Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CT1M-S-80 1000 2CSG280815R1000 is a 1000 A/5 A class 0.5 split-core through-primary current transformer with 10 VA class 0.5 output for accurate indirect electrical metering and monitoring applications.
£356.21
The ABB CT1M-S-80 1000, order code 2CSG280815R1000, is a 1000 A/5 A split-core current transformer designed for indirect measurement of electrical parameters in metering, monitoring and energy management applications. Part of ABB's Metering Accessories range, it transforms a nominal 1000 A primary current into a standardised 5 A secondary current for compatible electricity meters, network analysers and measuring instruments.
The ABB CT1M-S-80 series combines a through-primary measurement arrangement with split-core construction, allowing the transformer to be fitted around an existing busbar. This makes the range particularly useful for retrofit metering and monitoring installations where disconnecting or removing the primary conductor would be inconvenient.
With a 1000 A rated primary current, 5 A rated secondary current and accuracy class 0.5, the CT1M-S-80 1000 provides a 1000:5 transformation ratio for accurate indirect electrical measurement. It delivers 10 VA at class 0.5, 15 VA at class 1 and 20 VA at class 3, while its CT1M-S-80 aperture accommodates vertical busbars up to 85 × 55 mm.
Current transformers allow meters and measuring instruments to monitor electrical circuits carrying currents above their direct measurement range. The transformer produces a proportional secondary current, allowing electrical parameters to be measured without routing the full primary circuit current through the connected measuring instrument.
The ABB CT1M-S-80 1000 combines this measurement principle with a split-core design, making it particularly useful for retrofit metering, maintenance and extensions to existing electrical systems. Its 1000 A/5 A ratio, class 0.5 accuracy and 85 × 55 mm vertical busbar opening provide a practical solution for high-current energy metering and monitoring applications.
Tick the specs you need, then view products that match.
| Mounting Type | Busbar | |
|---|---|---|
| Device Type | Solid-core CT | |
| Rated Primary Current (A) | 1000 A | |
| Secondary Current / Output | 5 A | |
| Accuracy Class | Class 0.5 | |
| Rated Burden (VA) | 10 VA | |
| Product group | Metering Accessories | |
| Series | CT1M-S-80 | |
| Order code / Product ID | 2CSG280815R1000 | |
| Product type | Split-core through-primary current transformer | |
| Application | Indirect electrical measurement and metering | |
| Rated primary current | 1000 A | |
| Rated secondary current | 5 A | |
| Current ratio | 1000:5 | |
| Best accuracy class | 0.5 | |
| Rated output, class 0.5 | 10 VA | |
| Rated output, class 1 | 15 VA | |
| Rated output, class 3 | 20 VA | |
| Current limiting factor | FS 10 | |
| Rated frequency | 50–60 Hz | |
| Protection rating | IP20 | |
| Construction | Split-core, through-primary | |
| Maximum vertical busbar section | 85 × 55 mm | |
| Mounting | Busbar | |
| Standard | IEC 61869-2 | |
| Dimensions (H × W × D) | 158 × 125 × 40 mm | |
| Net weight | 1.42 kg | |
| EAN / GTIN | 8012542808152 | |
| Pack unit | 1 piece |
The CT1M-S-80 1000 is a split-core current transformer for indirect electrical measurement, converting a nominal 1000 A primary current into a standard 5 A secondary current for compatible meters, network analysers and measuring instruments.
The CT1M-S-80 1000 has a 1000 A primary current and 5 A secondary current, providing a transformation ratio of 1000:5.
The ABB CT1M-S-80 1000 has a best accuracy class of 0.5 and provides 10 VA at class 0.5, 15 VA at class 1 and 20 VA at class 3.
The CT1M-S-80 through-primary opening accommodates a vertical busbar up to 85 × 55 mm, making it suitable for substantial conductors in commercial and industrial distribution systems.
The split-core construction allows the transformer to be installed around an existing busbar, making it particularly useful for retrofit metering, maintenance and energy monitoring installations where removing the primary conductor would be inconvenient.
ABB CT1M-S current transformers combine standard 5 A secondary measurement with split-core construction, providing a practical solution for accurate indirect current measurement in new and existing commercial and industrial electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.