Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CT1M-8 2000 2CSG280575R1000 is a 2000 A/5 A class 0.5 through-primary current transformer with 60 VA class 0.5 output for accurate high-current indirect electrical metering and measurement applications.
£189.40
The ABB CT1M-8 2000, order code 2CSG280575R1000, is a 2000 A/5 A through-primary current transformer designed for indirect measurement of electrical parameters in high-current metering, monitoring and energy management applications. Part of ABB's Metering Accessories range, it transforms a high primary current into a standardised 5 A secondary current for compatible electricity meters, network analysers and measuring instruments.
As part of the ABB CT1M current transformer series, the CT1M-8 2000 is designed according to IEC 61869-2. Its large through-primary aperture supports cable and busbar installations, making it particularly suitable for industrial distribution boards, power centres and switchboards where substantial conductors must be monitored.
With a 2000 A rated primary current, 5 A rated secondary current and accuracy class 0.5, the CT1M-8 2000 provides a 2000:5 transformation ratio for accurate indirect electrical measurement. It delivers 60 VA at class 0.5, 60 VA at class 1 and 60 VA at class 3, while accommodating cables up to 73 mm and horizontal or vertical busbars up to 80 × 30 mm or 60 × 50 mm.
Current transformers allow meters and measuring instruments to monitor electrical circuits carrying currents above their direct measurement range. The transformer produces a proportional secondary current, allowing electrical parameters to be measured without routing the full primary circuit current through the connected measuring instrument.
The ABB CT1M-8 2000 converts a nominal 2000 A primary current into a 5 A secondary current. Its class 0.5 accuracy, 60 VA class 0.5 output and large conductor aperture make it particularly suitable for accurate indirect current measurement in industrial distribution boards, main switchboards, power centres and energy management systems using substantial cables or busbars.
Tick the specs you need, then view products that match.
| Mounting Type | Busbar, Cable, Panel / base | |
|---|---|---|
| Rated Primary Current (A) | 2000 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 73 mm | |
| Accuracy Class | Class 0.5 | |
| Rated Burden (VA) | 60 VA | |
| Device Type | Solid-core CT | |
| Product group | Metering Accessories | |
| Series | CT1M-8 | |
| Order code / Product ID | 2CSG280575R1000 | |
| Product type | Through-primary current transformer | |
| Application | Indirect electrical measurement and metering | |
| Rated primary current | 2000 A | |
| Rated secondary current | 5 A | |
| Current ratio | 2000:5 | |
| Best accuracy class | 0.5 | |
| Rated output, class 0.5 | 60 VA | |
| Rated output, class 1 | 60 VA | |
| Rated output, class 3 | 60 VA | |
| Current limiting factor | FS 5 | |
| Rated frequency | 50–60 Hz | |
| Protection rating | IP20 | |
| Construction | Through-primary current transformer | |
| Number of primary inputs | 1 | |
| Maximum cable diameter | 73 mm | |
| Maximum horizontal busbar | 80 × 30 mm or 60 × 50 mm | |
| Maximum vertical busbar | 80 × 30 mm or 60 × 50 mm | |
| Mounting | Cable, busbar or base mounting with feet | |
| Standard | IEC 61869-2 | |
| Dimensions (H × W × D) | 155 × 140 × 45 mm | |
| Net weight | 1.29 kg | |
| EAN / GTIN | 8012542805755 | |
| Pack unit | 1 piece |
The CT1M-8 2000 is a current transformer for indirect electrical measurement, converting a nominal 2000 A primary current into a standard 5 A secondary current for compatible meters, network analysers and measuring instruments.
The CT1M-8 2000 has a 2000 A primary current and 5 A secondary current, providing a transformation ratio of 2000:5.
The ABB CT1M-8 2000 has a best accuracy class of 0.5 and provides a rated output of 60 VA at class 0.5. It also provides 60 VA at class 1 and 60 VA at class 3.
The CT1M-8 through-primary design accommodates cables up to 73 mm in diameter and horizontal or vertical busbars up to 80 × 30 mm or 60 × 50 mm.
The ABB CT1M-8 2000 is designed according to IEC 61869-2 for instrument current transformers and is intended for indirect measurement of electrical network parameters.
ABB CT1M current transformers provide a dependable solution for converting high primary currents into standard 5 A secondary signals, supporting accurate indirect electrical measurement in industrial metering, monitoring and energy management installations.