CTD5S1505AXXX - 150 A Primary current, 5A output 26x32 mm

CTD5S1505AXXX – 150 A Primary current, 5A output 26×32 mm

Carlo Gavazzi CTD5S1505AXXX is a CTD-5S split-core 150/5 A AC current transformer with Class 1 accuracy, a 1.5 VA rated burden and a 26 mm conductor opening for industrial electrical metering and energy monitoring.

SKU: CTD5S1505AXXXMPN: CTD5S1505AXXX
Price
List Price £117.70 ex VAT
Your Price (ex VAT) Save 15%
£100.05 15% OFF
You save £17.66 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £100.05
Trade pricing is personalised to your account

Manufacturer Lead Time

Sold in packs of 3

£100.05

Why Choose the Carlo Gavazzi CTD5S1505AXXX Split-Core Current Transformer?

The Carlo Gavazzi CTD5S1505AXXX is a reliable split-core AC current transformer designed for electrical current measurement, energy monitoring and metering applications. As part of the Carlo Gavazzi CTD-5S current transformer series, its split-core construction enables installation around an existing cable or busbar without requiring the primary conductor to be disconnected.

This current transformer provides a 150 A rated primary current and 5 A secondary output, giving a 150/5 A transformation ratio for connection to compatible energy meters, power analysers and electrical monitoring equipment. The CTD5S1505AXXX provides Accuracy Class 1 with a 1.5 VA rated burden, supporting dependable measurement performance in industrial and commercial electrical systems.

The CTD5S1505AXXX has a 26 mm nominal conductor opening and accommodates rectangular busbars up to 26 × 32 mm. Its split-core format, double screw terminals and busbar mounting facility make it particularly suitable for retrofit installations in switchboards, distribution panels and control cabinets where existing conductors need to remain in place.

Key Advantages

  • Practical split-core current transformer for retrofit installations.
  • 150/5 A transformation ratio for industrial electrical current measurement.
  • Standard 5 A secondary output for compatible metering equipment.
  • Accuracy Class 1 supports dependable current and energy measurement.
  • 1.5 VA rated burden at Class 1.
  • 26 mm conductor opening accommodates suitable cables.
  • Supports rectangular busbars up to 26 × 32 mm.
  • Split-core construction simplifies installation around existing conductors.

Key Features

  • Carlo Gavazzi CTD-5S current transformer series.
  • 150 A rated primary current.
  • 5 A rated secondary current.
  • 150/5 A current transformation ratio.
  • Accuracy Class 1.
  • 1.5 VA rated burden at Class 1.
  • 2.5 VA rated burden at Class 3.
  • 26 mm nominal conductor opening.
  • 26 × 32 mm maximum busbar size.
  • 48–62 Hz operating frequency.
  • 0.72 kV maximum system voltage.
  • Double screw terminals for flexible secondary wiring.
  • Split-core construction with busbar mounting facility.

Convenient Current Measurement for Existing Electrical Systems

Current transformers such as the Carlo Gavazzi CTD-5S convert the current flowing through a primary conductor into a lower proportional secondary current suitable for compatible measuring instruments. This allows energy meters, power analysers and monitoring systems to measure substantial electrical loads without requiring the full primary circuit current to pass directly through the measuring device.

The split-core construction of the CTD5S1505AXXX makes it particularly useful for retrofit projects. The transformer can be opened and positioned around an existing cable or busbar, helping minimise disruption to established wiring while its 150/5 A ratio provides a standard 5 A secondary signal for compatible industrial metering equipment.

Typical Applications

  • Retrofit energy metering installations.
  • Electrical switchboards and distribution panels.
  • Power analysers and multifunction electrical meters.
  • Building energy management systems.
  • Industrial machinery and control cabinets.
  • Electrical load and consumption monitoring.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Busbar, Cable
Device Type Split-core CT
Rated Primary Current (A) 150 A
Secondary Current / Output 5 A
Aperture (mm) 32 × 26 mm
Accuracy Class Class 1
Rated Burden (VA) 1.5 VA
Manufacturer Carlo Gavazzi
Series CTD-5S
Model CTD5S1505AXXX
Product type Split-core AC current transformer
Rated primary current 150 A
Rated secondary current 5 A
Transformation ratio 150/5 A
Accuracy class Class 1
Rated burden at Class 1 1.5 VA
Rated burden at Class 3 2.5 VA
Operating frequency 48–62 Hz
Maximum system voltage 0.72 kV
Rated insulation level 3 kV / 1 min at 50 Hz
Extended current rating 120%
Security factor ≤5
Opening diameter 26 mm nominal
Maximum busbar size 26 × 32 mm
Core type Split core
Secondary connection Double screw terminals
Number of primary inputs 1
Mounting type Cable / busbar mounting

Frequently Asked Questions

What is the Carlo Gavazzi CTD5S1505AXXX used for?

The CTD5S1505AXXX is used to convert a 150 A primary current into a proportional 5 A secondary current for compatible electrical meters, power analysers and energy-monitoring equipment.

What is the transformation ratio of the CTD5S1505AXXX?

The current transformer has a 150/5 A transformation ratio, with a rated primary current of 150 A and a rated secondary output of 5 A.

What accuracy class does this current transformer provide?

The CTD5S1505AXXX provides Accuracy Class 1 with a rated burden of 1.5 VA, supporting dependable current and energy measurement.

What size conductor can the CTD5S1505AXXX accommodate?

The transformer has a nominal 26 mm conductor opening and accommodates rectangular busbars up to 26 × 32 mm.

Why use a split-core current transformer?

A split-core current transformer can be opened and fitted around an existing conductor, making it particularly useful for retrofit metering and monitoring installations where disconnecting existing cables or busbars would be inconvenient.

Trusted by Electrical and Automation Professionals

Carlo Gavazzi CTD-5S split-core current transformers provide a practical solution for electrical current measurement and energy monitoring, combining straightforward retrofit installation with dependable integration into industrial and commercial metering systems.