ABB CT1M-2 150 2CSG280265R1000 is a class 0.5 through-primary current transformer with a 150 A primary rating, 5 A secondary output and 2.5 VA class 0.5 rated output for indirect electrical metering applications.
£28.12
The ABB CT1M-2 150 is a compact and reliable 150/5 A current transformer designed for indirect measurement of electrical network parameters in low-voltage distribution systems. Supplied under ABB order code 2CSG280265R1000, it forms part of the ABB CT1M current transformer series and is designed in accordance with IEC 61869-2.
With a rated primary current of 150 A and a rated secondary current of 5 A, the CT1M-2 150 converts the primary circuit current into a proportional standard secondary signal for compatible electricity meters, ammeters, power analysers and monitoring equipment. Its class 0.5 accuracy and 2.5 VA rated output at class 0.5 support accurate electrical measurement in commercial and industrial installations.
The CT1M-2 150 uses a through-primary design for straightforward integration into electrical distribution equipment. Its compact 65 × 45 × 40 mm construction, IP20 degree of protection and 50–60 Hz rated frequency make it a practical metering accessory for switchboards, distribution panels and energy monitoring systems.
Current transformers allow electrical meters and monitoring instruments to measure circuits carrying currents above their direct-input range. The ABB CT1M-2 150 transforms a primary current of up to 150 A into a proportional 5 A secondary current, allowing compatible equipment to perform indirect measurement of electrical network parameters.
The CT1M range is designed for current measurement in electrical distribution systems. Its through-primary construction enables the primary conductor to pass through the transformer while the standardised secondary output can be connected to suitable metering, measurement and monitoring equipment.
Tick the specs you need, then view products that match.
| Rated Burden (VA) | 2.5 VA | |
|---|---|---|
| Device Type | Solid-core CT | |
| Rated Primary Current (A) | 150 A | |
| Secondary Current / Output | 5 A | |
| Accuracy Class | Class 0.5 | |
| Series | CT1M-2 | |
| ABB order code | 2CSG280265R1000 | |
| Product group | Metering Accessories | |
| Product type | Current transformer | |
| Rated primary current | 150 A | |
| Rated secondary current | 5 A | |
| Transformation ratio | 150/5 A | |
| Best accuracy class | 0.5 | |
| Rated output, class 0.5 | 2.5 VA | |
| Rated output, class 1 | 5 VA | |
| Rated output, class 3 | 5 VA | |
| Rated frequency | 50–60 Hz | |
| Protection rating | IP20 | |
| Mounting type | Through primary | |
| Dimensions (H × W × D) | 65 × 45 × 40 mm | |
| Weight | 0.35 kg | |
| Standard | IEC 61869-2 | |
| EAN | 8012542802655 |
The ABB CT1M-2 150 is a current transformer designed to convert primary circuit current into a proportional 5 A secondary current for indirect electrical metering and network measurement.
The CT1M-2 150 has a rated transformation ratio of 150/5 A, with a 150 A rated primary current and a 5 A rated secondary current.
The ABB CT1M-2 150 provides a best accuracy class of 0.5, with a rated output of 2.5 VA at class 0.5.
The ABB CT1M-2 150 measures approximately 65 × 45 × 40 mm, providing a compact solution for installation within electrical distribution and metering assemblies.
The ABB CT1M current transformer range is designed in accordance with IEC 61869-2, the applicable standard for instrument current transformers.
ABB CT1M current transformers provide dependable conversion of primary currents into standard 5 A secondary signals, supporting accurate indirect measurement in commercial, industrial and electrical distribution applications.