Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Rittal DK 7338.321 DET-AC III Slave is a 1 U 19-inch add-on fire extinguishing unit with a 2 l aluminium tank, approximately 1.8 l of FK 5-1-12 extinguishing agent and CAN networking for extending compatible Rittal fire protection systems across bayed IT enclosures.
£4,102.43
The Rittal DK 7338.321 DET-AC III Slave is a compact fire extinguishing add-on unit for protected IT and server enclosures. Designed to operate with a compatible DET-AC III Master or EFD III system, the slave unit provides an additional supply of extinguishing agent for an individual bayed enclosure while detection and activation are controlled by the master system.
For multi-enclosure installations, a DET-AC III Slave can be installed in additional bayed cabinets to extend fire protection across the enclosure suite. Communication between master and slave units is provided through CAN bus networking. When the master system detects a main alarm condition, extinguishing can be activated simultaneously across the connected systems.
The DK 7338.321 occupies just 1 U in a standard 482.6 mm (19-inch) rack and contains a 2 l aluminium tank with approximately 1.8 l of FK 5-1-12 extinguishing agent. The agent is discharged using a propellant cartridge with an integral electrical activation unit, while integrated monitoring indicates an extinguishing-agent loss greater than 15%.
The Rittal DET-AC III Slave enables fire suppression to be extended beyond a single protected cabinet. Each additional slave provides extinguishing agent for its associated enclosure, while detection and control remain centralised through the compatible master system. This architecture provides coordinated fire protection for bayed server and IT cabinets without requiring a completely independent detection system in every enclosure.
The slave unit communicates with the master through CAN networking and incorporates interfaces for alarms, faults, door monitoring and external signalling. In conjunction with a compatible DET-AC III Master, the system can provide coordinated extinguishing for up to five racks in an enclosure suite, making it suitable for critical IT environments requiring scalable enclosure-level fire protection.
Tick the specs you need, then view products that match.
| Material | Steel | |
|---|---|---|
| Manufacturer | Rittal | |
| Series | DET-AC III | |
| Model | DK 7338.321 | |
| Product type | Slave fire extinguishing system / add-on extinguishing unit | |
| Application | Closed, non-accessible IT and server enclosure systems | |
| Rack mounting | 482.6 mm (19-inch) | |
| Rack units | 1 U | |
| Width | 482.6 mm | |
| Height | 44 mm | |
| Depth | 660 mm | |
| Rated operating voltage | 24 V DC | |
| Uninterruptible operation | Approx. 4 hours | |
| Extinguishing agent | FK 5-1-12 | |
| Extinguishing-agent fill volume | Approx. 1.8 l | |
| Tank material | Aluminium | |
| Tank volume | 2 l | |
| Agent discharge | Propellant cartridge with integral electrical activation unit | |
| Extinguishing-agent monitoring | Indication of >15% loss | |
| Maximum protected enclosure volume | 2.8 m³ | |
| Interfaces | Relay outputs, door contact input, CAN master-slave networking, external alarm, manual triggering device, USB and CMC III CAN bus | |
| Voltage output | 24 V DC, max. 500 mA | |
| Operating temperature | 10–40 °C | |
| Storage temperature | -20–65 °C | |
| Battery storage temperature | -15–40 °C | |
| Relative humidity | Up to 96%, non-condensing | |
| Protection rating | IP30 | |
| Enclosure material | Sheet steel | |
| Enclosure colour | RAL 7035 | |
| Front colour | RAL 9005 | |
| Certification | VdS | |
| Net weight | 19 kg | |
| Gross weight | 19.5 kg | |
| Pack quantity | 1 piece | |
| EAN | 4028177699335 | |
| Customs tariff number | 84248970 | |
| ETIM 9 | EC002685 | |
| ECLASS 8.0 | 40040104 |
The DK 7338.321 is an add-on fire extinguishing unit that supplies extinguishing agent to an additional protected enclosure in a compatible Rittal DET-AC III or EFD III fire protection installation.
No. The slave unit requires networking with a compatible master fire detection or extinguishing system, which performs detection and sends the control signal required to activate extinguishing.
The unit contains approximately 1.8 l of FK 5-1-12 extinguishing agent within a 2 l aluminium tank and discharges the agent using a propellant cartridge with an integral electrical activation unit.
The DET-AC III Slave occupies just 1 U and is designed for standard 482.6 mm (19-inch) rack mounting.
Yes. The DK 7338.321 provides CAN bus interfaces for connection to the Rittal CMC III monitoring system, alongside master-slave CAN networking and relay interfaces for alarms and faults.
Rittal DET-AC III Slave systems provide scalable enclosure-level fire suppression for critical server, network and telecommunications infrastructure, combining compact 19-inch installation, monitored extinguishing-agent storage and coordinated master-slave operation.
We use cookies