Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
nVent HOFFMAN PCFB1YZ is an exterior-mounted 316L stainless steel continuous flow Type Y and Type Z purge and pressurisation system for protecting electrical equipment in hazardous-location enclosures.
£2,682.75
The nVent HOFFMAN PCFB1YZ is an exterior-mounted continuous flow purge and pressurisation system designed to help protect electrical and electronic equipment installed in hazardous locations. Using a controlled supply of clean, dry air or inert gas, the system first purges potentially hazardous gases or dust from an enclosure and then maintains positive internal pressure to help prevent hazardous external atmospheres from entering.
Designed for Type Y and Type Z pressurisation applications, the PCFB1YZ combines a control unit, calibrated outlet orifice and relief valve to maintain continuous protective flow through the enclosure. Local visual indication provides system status, while a dry contact output enables connection to a remote alarm system when required.
The PCFB1YZ features exterior mounting and uses 316L stainless steel with a brushed finish for excellent corrosion resistance. It operates with a dry, clean air or inert gas supply between 60–115 psi (4–8 bar) and is typically recommended for enclosures with an internal volume of up to 17 ft³.
Purge and pressurisation provides a practical method of protecting electrical equipment installed within hazardous environments. Before normal operation, the enclosure is purged with clean air or inert gas to remove potentially flammable gases or hazardous atmospheres. Positive internal pressure is then maintained so that the surrounding atmosphere is inhibited from entering the enclosure.
The PCFB1YZ uses the continuous flow method, maintaining positive pressure by continuously passing protective gas through the enclosure and controlling the exiting airflow through a calibrated outlet. Type Y pressurisation can permit suitably classified equipment to be used in a higher-risk location, while Type Z pressurisation can permit general-purpose equipment to be used in appropriate Division 2 or Zone 2 applications when the complete installation satisfies the applicable certification and safety requirements.
Tick the specs you need, then view products that match.
| Material | Stainless Steel 316 | |
|---|---|---|
| Country of Manufacture | United States | |
| Manufacturer | nVent HOFFMAN | |
| Series / bulletin | HLP | |
| Model | PCFB1YZ | |
| Product type | Purge and pressurisation system | |
| Operation type | Continuous Flow | |
| Mounting type | Exterior | |
| Certification type | Type Y and Type Z | |
| Finish | Brushed | |
| Material thickness | 3.18 mm | |
| Protective gas supply | Dry, clean air or inert gas | |
| Supply pressure | 60–115 psi (4–8 bar) | |
| Operating temperature | -20 to +55 °C | |
| Recommended enclosure volume | Up to 17 ft³ | |
| System components | Control unit, calibrated outlet orifice and relief valve | |
| Status indication | Local visual indicator | |
| Remote signalling | Dry contact alarm output | |
| Recommended enclosure protection | Type 4, 4X or 12; IP54 recommended minimum | |
| IECEx certification | IECEx SIR.0019X | |
| ATEX certificate | Sira 14ATEX1045X | |
| UL file | E466718 | |
| UPC | 783510271466 | |
| Weight | approx. 2.59 kg |
The PCFB1YZ is a continuous flow purge and pressurisation system used to help protect electrical and electronic equipment installed within enclosures in hazardous locations by maintaining a positive internal pressure.
The PCFB1YZ is designed for Type Y and Type Z pressurisation applications, subject to the requirements and certification of the complete installation.
The system uses a dry, clean air or inert gas supply between 60–115 psi (4–8 bar).
The PCFB1YZ is an exterior-mounted model designed for installation on the outside of a compatible enclosure.
The continuous flow Type Y and Z system is typically recommended for enclosures with an internal volume of up to 17 ft³. Larger enclosures may require longer purging times.
nVent HOFFMAN purge and pressurisation systems provide engineered protection for electrical and electronic equipment in hazardous locations, using controlled protective gas flow, system status monitoring and certified Type Y and Type Z configurations for demanding industrial applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.