ABB CT1M-S-80 400 is a 400/5 A through-primary current transformer with Class 0.5 accuracy and 2.5 VA rated output for indirect electrical metering and energy-monitoring applications.
£296.82
The ABB CT1M-S-80 400 is a reliable 400/5 A current transformer designed for indirect measurement of electrical current in low-voltage metering and energy-monitoring systems. As part of the ABB CT1M current transformer series, it transforms the primary current into a standardised 5 A secondary current suitable for connection to compatible meters and electrical measuring instruments.
Designed in accordance with IEC 61869-2, the CT1M-S-80 400 provides a best accuracy class of 0.5 for dependable electrical measurement. Its through-primary construction is designed for busbar conductors, making it suitable for switchboards, distribution panels and energy-monitoring installations where indirect current measurement is required.
With a rated primary current of 400 A, rated secondary current of 5 A and rated frequency of 50–60 Hz, the CT1M-S-80 400 provides rated outputs of 2.5 VA at Class 0.5, 3.75 VA at Class 1 and 5 VA at Class 3. The CT1M-S-80 format accommodates a vertical busbar section up to 85 × 55 mm, providing ample conductor clearance for electrical distribution applications.
Current transformers allow measuring equipment to monitor electrical current without routing the full primary current directly through the measuring instrument. The ABB CT1M-S-80 400 converts a 400 A primary current proportionally to a standard 5 A secondary signal, enabling compatible ammeters, multifunction meters and energy meters to perform indirect electrical measurement.
The CT1M range is designed for electrical distribution and energy-efficiency applications where accurate and dependable current measurement is required. The CT1M-S-80 through-primary format provides a generous busbar opening, while its defined accuracy classes and VA ratings allow the transformer to be matched appropriately to compatible metering circuits.
Tick the specs you need, then view products that match.
| Rated Burden (VA) | 2.5 VA | |
|---|---|---|
| Device Type | Solid-core CT | |
| Rated Primary Current (A) | 400 A | |
| Secondary Current / Output | 5 A | |
| Accuracy Class | Class 0.5 | |
| Series | CT1M-S-80 | |
| Order code | 2CSG280775R1000 | |
| Product type | Current transformer | |
| Primary rated current | 400 A | |
| Secondary rated current | 5 A | |
| Transformation ratio | 400/5 A | |
| Best accuracy class | 0.5 | |
| Rated output, Class 0.5 | 2.5 VA | |
| Rated output, Class 1 | 3.75 VA | |
| Rated output, Class 3 | 5 VA | |
| Rated frequency | 50–60 Hz | |
| Standard | IEC 61869-2 | |
| Protection rating | IP20 | |
| Primary type | Through primary | |
| Maximum vertical busbar section | 85 × 55 mm | |
| Dimensions (H × W × D) | 158 × 125 × 40 mm | |
| Weight | 1.27 kg |
The CT1M-S-80 400 is used for indirect measurement of electrical current, transforming the primary current into a standard 5 A secondary current suitable for compatible meters and monitoring equipment.
The transformer has a rated primary current of 400 A and a rated secondary current of 5 A, giving a 400/5 A transformation ratio.
The CT1M-S-80 400 provides a best accuracy class of 0.5, with a rated output of 2.5 VA at Class 0.5.
The CT1M-S-80 through-primary format accommodates a vertical busbar section up to 85 × 55 mm.
The ABB CT1M-S-80 400 is designed in accordance with IEC 61869-2 for instrument current transformers.
ABB CT1M current transformers provide dependable current transformation for indirect electrical measurement, supporting accurate metering and energy monitoring across commercial and industrial power-distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.