Carlo Gavazzi CTD8V12505AXXX CTD-8V solid-core current transformer with 1250 A primary current and 5 A secondary output for industrial electrical measurement applications.
£105.62
The Carlo Gavazzi CTD8V12505AXXX is a high-performance AC solid-core current transformer designed for accurate current measurement in industrial electrical systems, energy monitoring installations and power distribution applications. As part of the trusted Carlo Gavazzi CTD-8V current transformer series, it provides precise current transformation for measurement equipment requiring a standard 5 A secondary output.
The CTD-8V series features a solid-core construction with vertical bus-bar mounting capability, making it suitable for integration into electrical distribution systems, switchboards and industrial control panels. Its robust design includes isolated bus-bar fixing screws, double screw terminals and sealable terminal covers for secure installation.
With a rated primary current of 1250 A, a 5 A secondary output, a maximum bus-bar size of 30 × 80 mm and Class 0.5 accuracy, the CTD8V12505AXXX is suitable for precise monitoring of high-current electrical loads in industrial energy management applications.
Current transformers such as the Carlo Gavazzi CTD8V12505AXXX provide electrical isolation while converting high primary currents into a standard secondary current signal suitable for meters, monitoring equipment and protection devices. This enables safe and accurate measurement of electrical loads within industrial installations.
The CTD-8V series is designed for demanding energy management and automation applications where reliable performance, flexible installation and accurate current measurement are required. Its solid-core construction and large bus-bar mounting capability make it suitable for electrical distribution equipment and industrial control systems.
Tick the specs you need, then view products that match.
| Mounting Type | Busbar | |
|---|---|---|
| Rated Primary Current (A) | 1250 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 80 × 30 mm | |
| Accuracy Class | Class 0.5 | |
| Rated Burden (VA) | 12 VA | |
| Device Type | Solid-core CT | |
| IP Rating | IP20 | |
| Manufacturer | Carlo Gavazzi | |
| Series | CTD-8V | |
| Model | CTD8V12505AXXX | |
| Product type | AC solid-core current transformer | |
| Primary current | 1250 A | |
| Secondary current | 5 A | |
| Current ratio | 1250:5 | |
| Accuracy class | Class 0.5 | |
| Operating frequency | 48–62 Hz | |
| Maximum system voltage | 0.72 kV | |
| Rated insulation level | 3 kV / 1 min at 50 Hz | |
| Standards | EN 61869-2 | |
| Mounting type | Vertical bus-bar mounting | |
| Maximum bus-bar size | 30 × 80 mm | |
| Connection type | Screw terminals | |
| Cable cross section | 1.5–6 mm² | |
| Rated secondary apparent power | 12 VA | |
| Protection rating | IP00 (IP20 with sealable terminal covers and wire terminals) | |
| Housing material | ABS self-extinguishing UL 94 V-0 | |
| Operating temperature | -25 °C to +60 °C | |
| Weight | approx. 450–700 g |
The CTD8V12505AXXX is an AC current transformer designed for measuring high electrical currents in industrial monitoring, metering and protection applications.
The CTD8V12505AXXX has a rated primary current of 1250 A.
The current transformer provides a standard 5 A secondary current output.
The CTD8V12505AXXX provides Class 0.5 accuracy for reliable electrical measurement.
The current transformer supports bus-bars up to 30 × 80 mm in size.
Carlo Gavazzi CTD-8V current transformers are widely used in industrial automation and energy monitoring systems where accurate measurement, robust construction and reliable power monitoring are essential.