Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Rittal SK3312.130 LCP Rack CW is a scalable chilled-water rack cooling system with up to 30 kW cooling output, EC fan technology, dynamic water-flow control, IP20 protection and flush integration with compatible TS IT enclosures.
The Rittal SK3312.130 Liquid Cooling Package LCP Rack CW is a high-performance chilled-water rack cooling system designed for targeted thermal management of servers and other high-density IT equipment. Its integrated air/water heat exchanger provides a scalable cooling output of up to 30 kW, allowing one or two adjacent server racks to be cooled independently of the surrounding room air.
The LCP draws heated air from the sides at the rear of the server enclosure, passes it through the high-performance heat exchanger and returns cooled air to the front of the rack. Dynamic control of the chilled-water volume flow, infinitely variable EC fan control and redundant air-side temperature sensing help maintain a stable server inlet temperature while minimising unnecessary energy consumption.
The SK3312.130 measures 300 mm wide × 2000 mm high × 1000 mm deep and is designed for flush integration alongside compatible Rittal TS IT enclosures. Supplied with one EC fan module for up to 10 kW cooling, the modular design can be expanded with additional fan modules to achieve 20 kW or 30 kW total cooling output, providing a scalable solution as IT heat loads increase.
High-density servers can generate substantial concentrated heat loads that require cooling close to the equipment. The Rittal SK3312.130 positions an air/water heat exchanger alongside the server rack, drawing heated exhaust air from the rear and returning conditioned air towards the front of the IT equipment. This enclosure-based approach reduces dependence on room-level airflow and helps maintain predictable server inlet temperatures.
The modular EC fan architecture allows cooling capacity to grow with the installation. A single fan module provides up to 10 kW, while additional modules increase total capacity to 20 kW or 30 kW. Continuous control of both airflow and chilled-water volume helps match cooling performance to the actual IT load, while higher chilled-water inlet temperatures can increase opportunities for energy-saving indirect free cooling.
Tick the specs you need, then view products that match.
| Device Type | Wall / door-mounted cooling unit | |
|---|---|---|
| Coil / Supply Voltage | 230 V AC, 1-phase | |
| IP Rating | IP20 | |
| Voltage | 230 V AC | |
| Cooling Output (W) | 10000 W | |
| Manufacturer | Rittal | |
| Series | Liquid Cooling Package LCP Rack CW | |
| Model | SK3312.130 | |
| Alternative article number | 3312130 | |
| Product type | Chilled-water rack cooling unit | |
| Design | Rack cooling | |
| Maximum cooling output | 30 kW | |
| Cooling output with 1 fan module | 10 kW | |
| Cooling output with 2 fan modules | 20 kW | |
| Cooling output with 3 fan modules | 30 kW | |
| Fan modules supplied | 1 | |
| Fan technology | EC | |
| Air throughput at 50 Hz | 4,800 m³/h | |
| Rated operating voltage | 230 V AC, 1~, 50/60 Hz or 400 V AC, 3~, 50/60 Hz | |
| Duty cycle | 100% | |
| Temperature control | Infinitely variable fan control and two-way control valve | |
| Water connection | DN 40, G 1½" external thread | |
| Maximum permissible operating pressure | 10 bar | |
| Water inlet temperature | 15 °C | |
| Colour | RAL 7035 | |
| Suitable enclosure type | TS IT | |
| Installation in bayed enclosure suite | Flush | |
| Width | 300 mm | |
| Height | 2000 mm | |
| Depth | 1000 mm | |
| Dimensions (W × H × D) | 300 × 2000 × 1000 mm | |
| Net weight | 180 kg | |
| Gross weight | 194 kg | |
| EAN | 4028177811676 |
The Rittal SK3312.130 LCP Rack CW supports a maximum cooling output of 30 kW when configured with three fan modules.
The unit is supplied with one EC fan module, providing up to 10 kW cooling output. Additional modules can increase capacity to 20 kW or 30 kW.
The LCP Rack CW uses chilled water through an integrated air/water heat exchanger. The water connection is DN 40 with a G 1½" external thread.
The cooling unit measures 300 mm wide × 2000 mm high × 1000 mm deep and is designed for flush integration alongside compatible Rittal TS IT enclosures.
Yes. The LCP Rack CW supports monitoring of key operating parameters including server temperatures, water temperatures, water flow, cooling output, fan speed and leakage, with direct network connection via SNMP over Ethernet.
Rittal LCP Rack CW solutions combine scalable chilled-water cooling, efficient EC fan technology and intelligent IT-oriented control to provide precise thermal management for high-density server, storage and network infrastructure.
We use cookies