Carlo Gavazzi CTD8S20005AXXX split-core current transformer with 2000 A primary current and 5 A secondary output for high-current industrial measurement applications.
£131.51
The Carlo Gavazzi CTD8S20005AXXX is a high-current split-core AC current transformer designed for accurate measurement and monitoring of large electrical currents in industrial power distribution systems. As part of the reliable Carlo Gavazzi CTD-8S current transformer series, it provides a standard 5 A secondary output for connection to energy meters, monitoring systems and electrical protection equipment.
The CTD8S20005AXXX features a split-core design with bus-bar mounting capability, allowing easier installation and retrofit integration without requiring complete conductor removal. Its robust construction includes secure fixing screws, sealable terminal covers and flexible mounting options for demanding industrial electrical applications.
With a 2000 A primary current rating, 5 A secondary output and a 31 mm × 81 mm opening suitable for bus-bar installations, the CTD8S20005AXXX is designed for dependable current measurement in high-power electrical distribution and energy monitoring applications.
Current transformers such as the Carlo Gavazzi CTD8S20005AXXX allow high electrical currents to be monitored safely by reducing the primary current to a standard secondary signal. This enables accurate connection to energy meters, monitoring equipment and industrial protection systems.
The CTD-8S series is designed for demanding industrial installations where accurate measurement, secure mounting and long-term reliability are essential. Its split-core construction provides installation flexibility for both new systems and retrofit projects.
Tick the specs you need, then view products that match.
| Mounting Type | Busbar, DIN rail, Panel / base | |
|---|---|---|
| Rated Primary Current (A) | 2000 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 80 × 30 mm | |
| Accuracy Class | Class 1 | |
| Rated Burden (VA) | 20 VA | |
| Device Type | Split-core CT | |
| IP Rating | IP20 | |
| Manufacturer | Carlo Gavazzi | |
| Series | CTD-8S | |
| Model | CTD8S20005AXXX | |
| Product type | Split-core AC current transformer | |
| Primary current | 2000 A | |
| Secondary current | 5 A | |
| Current ratio | 2000:5 | |
| Accuracy class | Class 1 | |
| Rated secondary apparent power | 20 VA | |
| Frequency range | 48–62 Hz | |
| Maximum system voltage | 0.72 kV | |
| Rated insulation level | 3 kV / 1 min at 50 Hz | |
| Insulation class | E (maximum 75 °C) | |
| Security factor | ≤5 | |
| Mounting type | Bus-bar / DIN rail / panel mounting | |
| Opening size | 31 mm × 81 mm | |
| Maximum bus-bar size | 30 mm × 80 mm | |
| Housing material | Self-extinguishing UL 94 V-0 material | |
| Connection type | Double screw terminals | |
| Protection rating | IP00 without terminal covers / IP20 with sealable terminal covers | |
| Working temperature | -25 °C to product-specific maximum rating |
The CTD8S20005AXXX is used for measuring high AC currents and providing a standard 5 A secondary output for industrial monitoring and metering equipment.
The transformer has a 2000:5 ratio, with a 2000 A primary current rating and 5 A secondary output.
The CTD8S20005AXXX is a split-core bus-bar current transformer designed for high-current industrial installations.
The transformer features a 31 mm × 81 mm opening for bus-bar installation.
The CTD8S20005AXXX provides Class 1 accuracy for reliable industrial current measurement applications.
Carlo Gavazzi CTD-8S current transformers are widely used in high-current industrial measurement applications where accurate monitoring, safe installation and dependable energy management are required.