ABB CT1M-4 800 is an IEC 61869-2 through-primary current transformer with an 800/5 A ratio, class 0.5 accuracy and 10 VA class 0.5 burden for indirect electrical measurement.
£43.56
The ABB CT1M-4 800 is a through-primary 800/5 A current transformer designed for indirect measurement of electrical network parameters. Supplied under ABB order code 2CSG280355R1000, it transforms a rated primary current of 800 A into a proportional 5 A secondary current for compatible energy meters, ammeters and multifunction measuring instruments.
Part of ABB's CT1M current-transformer range, the CT1M-4 800 is designed in accordance with IEC 61869-2. It provides a best accuracy class of 0.5, with rated burdens of 10 VA at class 0.5, 10 VA at class 1 and 12.5 VA at class 3, supporting dependable current and energy measurement in commercial and industrial installations.
The CT1M-4 format accommodates cables up to 31 mm and horizontal or vertical busbars up to 40 × 10 mm or 30 × 20 mm. With compact 78 × 62 × 40 mm dimensions, IP20 protection and a rated frequency of 50–60 Hz, the CT1M-4 800 is well suited to switchboards, distribution panels and energy-metering assemblies.
Current transformers allow electrical measuring instruments to monitor circuits carrying currents well beyond their direct-input capability. The ABB CT1M-4 800 converts a rated 800 A primary current into a proportional 5 A secondary current, providing a standardised signal for compatible energy meters, ammeters and multifunction monitoring equipment.
With class 0.5 accuracy available at a substantial 10 VA burden, the CT1M-4 800 is suited to demanding electrical metering and load-monitoring installations. Its through-primary design supports both cables and busbars, while supplied mounting-foot and busbar fixings plus an optional DIN rail adapter provide flexibility when integrating the transformer into new electrical distribution assemblies.
Tick the specs you need, then view products that match.
| Rated Burden (VA) | 10 VA | |
|---|---|---|
| Rated Primary Current (A) | 800 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 31 mm | |
| Accuracy Class | Class 0.5 | |
| Device Type | Solid-core CT | |
| Series | CT1M-4 | |
| ABB order code | 2CSG280355R1000 | |
| Product type | Through-primary current transformer | |
| Rated primary current | 800 A | |
| Rated secondary current | 5 A | |
| Transformation ratio | 800/5 A | |
| Best accuracy class | Class 0.5 | |
| Rated burden at class 0.5 | 10 VA | |
| Rated burden at class 1 | 10 VA | |
| Rated burden at class 3 | 12.5 VA | |
| Rated frequency | 50–60 Hz | |
| Maximum cable diameter | 31 mm | |
| Horizontal busbar capacity | 40 × 10 mm or 30 × 20 mm | |
| Vertical busbar capacity | 40 × 10 mm or 30 × 20 mm | |
| Protection rating | IP20 | |
| Dimensions (H × W × D) | 78 × 62 × 40 mm | |
| Product weight | 0.48 kg | |
| Standard | IEC 61869-2 | |
| GTIN / EAN | 8012542803553 | |
| Pack quantity | 1 piece | |
| Product group | Metering Accessories |
The ABB CT1M-4 800 is a through-primary current transformer used to convert a rated primary current of 800 A into a proportional 5 A secondary current for compatible electrical metering and measuring equipment.
The CT1M-4 800 has a rated transformation ratio of 800/5 A.
The CT1M-4 800 has a best accuracy class of 0.5, with rated burdens of 10 VA at class 0.5, 10 VA at class 1 and 12.5 VA at class 3.
The CT1M-4 format accepts cables up to 31 mm diameter and horizontal or vertical busbars measuring up to 40 × 10 mm or 30 × 20 mm.
The ABB order code for the CT1M-4 800 current transformer is 2CSG280355R1000.
ABB CT1M current transformers provide standardised 5 A secondary signals for indirect electrical measurement, supporting accurate current monitoring, energy metering and load analysis across commercial and industrial electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.