ABB CT1M-7 2500 2CSG280515R1000 is a 2500 A/5 A class 0.5 through-primary current transformer with 15 VA class 0.5 output for accurate high-current indirect electrical metering and measurement applications.
£129.87
The ABB CT1M-7 2500, order code 2CSG280515R1000, is a 2500 A/5 A through-primary current transformer designed for indirect measurement of electrical parameters in high-current metering, monitoring and energy management applications. Part of ABB's Metering Accessories range, it transforms a high primary current into a standardised 5 A secondary current for compatible electricity meters, network analysers and measuring instruments.
As part of the ABB CT1M current transformer series, the CT1M-7 2500 is designed according to IEC 61869-2. Its through-primary construction and large 101 × 56 mm rated cross-section make it particularly suitable for substantial busbar installations in industrial distribution equipment and high-current electrical switchboards.
With a 2500 A rated primary current, 5 A rated secondary current and accuracy class 0.5, the CT1M-7 2500 provides a 2500:5 transformation ratio for accurate indirect electrical measurement. It provides a rated output of 15 VA at class 0.5, 15 VA at class 1 and 15 VA at class 3, together with an FS 10 current limiting factor.
Current transformers allow meters and measuring instruments to monitor electrical circuits carrying currents above their direct measurement range. The transformer produces a proportional secondary current, allowing electrical parameters to be measured without routing the full primary circuit current through the connected measuring instrument.
The ABB CT1M-7 2500 converts a nominal 2500 A primary current into a 5 A secondary current. Its class 0.5 accuracy, 15 VA class 0.5 output and large 101 × 56 mm rated cross-section make it suitable for accurate indirect current measurement in high-current industrial distribution, switchboard, power monitoring and energy management applications.
Tick the specs you need, then view products that match.
| Mounting Type | Busbar, DIN rail, Panel / base | |
|---|---|---|
| Rated Primary Current (A) | 2500 A | |
| Secondary Current / Output | 5 A | |
| Accuracy Class | Class 0.5 | |
| Rated Burden (VA) | 15 VA | |
| Device Type | Solid-core CT | |
| Product group | Metering Accessories | |
| Series | CT1M-7 | |
| Order code / Product ID | 2CSG280515R1000 | |
| Product type | Through-primary current transformer | |
| Application | Indirect electrical measurement and metering | |
| Rated primary current | 2500 A | |
| Rated secondary current | 5 A | |
| Current ratio | 2500:5 | |
| Best accuracy class | 0.5 | |
| Accuracy | ±0.5% | |
| Rated output, class 0.5 | 15 VA | |
| Rated output, class 1 | 15 VA | |
| Rated output, class 3 | 15 VA | |
| Current limiting factor | FS 10 | |
| Rated frequency | 50–60 Hz | |
| Protection rating | IP20 | |
| Construction | Through-primary current transformer | |
| Number of primary inputs | 1 | |
| Rated cross-section | 101 × 56 mm | |
| Mounting | Busbar / mounting feet; optional DIN rail adapter | |
| Compatible DIN rail adapter | CT1M-4/5/6/7 DIN Rail Adapter | |
| Standard | IEC 61869-2 | |
| Dimensions (H × W × D) | 170 × 130 × 51 mm | |
| Net weight | 1.42 kg | |
| EAN / GTIN | 8012542805151 | |
| Pack unit | 1 piece |
The CT1M-7 2500 is a current transformer for indirect electrical measurement, converting a nominal 2500 A primary current into a standard 5 A secondary current for compatible meters, network analysers and measuring instruments.
The CT1M-7 2500 has a 2500 A primary current and 5 A secondary current, providing a transformation ratio of 2500:5.
The ABB CT1M-7 2500 has a best accuracy class of 0.5 and provides a rated output of 15 VA at class 0.5. It also provides 15 VA at class 1 and 15 VA at class 3.
The CT1M-7 2500 has a large 101 × 56 mm rated cross-section, making it suitable for substantial through-primary busbar installations.
Yes. Busbar and mounting feet fixings are supplied as standard, while the compatible CT1M-4/5/6/7 DIN Rail Adapter is available as an optional accessory for DIN rail installation.
ABB CT1M current transformers provide a dependable solution for converting high primary currents into standard 5 A secondary signals, supporting accurate indirect electrical measurement in industrial metering, monitoring and energy management installations.