Lovato DM2TA0800 split-core current transformer with 800/5 A ratio, 80 x 80 mm opening, 3 VA class 0.5 and 7.5 VA class 1 burden for industrial energy monitoring.
£145.45
The Lovato DM2TA0800 is a high-performance split-core current transformer designed for accurate current measurement in industrial switchboards, electrical distribution panels and energy-monitoring systems. Featuring a 800/5 A transformation ratio, it converts a primary current of up to 800 A into a standard 5 A secondary output for connection to compatible energy meters, multifunction power analysers, ammeters and protection devices.
Its split-core construction allows the transformer to be installed around existing conductors or busbars without disconnecting the primary circuit, making it ideal for retrofit metering projects, energy-management upgrades and operational installations where downtime must be minimised. The robust housing and screw fixing provide dependable long-term performance in demanding industrial environments.
Designed for continuous operation at 50/60 Hz, the DM2TA0800 features a large 80 × 80 mm internal opening, 3 VA burden at accuracy class 0.5 and 7.5 VA burden at accuracy class 1, providing accurate and reliable current measurement across a wide range of industrial and commercial applications.
Current transformers safely reduce high primary currents into proportional low-current outputs suitable for measuring equipment. The Lovato DM2TA0800 converts currents up to 800 A into a standard 5 A secondary signal, enabling safe monitoring of electrical loads, energy consumption and system performance.
Its split-core construction removes the need to disconnect existing conductors during installation, making it particularly valuable when upgrading live electrical systems with additional metering or monitoring equipment while minimising operational disruption.
Tick the specs you need, then view products that match.
| Mounting Type | Panel / base | |
|---|---|---|
| Device Type | Split-core CT | |
| Rated Primary Current (A) | 800 A | |
| Secondary Current / Output | 5 A | |
| Rated Burden (VA) | 3 VA | |
| Current | 5 A | |
| Manufacturer | Lovato Electric | |
| Series | DM2TA | |
| Model | DM2TA0800 | |
| Product type | Split-core current transformer | |
| Primary current | 800 A | |
| Secondary current | 5 A | |
| Transformation ratio | 800/5 A | |
| Internal opening | 80 × 80 mm | |
| Operating frequency | 50 / 60 Hz | |
| Burden | 3 VA (Class 0.5), 7.5 VA (Class 1) | |
| Rated insulation voltage | 720 V | |
| Permanent overload | 120% In | |
| Short-time thermal current | 40...60 × In for 1 second | |
| Dynamic current | 2.5 × Ith | |
| Insulation class | Class E | |
| Terminal type | Screw terminals | |
| Mounting | Screw fixing | |
| Protection rating | IP30 | |
| Operating temperature | -25°C to +50°C | |
| Storage temperature | -40°C to +80°C | |
| Relative humidity | 90% max. | |
| Dimensions (H × W × D) | approx. 142 × 50 × 144 mm | |
| Weight | approx. 1.05 kg | |
| Standards | IEC/EN 60044-1 | |
| EAN | 8013975178706 | |
| HS Code | 85389091 |
The DM2TA0800 measures electrical currents up to 800 A and provides a standard 5 A secondary output for compatible measuring instruments.
Yes. Its split-core construction allows installation around an existing conductor without disconnecting the primary circuit.
The transformer features a large 80 × 80 mm opening suitable for substantial cables and busbars.
The transformer provides 3 VA at accuracy class 0.5 and 7.5 VA at accuracy class 1.
It is commonly used in industrial switchboards, commercial electrical installations, energy-monitoring systems and retrofit metering projects.
Lovato Electric current transformers are trusted by panel builders, electrical contractors and industrial engineers to deliver reliable current measurement, safe retrofit installation and dependable performance in modern electrical distribution systems.