Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB CT1M-4 600 2CSG280405R1000 is a 600 A/5 A class 0.5 closed-core through-primary current transformer designed for accurate indirect electrical metering and measurement applications.
£43.56
The ABB CT1M-4 600, order code 2CSG280405R1000, is a 600 A/5 A closed-core through-primary current transformer designed for indirect measurement of electrical parameters in metering, monitoring and energy management applications. Part of ABB's Metering Accessories range, it transforms a high primary current into a standardised 5 A secondary current for compatible electricity meters, ammeters, multimeters and network measuring instruments.
As part of the ABB CT1M current transformer series, the CT1M-4 600 is designed according to IEC 61869-2. Its through-primary construction allows the monitored cable or busbar to pass through the transformer aperture, providing a robust current sensing solution for electrical distribution panels, switchboards and energy monitoring systems.
With a 600 A rated primary current, 5 A rated secondary current and accuracy class 0.5, the CT1M-4 600 provides a 600:5 transformation ratio for accurate indirect electrical measurement. It offers a rated output of 7.5 VA at class 0.5, 10 VA at class 1 and 12.5 VA at class 3, while accommodating cables up to 31 mm and horizontal busbars up to 40 × 10 mm or 30 × 20 mm.
Current transformers allow meters and measuring instruments to monitor electrical circuits carrying currents above their direct measurement range. The transformer produces a proportional secondary current, allowing electrical parameters to be measured without routing the full primary circuit current through the connected measuring instrument.
The ABB CT1M-4 600 converts a nominal 600 A primary current into a 5 A secondary current. Its class 0.5 accuracy, generous conductor aperture and closed-core through-primary construction make it suitable for accurate indirect current measurement in commercial and industrial electrical distribution, power monitoring and energy management systems.
Tick the specs you need, then view products that match.
| Rated Burden (VA) | 7.5 VA | |
|---|---|---|
| Device Type | Solid-core CT | |
| Rated Primary Current (A) | 600 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 31 mm | |
| Accuracy Class | Class 0.5 | |
| Product group | Metering Accessories | |
| Series | CT1M-4 | |
| Order code / Product ID | 2CSG280405R1000 | |
| Product type | Closed-core through-primary current transformer | |
| Application | Indirect electrical measurement and metering | |
| Rated primary current | 600 A | |
| Rated secondary current | 5 A | |
| Current ratio | 600:5 | |
| Best accuracy class | 0.5 | |
| Rated output, class 0.5 | 7.5 VA | |
| Rated output, class 1 | 10 VA | |
| Rated output, class 3 | 12.5 VA | |
| Overcurrent limiting factor | FS 5 | |
| Rated frequency | 50–60 Hz | |
| Protection rating | IP20 | |
| Construction | Closed-core through-primary current transformer | |
| Number of primary inputs | 1 | |
| Maximum cable diameter | 31 mm | |
| Maximum horizontal busbar | 40 × 10 mm or 30 × 20 mm | |
| Standard | IEC 61869-2 | |
| Dimensions (H × W × D) | 78 × 62 × 40 mm | |
| Weight | 0.47 kg | |
| EAN | 8012542804055 | |
| Pack unit | 1 piece |
The CT1M-4 600 is a current transformer for indirect electrical measurement, converting a nominal 600 A primary current into a standard 5 A secondary current for compatible meters and measuring instruments.
The CT1M-4 600 has a 600 A primary current and 5 A secondary current, providing a transformation ratio of 600:5.
The ABB CT1M-4 600 has a best accuracy class of 0.5 with a rated output of 7.5 VA at class 0.5. It also provides 10 VA at class 1 and 12.5 VA at class 3.
The CT1M-4 format accommodates cables up to 31 mm in diameter and horizontal busbars up to 40 × 10 mm or 30 × 20 mm.
The ABB CT1M current transformer range is designed according to IEC 61869-2 for instrument transformers.
ABB CT1M current transformers provide a dependable solution for converting higher primary currents into standard 5 A secondary signals, supporting accurate indirect electrical measurement in metering, monitoring and energy management installations.
We use cookies