Carlo Gavazzi CTD2X1501AXXX solid-core current transformer with 150 A primary current, 1 A secondary output, Class 0.5 accuracy and a 24 mm cable aperture for industrial electrical measurement and energy monitoring.
£40.33
The Carlo Gavazzi CTD2X1501AXXX is a compact and accurate solid-core current transformer (CT) designed for AC current measurement in industrial electrical installations, energy monitoring systems and power distribution equipment. As part of the Carlo Gavazzi CTD-2X series, it provides dependable current transformation for use with compatible energy meters, power analysers and electrical monitoring equipment.
This current transformer converts the current flowing through a primary cable or busbar into a proportional secondary current that can be safely measured by compatible instrumentation. Its solid-core construction provides a robust solution for permanent installations, while the stepped aperture accommodates both cables and common industrial busbar sizes. A double set of connection terminals and integrated DIN rail mounting facility help simplify installation within electrical panels and switchboards.
With a rated primary current of 150 A and a 1 A secondary output, the CTD2X1501AXXX provides a transformation ratio of 150/1 A. It features Class 0.5 accuracy, a 24 mm cable aperture and support for busbars up to approximately 32 mm wide, making it well suited to accurate industrial current measurement and energy monitoring applications.
Current transformers such as the Carlo Gavazzi CTD2X1501AXXX allow AC current to be monitored without routing the full primary current directly through the connected measuring instrument. The transformer produces a proportional 1 A secondary current that can be measured by compatible energy meters, power analysers and electrical monitoring equipment.
The CTD-2X series is designed for electrical applications where accurate measurement, robust construction and flexible installation are important. Its 150/1 A transformation ratio, Class 0.5 accuracy, stepped conductor opening and solid-core design make the CTD2X1501AXXX particularly suitable for permanent energy management, power distribution and electrical monitoring installations.
Tick the specs you need, then view products that match.
| Mounting Type | Busbar, DIN rail, Panel / base | |
|---|---|---|
| Rated Primary Current (A) | 150 A | |
| Secondary Current / Output | 1 A | |
| Aperture (mm) | 32 mm | |
| Accuracy Class | Class 0.5 | |
| Device Type | Solid-core CT | |
| Manufacturer | Carlo Gavazzi | |
| Series | CTD-2X | |
| Model | CTD2X1501AXXX | |
| Product type | Solid-core current transformer | |
| Rated primary current | 150 A | |
| Rated secondary current | 1 A | |
| Transformation ratio | 150/1 A (150:1) | |
| Accuracy class | Class 0.5 | |
| Hole diameter | 24 mm | |
| Maximum busbar width | 32 mm | |
| Opening height | approx. 25.5 mm | |
| Typical busbar sizes | 30 × 10 mm / 25 × 20 mm | |
| Operating frequency | 50 / 60 Hz | |
| Maximum system voltage | 0.72 kV | |
| Rated insulation level | 3 kV / 1 min at 50 Hz | |
| Security factor | ≤5 | |
| Construction | Solid core | |
| Primary connection | Through-feed cable or busbar | |
| Secondary connection | Screw terminals | |
| Mounting | DIN rail, panel or busbar mounting | |
| Dimensions (H × W × D) | approx. 86 × 56 × 42 mm | |
| EAN | 8030956041415 |
The CTD2X1501AXXX is used to transform AC current into a proportional 1 A secondary current for electrical measurement, energy metering and power monitoring applications.
The current transformer has a rated primary current of 150 A.
The CTD2X1501AXXX provides a rated 1 A secondary output, giving it a transformation ratio of 150/1 A or 150:1.
The CTD2X1501AXXX has Class 0.5 accuracy, making it suitable for accurate industrial current measurement and energy monitoring applications.
The current transformer has a 24 mm cable aperture and supports busbars up to approximately 32 mm wide, including common 30 × 10 mm and 25 × 20 mm busbar arrangements.
Carlo Gavazzi CTD solid-core current transformers are designed to provide dependable current measurement for industrial energy monitoring, power distribution and automation systems, combining accurate measurement with practical installation options and robust construction.