ABB CT1M-6 250 is an IEC 61869-2 through-primary current transformer with a 250/5 A ratio, class 0.5 accuracy and 1.5 VA class 0.5 burden for indirect electrical measurement.
£74.22
The ABB CT1M-6 250 is a through-primary 250/5 A current transformer designed for indirect measurement of electrical network parameters. Supplied under ABB order code 2CSG280415R1000, it converts a rated primary current of 250 A into a proportional 5 A secondary current for compatible energy meters, ammeters and multifunction measuring instruments.
Part of ABB's CT1M current-transformer range, the CT1M-6 250 is designed in accordance with IEC 61869-2. It provides a best accuracy class of 0.5, with rated burdens of 1.5 VA at class 0.5, 2.5 VA at class 1 and 3.75 VA at class 3, providing a versatile measurement solution for commercial and industrial electrical systems.
The CT1M-6 frame provides a generous through-primary aperture, accommodating cables up to 65 mm diameter and horizontal or vertical busbars up to 80 × 10 mm, 60 × 30 mm or 50 × 50 mm. With 126 × 104 × 45 mm dimensions, IP20 protection and a rated frequency of 50–60 Hz, it is suitable for switchboards and metering assemblies requiring flexible conductor accommodation.
Current transformers enable electrical meters and measuring instruments to monitor circuits carrying currents beyond their direct-input capability. The ABB CT1M-6 250 converts a rated 250 A primary current into a proportional 5 A secondary current, providing a standardised signal for compatible electrical metering and monitoring equipment.
With class 0.5 accuracy available at a 1.5 VA burden, the CT1M-6 250 supports dependable current and energy measurement. Its unusually generous conductor opening for a 250 A transformer makes it particularly useful where large cables or busbars must pass through the CT, while supplied busbar and mounting-foot fixings simplify integration into electrical distribution assemblies.
Tick the specs you need, then view products that match.
| Rated Burden (VA) | 1.5 VA | |
|---|---|---|
| Rated Primary Current (A) | 250 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 65 mm | |
| Accuracy Class | Class 0.5 | |
| Device Type | Solid-core CT | |
| Series | CT1M-6 | |
| ABB order code | 2CSG280415R1000 | |
| Product type | Through-primary current transformer | |
| Rated primary current | 250 A | |
| Rated secondary current | 5 A | |
| Transformation ratio | 250/5 A | |
| Best accuracy class | Class 0.5 | |
| Rated burden at class 0.5 | 1.5 VA | |
| Rated burden at class 1 | 2.5 VA | |
| Rated burden at class 3 | 3.75 VA | |
| Rated frequency | 50–60 Hz | |
| Maximum cable diameter | 65 mm | |
| Horizontal busbar capacity | 80 × 10 mm, 60 × 30 mm or 50 × 50 mm | |
| Vertical busbar capacity | 80 × 10 mm, 60 × 30 mm or 50 × 50 mm | |
| Protection rating | IP20 | |
| Dimensions (H × W × D) | 126 × 104 × 45 mm | |
| Product weight | 0.66 kg | |
| Standard | IEC 61869-2 | |
| GTIN / EAN | 8012542804154 | |
| Pack quantity | 1 piece | |
| Product group | Metering Accessories |
The ABB CT1M-6 250 is a through-primary current transformer used to convert a rated primary current of 250 A into a proportional 5 A secondary current for compatible electrical metering and measuring equipment.
The CT1M-6 250 has a rated transformation ratio of 250/5 A.
The CT1M-6 250 has a best accuracy class of 0.5, with rated burdens of 1.5 VA at class 0.5, 2.5 VA at class 1 and 3.75 VA at class 3.
The CT1M-6 frame accepts cables up to 65 mm diameter and horizontal or vertical busbars up to 80 × 10 mm, 60 × 30 mm or 50 × 50 mm.
The ABB order code for the CT1M-6 250 current transformer is 2CSG280415R1000.