ABB TA5110-2DI2DOT AC500-eCo V3 digital I/O option board with two 24 V DC digital inputs and two 24 V DC 0.5 A transistor outputs for compact industrial PLC expansion.
The ABB TA5110-2DI2DOT is a compact digital input/output option board designed to expand the I/O capacity of compatible ABB AC500-eCo V3 programmable logic controllers. It combines two 24 V DC digital inputs and two 24 V DC transistor outputs in a single module, providing a space-efficient solution for connecting additional sensors, switches, actuators and other field devices.
Designed for the ABB AC500-eCo V3 automation platform, the TA5110-2DI2DOT supports both sink and source configurations for its two digital inputs. The two transistor outputs provide solid-state switching for 24 V DC loads and are rated at 0.5 A per channel for resistive loads, making the board suitable for compact machinery and industrial automation applications.
The TA5110-2DI2DOT uses a removable 7-pin spring terminal block with 3.50 mm pitch. Its internal circuitry is powered through the connected CPU, while a separate 24 V DC process supply is connected through the UP and ZP terminals for the transistor outputs. This combined input and output arrangement provides convenient local I/O expansion without requiring a separate external I/O module.
Combined digital I/O option boards allow a PLC to monitor additional field signals and control additional devices without installing a separate external I/O module. The ABB TA5110-2DI2DOT provides two input channels for receiving 24 V DC signals and two transistor output channels for switching suitable DC loads according to the PLC control program.
The digital inputs can be configured for source or sink operation, providing flexibility when integrating switches and sensors. The solid-state transistor outputs are well suited to applications requiring frequent switching. Because the outputs are not internally protected against short circuits or overload, suitable external output protection should be incorporated into the control system.
Tick the specs you need, then view products that match.
| Number of I/O | 4 | |
|---|---|---|
| Product Series | ABB AC500 | |
| Device Type | Digital I/O Module | |
| Coil / Supply Voltage | 20.4–28.8 V DC | |
| Digital Inputs | 2 | |
| Digital Outputs | 2 | |
| Output Type | Transistor | |
| Signal Type / Function | Digital | |
| Manufacturer | ABB | |
| Series | AC500-eCo V3 | |
| Model | TA5110-2DI2DOT | |
| ABB order code | 1SAP187000R0003 | |
| Product type | Digital I/O option board | |
| Digital inputs | 2 | |
| Digital input voltage | 24 V DC | |
| Input identification | I0 and I1 | |
| Input configuration | Sink or source | |
| Digital outputs | 2 | |
| Output type | Transistor | |
| Rated output voltage | 24 V DC | |
| Nominal output current | 0.5 A per channel, resistive | |
| Output identification | O0 and O1 | |
| Process supply | 24 V DC via UP / ZP | |
| Connection | Removable 7-pin spring terminal block | |
| Terminal pitch | 3.50 mm | |
| Terminal 1 | COM 0..1 | |
| Terminal 2 | I0 | |
| Terminal 3 | I1 | |
| Terminal 4 | O0 | |
| Terminal 5 | O1 | |
| Terminal 6 | UP, +24 V DC process supply | |
| Terminal 7 | ZP, 0 V DC process supply | |
| CPU supply current consumption | 10 mA | |
| Output protection | External fuse required | |
| System compatibility | Compatible ABB AC500-eCo V3 CPU modules | |
| HS Code | 85389091 | |
| Country of Manufacture | Germany |
The TA5110-2DI2DOT is a digital I/O option board used to add two 24 V DC digital inputs and two 24 V DC transistor outputs to compatible ABB AC500-eCo V3 PLC systems.
The option board provides two digital inputs and two transistor digital outputs, identified as I0, I1, O0 and O1.
Each transistor output is rated for 24 V DC with a nominal current of 0.5 A per channel for a resistive load.
Yes. The two 24 V DC digital inputs can be used as source inputs or sink inputs, providing flexibility when connecting compatible industrial sensors and switching devices.
No. The transistor outputs are not protected against short circuits or overload, so suitable external fuse protection should be provided and the outputs must not be short-circuited or overloaded.
ABB AC500-eCo V3 option boards provide machine builders and automation engineers with a compact way to expand PLC functionality, and the TA5110-2DI2DOT combines two 24 V DC digital inputs with two 0.5 A transistor outputs for flexible industrial machine control.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.