a wide range of CT/VT installations.
  • Configurable output provides active-energy pulse or alarm functionality.
  • Up to 25 configurable alarm conditions support detailed electrical monitoring.
  • IEC approved and MID approved and verified for professional metering applications.

Key Features

  • ABB A44 energy meter series.
  • Three-phase transformer-connected electricity meter.
  • CT/VT connection with configurable current and voltage transformer ratios.
  • Maximum measurement current: 6 A.
  • 3 × 57.7/100–288/500 V AC voltage range.
  • 50–60 Hz operating frequency.
  • Class B (Class 1) active energy accuracy.
  • Active energy measurement.
  • Instrumentation values for power, current, voltage, frequency and power factor.
  • Per-phase and total electrical measurements.
  • Integrated M-Bus communication.
  • Infrared communication interface.
  • One configurable output for active-energy pulses or alarms.
  • Up to 25 configurable alarm conditions with threshold monitoring.
  • Backlit digital display with up to seven digits.
  • Event logging functionality.
  • Compact seven-module DIN-rail construction.

Reliable Transformer-Connected Energy Monitoring

Transformer-connected energy meters such as the ABB A44 113-100 allow higher-current three-phase electrical systems to be monitored without routing the full load current through the meter. External current transformers provide a reduced measurement signal, while configurable current and voltage transformer ratios enable the meter to calculate energy consumption for the primary electrical circuit.

Beyond accumulated active energy, the A44 113-100 provides instrumentation values including power, current, line-to-line and line-to-neutral voltage, frequency and power factor, both per phase and as total values. M-Bus communication, configurable alarms and pulse functionality allow this information to be incorporated into wider building-management, energy-management and industrial monitoring systems.

Typical Applications

  • Industrial three-phase energy monitoring.
  • Commercial building electricity metering.
  • CT/VT-connected electrical sub-metering.
  • Higher-current distribution boards and switchgear.
  • Building management systems using M-Bus communication.
  • Factory and production-facility energy monitoring.
  • Tenant and departmental electricity consumption monitoring.
  • Electrical instrumentation and alarm monitoring.
  • Energy efficiency and consumption analysis.
  • Three-phase 3-wire and 4-wire distribution systems.

Technical Specifications

Tick the specs you need, then view products that match.

Measurement Connection Type CT connection
MID Approval Yes
Device Type Energy meter
Series A44 Energy Meters
ABB order code 2CMA100249R1000
Product type Three-phase electricity / energy meter
Connection type CT/VT transformer connected
Number of phases 3
Network configuration 3-wire / 4-wire
Nominal current 1 A
Maximum measurement current 6 A
Phase-to-neutral voltage 57.7–288 V AC
Phase-to-phase voltage 100–500 V AC
System voltage range 3 × 57.7/100–288/500 V AC
Frequency 50–60 Hz
Measured energy Active energy
Active energy accuracy Class B (Class 1)
Communication M-Bus
Additional interface Infrared
Output 1 configurable pulse / alarm output
Alarm capability Up to 25 configurable alarms
Display Backlit digital display, up to 7 digits
Tariff Single tariff
Protection rating IP20
Mounting type DIN rail
Module width 7 DIN modules
Dimensions (W × H × D) 123 × 97 × 65 mm
Weight approx. 0.35 kg
Standards IEC 62052-11, IEC 62053-21, EN 50470-1, EN 50470-3
Approvals IEC approved, MID approved and verified

Frequently Asked Questions

What is the ABB A44 113-100 used for?

The ABB A44 113-100 is used for three-phase transformer-connected active energy measurement in commercial and industrial electrical systems, including 3-wire and 4-wire networks.

What measurement current does the ABB A44 113-100 support?

The A44 113-100 has a nominal measurement current of 1 A and supports measurement current up to 6 A through its transformer-connected inputs.

What is the accuracy of the ABB A44 113-100?

The meter measures active electrical energy to Class B (Class 1) accuracy and is IEC approved as well as MID approved and verified.

Does the ABB A44 113-100 support M-Bus communication?

Yes. The A44 113-100 includes an integrated M-Bus interface for remote meter reading and integration with compatible building and energy-management systems.

What electrical values can the A44 113-100 display?

The meter can display active energy, power, current, line-to-line and line-to-neutral voltage, frequency and power factor, with relevant instrumentation values available per phase and as total values.

Trusted Energy Measurement from ABB

ABB A44 energy meters provide accurate transformer-connected three-phase measurement with extensive instrumentation and communication functionality, supporting dependable energy monitoring across commercial buildings, industrial facilities and electrical distribution systems.