Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CT1M-10 600 2CSG280605R1000 is a class 0.5 closed-core through-primary current transformer with a 600 A primary rating, 5 A secondary output and 10 VA class 0.5 rated output for indirect electrical metering applications.
£123.69
The ABB CT1M-10 600 is a closed-core 600/5 A current transformer designed for indirect measurement of electrical parameters in low-voltage distribution systems. Supplied under ABB order code 2CSG280605R1000, it forms part of the ABB CT1M current transformer range and is designed in accordance with IEC 61869-2.
With a rated primary current of 600 A and a rated secondary current of 5 A, the CT1M-10 600 converts primary circuit current into a proportional standard secondary signal for compatible electricity meters, ammeters, power analysers and monitoring equipment. It provides class 0.5 accuracy with a 10 VA rated output, together with 15 VA outputs at classes 1 and 3.
The CT1M-10 600 uses a through-primary design with a large opening suitable for cables up to 86 mm and horizontal or vertical busbars up to 100 × 30 mm, 80 × 50 mm or 70 × 60 mm. Its 155 × 140 × 45 mm dimensions, IP20 degree of protection and 50–60 Hz rated frequency make it a practical choice for commercial and industrial metering installations.
Current transformers enable electricity meters and monitoring instruments to measure circuits carrying currents above their direct-input range. The ABB CT1M-10 600 transforms a primary current of 600 A into a proportional 5 A secondary current, allowing compatible instrumentation to perform indirect measurement of electrical network parameters.
The CT1M-10 600 combines class 0.5 accuracy with a large through-primary opening capable of accepting substantial cables and busbars. This makes it particularly useful in switchboards and distribution systems where conductor dimensions require a larger CT aperture while maintaining a standard 5 A secondary interface for metering equipment.
Tick the specs you need, then view products that match.
| Rated Burden (VA) | 10 VA | |
|---|---|---|
| Rated Primary Current (A) | 600 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 86 mm | |
| Accuracy Class | Class 0.5 | |
| Device Type | Solid-core CT | |
| Series | CT1M-10 | |
| ABB order code | 2CSG280605R1000 | |
| Product group | Metering Accessories | |
| Product type | Closed-core current transformer | |
| Rated primary current | 600 A | |
| Rated secondary current | 5 A | |
| Transformation ratio | 600/5 A | |
| Best accuracy class | 0.5 | |
| Rated output, class 0.5 | 10 VA | |
| Rated output, class 1 | 15 VA | |
| Rated output, class 3 | 15 VA | |
| Rated frequency | 50–60 Hz | |
| Protection rating | IP20 | |
| Mounting type | Through primary | |
| Conductor arrangement | Cable / horizontal or vertical busbar | |
| Maximum cable diameter | 86 mm | |
| Horizontal busbar sizes | 100 × 30 mm / 80 × 50 mm / 70 × 60 mm | |
| Vertical busbar sizes | 100 × 30 mm / 80 × 50 mm / 70 × 60 mm | |
| Dimensions (H × W × D) | 155 × 140 × 45 mm | |
| Weight | 0.92 kg | |
| Standard | IEC 61869-2 | |
| GTIN / EAN | 8012542806059 |
The ABB CT1M-10 600 is a current transformer used to convert a 600 A primary current into a proportional 5 A secondary current for indirect electrical metering and network measurement.
The CT1M-10 600 has a rated transformation ratio of 600/5 A, with a 600 A rated primary current and a 5 A rated secondary current.
The ABB CT1M-10 600 provides class 0.5 accuracy at 10 VA. It also provides 15 VA at class 1 and 15 VA at class 3.
The through-primary design accommodates cables up to 86 mm and horizontal or vertical busbars up to 100 × 30 mm, 80 × 50 mm or 70 × 60 mm.
The ABB CT1M-10 600 is designed in accordance with IEC 61869-2, the applicable standard for instrument current transformers.
ABB CT1M current transformers provide dependable conversion of primary currents into standard 5 A secondary signals, supporting accurate indirect measurement in commercial, industrial and electrical distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.